Plan Review Details - Permit 13090771
Plan Review Stops For Permit 13090771
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2013-10-11 Cont ID  
Sent By rmcdouga Date 2013-10-11 Time 15:17 Rev Time 0.00
Received By rmcdouga Date 2013-10-11 Time 14:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-10-09 Cont ID  
Sent By rmcdouga Date 2013-10-09 Time 18:05 Rev Time 0.00
Received By rmcdouga Date 2013-10-09 Time 18:05 Sent To  
Notes
2013-10-09 18:14:302010 FBC
  
 DENIED BY BUILDING
  
 1) THE RAS 117 CALCULATIONS THAT WERE SUBMITTED FOR
 PUBLIC RECORD ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ENGINEER. FLORIDA STATUTES 471 AND FAC 61G15-23.002
 THE ONES THAT WERE SUBMITTED ARE NOT SEALED AND ARE NOT
 ORIGINAL SIGNATURES.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-10-03 Cont ID  
Sent By jwitmer Date 2013-10-03 Time 08:45 Rev Time 0.00
Received By jwitmer Date 2013-10-03 Time 08:45 Sent To  
Notes
2013-10-03 08:51:09BUILDING PLAN REVIEW
 PERMIT: 13090771
 ADD: 342 ORANGE WAY
 CONT: FLORIDA QUALITY ROOFING
 TEL: (954)458-6095
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: OCT. 03/2013
 ACTION: DENIED
  
 1) THE PRODUCT APPROVAL FL 9487-R2 SYSTEM # W-6 MPD OF
 -75.0 PSFLIMITATION # 4 ALLOWS FOR ENHANCED FASTENING
 BY EITHER AN ENGINEER OR ARCHITECT USING RAS 117
 CALCULATIONS, CONSIDEERED A "C" EXPOSURE WITH -95.7 PSF
 PRESSURE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-09-25 Cont ID  
Sent By shill Date 2013-09-25 Time 10:57 Rev Time 0.00
Received By shill Date 2013-09-25 Time 10:57 Sent To  
Notes
2013-09-25 10:59:37****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC 2010 RESIDENTIAL 301
  
 1. SEE ITEM 4 ON WHAT APPEARS TO BE APPENDIX PAGE 1.
 ENHANCED FASTENING TO BE DETERMINED BY A QUALIFIED
 DESIGN PROFESSIONAL.
  
 2. PRODUCT APPROVAL IS ILLEGIBLE. SUBMIT TWO LEGIBLE
 COPIES FOR REVIEW. FBC 107
  
 3. CONTRACTOR STATES THAT SYSTEM TYPE E IS PROPOSED. I
 AM UNABLE TO LOCATE THIS ON THE PRODUCT APPROVAL SHEETS
 SUBMITTED. FBC 107. PROPOSED ENHANCED FASTENING
 PROPOSED NOT REVIEWED AS IT IS NOT CLEAR WHICH SYSTEM
 IS TO BE INSTALLED.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-09 Cont ID  
Sent By rmcdouga Date 2013-10-09 Time 18:06 Rev Time 0.00
Received By rmcdouga Date 2013-10-07 Time 13:02 Sent To  
Notes
2013-10-09 13:02:38TO MCDOUGAL