| 2013-10-26 14:08:09 | BUILDING PLAN REVIEW |
| | PERMIT:13090696 |
| | ADD: 1875 PALM BEACH LAKES BLDG "A" |
| | CONT: TO BE DETERMINED |
| | TEL: |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: OCT. 26/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) ) PB OUTLET MALLS:A LETTER FROM THE QUALIFIER OF |
| | BOTH THE SHELL CONTRACTOR (EMJ CORPORATION) AND TENANT |
| | BUILD-OUT CONTRACTOR MUST BE PROVIDED BEFORE TENANT |
| | BUILD-OUT PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT |
| | CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK |
| | HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY |
| | WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE |
| | DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND |
| | NOTARIZED. |
| | |
| | 2) THIS JOB WILL REQUIRE A RESIDENT INSPECTOR SINCE |
| | TILT-UP CONSTRUCTION AND BEING TYPE II CONSTRUCTION. |
| | PLEASE CONTACT THE MANAGER OF THE RESIDENT INSPECTOR |
| | PROGRAM KEN CONRAD FOR THE REQUIRED INFORMATION AND |
| | PAPERWORK THAT WILL NEED TO BE FILED. 110.3.9. 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 2012 |
| | KEN CONRAD MANAGER OF RESIDENT INSPECTOR PROGRAM |
| | TEL: (561) 805-6666 |
| | E-MAIL: [email protected] |
| | THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE MADE |
| | BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109. |
| | HE/SHE MAY ACCEPT REPORTS OF INSPECTORS |
| | OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER |
| | INVESTIGATION HE/SHE IS SATISFIED AS TO |
| | THEIR QUALIFICATIONS AND RELIABILITY. A CERTIFICATE |
| | CALLED FOR BY ANY PROVISION OF THE TECHNICAL |
| | CODES SHALL NOT BE BASED ON SUCH REPORTS UNLESS THE |
| | SAME ARE IN WRITING AND CERTIFIED BY A |
| | RESPONSIBLE OFFICER OF SUCH SERVICE. |
| | |
| | 3) WITH THE REQUIREMENT OF A RESIDENT INSPECTOR, (3) |
| | SETS OF PLANS AND DOCUMENTS WILL BE REQUIRED BEFORE |
| | PERMIT ISSUANCE. ONE FOR THE FIELD, ONE FOR THE |
| | RESIDENT INSPECTOR AND ONE ON FILE WITHIN THE BUILDING |
| | DEPARTMENT. |
| | |
| | 4) MISSING SOILS REPORT BY ECS COMPLETED JUNE 16/2012 |
| | PROJECT # 25-1847-C. 1803.5.2 QUESTIONABLE SOIL. |
| | |
| | 5) COVER-SHEET PLANS INDICATE THE OCCUPANT LOAD AND THE |
| | REQUIRED EGRESS WIDTH PER OCCUPANT AT 0.2" / OCCUPANT |
| | FBC-B 1005.1 BUT THE PLANS LACK WHAT WIDTH IS PROVIDED |
| | NOR WIDTH REQUIRED. |
| | |
| | 6) SHEET A112 THE LIFE SAFETY SHEET FOR TENANT SPACE A3 |
| | THE OCCUPANT LOAD IS 1170, THE REQUIRED DOOR WIDTH OF |
| | 19.5' IS MET WITH 21' PROVIDED, THE ISSUE IS BECAUSE OF |
| | THE OCCUPANT LOAD BEING OVER 1000 FBC-B TABLE 1021.1 |
| | REQUIRES 4 EXITS. |
| | |
| | 7) S002 DETAIL #7 INDICATES THE USE OF 5/8 INCH CDX |
| | PLYWOOD , THIS A TYPE IIB BUILDING 603.1.1 ONLY ALLOWS |
| | FOR THE USE OF FIRE RETARDANT TREATED PLYWOOD. |
| | |
| | 8) SHEET S004 DETAIL FOR FOUNDATION EMBEDS INDICATES |
| | THE USE OF EMBEDS FOR TILT-WAL CONSTRUCTION BUT S-101 |
| | DOES NOT PROVIDE THE LOCATION WHERE THE EMBEDS ARE TO |
| | BE PLACED. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. |
| | THE EMBEDS ARE PART OF THE MWFRS MAIN WIND FORCE |
| | RESISTING SYSTEM. |
| | |
| | 9) SHEET A141; |
| | A/C UNIT # 6 IS WITH IN 10'-0 OF THE EDGE OF THE ROOF |
| | FBC-B 1013.5 MECHANICAL EQUIPMENT. |
| | GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT, |
| | FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT |
| | REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF |
| | A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH |
| | EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 |
| | MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD |
| | SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A |
| | SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL |
| | EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END |
| | OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT. |
| | |
| | 10) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 11) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS., ROLL UP, SWING, SLIDING, |
| | METAL, LOUVER |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES AND ROOFING |
| | INSULATION |
| | (E) |
| | (F) SKYLIGHTS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 12) FOR EACH OF THE VARIOUS PRODUCT APPROVALS LISTED |
| | ABOVE PLEASE INDICATE WHICH TYPE OF GLAZING, OR ROOFING |
| | SUBSYSTEM IS TO BE INSTALLED, CIRCLE TO IDENTIFY THE |
| | SYSTEM, AND ASSOCIATED PRESSURES. |
| | |
| | 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |