Plan Review Details - Permit 13090805
Plan Review Stops For Permit 13090805
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-01-04 Cont ID  
Sent By shill Date 2014-01-04 Time 12:16 Rev Time 0.00
Received By shill Date 2014-01-04 Time 12:16 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-12-12 Cont ID  
Sent By shill Date 2013-12-12 Time 13:58 Rev Time 0.00
Received By shill Date 2013-12-12 Time 13:58 Sent To  
Notes
2013-12-12 14:06:50***CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 1. THIS PARCEL IS LOCATED IN EXPOSURE C, PLEASE SEE
 DEFINITION AND AERIAL, FBC 1609. PLEASE FEEL FREE TO
 CONTACT ME TO DISCUSS.
  
 3RD REVIEW - ENGINEER'S LETTER (JOHN A. HOY, PE) THAT
 THIS IS EXPOSURE B IS ACKNOWLEDGED. PLEASE SEE
 DEFINITIONS IN ASCE7-10; THE LANGUAGE IN THE LETTER
 WHICH ENGINEER HAS USED TO DETERMINE WIND DESIGN
 CRITERIA WAS CHANGED IN ASCE7-05. PLEASE READ
 DEFINITION FOR EXPOSURE C IN ASCE7-10 AND FBC 1609.
  
 IF ENGINEER DOES NOT AGREE, PLEASE HAVE HIM CONTACT ME
 TO DISCUSS. IF ENGINEER AGREES, PLEASE HAVE HIM REVISE
 THE LETTER, SEND VIA EMAIL, AND THE PERMIT WILL BE
 ISSUED WITH PROVISO THAT SHEET C407 BE REVISED AND
 SHEET C407 AND ORIGINAL LETTER SUBMITTED AS A REVISION
 AFTER ISSUANCE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-11-25 Cont ID  
Sent By shill Date 2013-11-25 Time 18:02 Rev Time 0.00
Received By shill Date 2013-11-25 Time 18:02 Sent To  
Notes
2013-11-25 18:04:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THIS PARCEL IS LOCATED IN EXPOSURE C, PLEASE SEE
 DEFINITION AND AERIAL, FBC 1609. PLEASE FEEL FREE TO
 CONTACT ME TO DISCUSS.
  
 2. SHOP DRAWINGS ARE PREPARED BY AN ENGINEER. IF THEY
 ARE TO BE INCLUDED IN THE PERMIT PACKAGE, PLEASE
 PROVIDE ORIGINALS, FS471.
  
 3. SHEET 407 IS SIGNED BUT NOT SEALED, FS471.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-10-16 Cont ID  
Sent By shill Date 2013-10-16 Time 13:25 Rev Time 0.00
Received By shill Date 2013-10-16 Time 13:25 Sent To  
Notes
2013-10-16 13:27:30****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A STRUCTURAL DETAIL FOR PROPOSED WALL, FBC
 1609. THIS IS TO BE PREPARED, SIGNED AND SEALED BY A
 DESIGN PROFESSIONAL AND IS TO INCLUDE WIND DESIGN
 CRITERIA FBC 1603.1.4.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-01-04 Cont ID  
Sent By shill Date 2014-01-04 Time 12:16 Rev Time 0.00
Received By shill Date 2014-01-02 Time 15:39 Sent To  
Notes
2014-01-02 15:40:40SENT TO SHILL DESK.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-12-12 Cont ID  
Sent By shill Date 2013-12-12 Time 14:06 Rev Time 0.00
Received By shill Date 2013-12-05 Time 18:26 Sent To  
Notes
2013-12-05 18:26:55TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-11-25 Cont ID  
Sent By shill Date 2013-11-25 Time 18:04 Rev Time 0.00
Received By shill Date 2013-10-21 Time 12:09 Sent To  
Notes
2013-10-21 12:09:54SENT TO ZONING BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-16 Cont ID  
Sent By shill Date 2013-10-16 Time 13:27 Rev Time 0.00
Received By shill Date 2013-09-26 Time 07:25 Sent To  
Notes
2013-09-26 07:26:34SENT TO ZONING BOX.

Review Stop Z ZONING
Rev No 2 Status P Date 2013-11-20 Cont ID  
Sent By eschneid Date 2013-11-20 Time 17:16 Rev Time 0.50
Received By eschneid Date 2013-10-22 Time 15:51 Sent To B
Notes
2013-11-20 17:17:20PASSED W/PROVISO
  
  
 PRIOR TO FINAL (104) INSPECTION, PROVIDE REVISED PLANS
 SHOWING ACCURATE WALL LOCATION.
  
  
  
  
2013-10-22 16:35:42ESCHNEID

Review Stop Z ZONING
Rev No 1 Status F Date 2013-10-15 Cont ID  
Sent By eschneid Date 2013-10-15 Time 16:22 Rev Time 0.25
Received By eschneid Date 2013-09-27 Time 10:12 Sent To B
Notes
2013-10-15 16:25:42FAILED
  
 1) PLEASE VERIFY THE EXTENT OF THE WALL BEING
 INSTALLED.
  
 2) PLEASE INDICATE THE SET BACK OF THE WALL IN THE
 LOCATION THAT IT IS REQUIRED TO COMPLY WITH THE
 RESTRICTION IN ORB 2739 PG 1252.
  
 3) THE PLANS STATE THAT THE WALL DETAILS ARE SHOWN ON
 SHEET C-406. THIS SHEET WAS NOT PROVIDED WITH THE
 PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2013-09-27 10:12:41GIVEN TO ES