Plan Review Details - Permit 13090696
Plan Review Stops For Permit 13090696
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-11-30 Cont ID  
Sent By jwitmer Date 2013-11-30 Time 15:41 Rev Time 0.00
Received By jwitmer Date 2013-11-30 Time 14:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-10-26 Cont ID  
Sent By jwitmer Date 2013-10-26 Time 14:27 Rev Time 0.00
Received By jwitmer Date 2013-10-26 Time 13:07 Sent To  
Notes
2013-10-26 14:08:09BUILDING PLAN REVIEW
 PERMIT:13090696
 ADD: 1875 PALM BEACH LAKES BLDG "A"
 CONT: TO BE DETERMINED
 TEL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: OCT. 26/ 2013
 ACTION: DENIED
  
 1) ) PB OUTLET MALLS:A LETTER FROM THE QUALIFIER OF
 BOTH THE SHELL CONTRACTOR (EMJ CORPORATION) AND TENANT
 BUILD-OUT CONTRACTOR MUST BE PROVIDED BEFORE TENANT
 BUILD-OUT PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 2) THIS JOB WILL REQUIRE A RESIDENT INSPECTOR SINCE
 TILT-UP CONSTRUCTION AND BEING TYPE II CONSTRUCTION.
 PLEASE CONTACT THE MANAGER OF THE RESIDENT INSPECTOR
 PROGRAM KEN CONRAD FOR THE REQUIRED INFORMATION AND
 PAPERWORK THAT WILL NEED TO BE FILED. 110.3.9. 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 2012
 KEN CONRAD MANAGER OF RESIDENT INSPECTOR PROGRAM
 TEL: (561) 805-6666
 E-MAIL: [email protected]
 THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE MADE
 BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109.
 HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO
 THEIR QUALIFICATIONS AND RELIABILITY. A CERTIFICATE
 CALLED FOR BY ANY PROVISION OF THE TECHNICAL
 CODES SHALL NOT BE BASED ON SUCH REPORTS UNLESS THE
 SAME ARE IN WRITING AND CERTIFIED BY A
 RESPONSIBLE OFFICER OF SUCH SERVICE.
  
 3) WITH THE REQUIREMENT OF A RESIDENT INSPECTOR, (3)
 SETS OF PLANS AND DOCUMENTS WILL BE REQUIRED BEFORE
 PERMIT ISSUANCE. ONE FOR THE FIELD, ONE FOR THE
 RESIDENT INSPECTOR AND ONE ON FILE WITHIN THE BUILDING
 DEPARTMENT.
  
 4) MISSING SOILS REPORT BY ECS COMPLETED JUNE 16/2012
 PROJECT # 25-1847-C. 1803.5.2 QUESTIONABLE SOIL.
  
 5) COVER-SHEET PLANS INDICATE THE OCCUPANT LOAD AND THE
 REQUIRED EGRESS WIDTH PER OCCUPANT AT 0.2" / OCCUPANT
 FBC-B 1005.1 BUT THE PLANS LACK WHAT WIDTH IS PROVIDED
 NOR WIDTH REQUIRED.
  
 6) SHEET A112 THE LIFE SAFETY SHEET FOR TENANT SPACE A3
 THE OCCUPANT LOAD IS 1170, THE REQUIRED DOOR WIDTH OF
 19.5' IS MET WITH 21' PROVIDED, THE ISSUE IS BECAUSE OF
 THE OCCUPANT LOAD BEING OVER 1000 FBC-B TABLE 1021.1
 REQUIRES 4 EXITS.
  
 7) S002 DETAIL #7 INDICATES THE USE OF 5/8 INCH CDX
 PLYWOOD , THIS A TYPE IIB BUILDING 603.1.1 ONLY ALLOWS
 FOR THE USE OF FIRE RETARDANT TREATED PLYWOOD.
  
 8) SHEET S004 DETAIL FOR FOUNDATION EMBEDS INDICATES
 THE USE OF EMBEDS FOR TILT-WAL CONSTRUCTION BUT S-101
 DOES NOT PROVIDE THE LOCATION WHERE THE EMBEDS ARE TO
 BE PLACED. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
 THE EMBEDS ARE PART OF THE MWFRS MAIN WIND FORCE
 RESISTING SYSTEM.
  
 9) SHEET A141;
 A/C UNIT # 6 IS WITH IN 10'-0 OF THE EDGE OF THE ROOF
 FBC-B 1013.5 MECHANICAL EQUIPMENT.
 GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT,
 FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT
 REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF
 A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH
 EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762
 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD
 SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A
 SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL
 EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END
 OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT.
  
 10) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 11) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS., ROLL UP, SWING, SLIDING,
 METAL, LOUVER
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES AND ROOFING
 INSULATION
 (E)
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
  
 12) FOR EACH OF THE VARIOUS PRODUCT APPROVALS LISTED
 ABOVE PLEASE INDICATE WHICH TYPE OF GLAZING, OR ROOFING
 SUBSYSTEM IS TO BE INSTALLED, CIRCLE TO IDENTIFY THE
 SYSTEM, AND ASSOCIATED PRESSURES.
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-12-03 Cont ID  
Sent By albarran Date 2013-12-03 Time 12:37 Rev Time 0.00
Received By albarran Date 2013-12-03 Time 11:05 Sent To  
Notes
2013-12-03 12:41:58ALL THE PREVIOUSLY REQUESTED ELECTRICAL CORRECTIONS
 HAVE BEEN ADDRESSED, BUT THE NEW ELECTRICAL PAGE E103
 HAS A LIGHTLY GRAYED GENERATOR THAT WAS NOT ON THE
 INITIAL SHEET AND THUS IS BEYOND THE SCOPE OF THIS
 PERMIT.
 THOUGH THE GENERATOR IS NOT IN THE NORMAL DARK PRINT
 NOR IS IT ADDRESSED ON ANY OF THE ELECTRICAL RISER
 DIAGRAMS, A NOTE EXCLUDING IT FROM THE PERMIT WAS
 PLACED ON THE CORRESPONDING PAGES. IF THE GENERATOR
 WILL BE INSTALLED, A REVISION TO THIS OR A STAND ALONE
 PERMIT FOR IT SHALL BE SECURED.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-11-06 Cont ID  
Sent By albarran Date 2013-11-06 Time 14:50 Rev Time 0.00
Received By albarran Date 2013-11-06 Time 13:58 Sent To  
Notes
2013-11-06 15:07:25THOUGH THE SCOPE OF THIS PERMIT IS LIMITED TO SHELL
 STRUCTURE FOR TENANT BUILD-OUT, WHATEVER MINIMUM
 ELECTRIC SERVICE IS BEING PROVIDED SHALL BE DESCRIBED
 AND THUS PRESENTED ON THE PLANS FOR REVIEW.
 PG. E001 REFLECTS PANEL HVA (NEW) & PANEL LVA (NEW)
 SERVICED FROM TRANSFORMER #3 AND PAGE E002 SHOWS THREE
 DIFFERENT RISER DIAGRAMS INDICATING THEIR RESPECTIVE
 TERMINATIONS, BUT NO PANEL SCHEDULES ARE PROVIDED FOR
 EACH.
 PLEASE MAKE THE APPROPRIATE CORRECTIONS AND RESUBMIT
 FOR REVIEW.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-12-03 Cont ID  
Sent By scaldero Date 2013-12-03 Time 14:39 Rev Time 0.00
Received By scaldero Date 2013-12-03 Time 14:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-10-31 Cont ID  
Sent By scaldero Date 2013-10-31 Time 16:06 Rev Time 0.00
Received By scaldero Date 2013-10-31 Time 16:00 Sent To  
Notes
2013-10-31 16:04:34PERMIT #13090696
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 **** FAIL COMMENTS********
 1) SHEET A112, TENANT SPACE A3: PER NFPA 101, 7.4.1.2
 (2) - REQUIRES NOT LESS THAN FOUR (4) MEANS OF EGRESS
 WHERE THE OCCUPANT LOAD EXCEEDS 1000 PERSONS.
  
 2) EGRESS WIDTH NOT PROVIDED ON PLANS.
  
 ****PROVISO*******
 PLAN SUBMITTED IS FOR BUILDING SHELL, ONLY. ADDITIONAL
 REQUIREMENTS MAY NEED TO BE MET UPON REVIEW OF TENAT
 LAYOUT/PLANS.
  
 ADDITIONAL FIRE EXTINGUISHERS MAY BE NEEDED PENDING
 FIELD INSPECTION.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shill Date 2014-06-03 Time 12:09 Sent To  
Notes
2014-06-03 12:10:11STORE FRONT SHOPS (2 SUBMITTALS) ROUTED TO JW DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-02-12 Cont ID  
Sent By shill Date 2014-02-12 Time 13:37 Rev Time 0.00
Received By shill Date 2013-12-20 Time 08:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-11 Cont ID  
Sent By rregueir Date 2013-12-11 Time 14:33 Rev Time 0.00
Received By rregueir Date 2013-11-20 Time 17:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-12 Cont ID  
Sent By shill Date 2013-11-06 Time 17:25 Rev Time 0.00
Received By shill Date 2013-09-26 Time 07:30 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2013-12-04 Cont ID  
Sent By jwitmer Date 2013-12-04 Time 07:56 Rev Time 0.00
Received By jwitmer Date 2013-12-04 Time 07:56 Sent To  
Notes
2013-12-04 07:58:15P. B. CTY IMPACT FEE OFFICE:
 PLANS STAMPED NO FEES DUE
 RE: MU-2013-024546-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-11-30 Cont ID  
Sent By jwitmer Date 2013-11-30 Time 15:25 Rev Time 0.00
Received By jwitmer Date 2013-11-30 Time 15:25 Sent To  
Notes
2013-11-30 15:26:00BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-10-26 Cont ID  
Sent By jwitmer Date 2013-10-26 Time 13:07 Rev Time 0.00
Received By jwitmer Date 2013-10-26 Time 13:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-11-06 Cont ID  
Sent By rregueir Date 2013-11-06 Time 10:36 Rev Time 0.00
Received By rregueir Date 2013-11-06 Time 10:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-10-28 Cont ID  
Sent By lwagner Date 2013-10-28 Time 10:54 Rev Time 0.00
Received By lwagner Date 2013-10-28 Time 10:35 Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2013-11-21 Time   Rev Time 0.00
Received By   Date 2013-11-21 Time   Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2013-11-30 Cont ID  
Sent By jwitmer Date 2013-11-30 Time 15:26 Rev Time 0.00
Received By jwitmer Date 2013-11-30 Time 15:26 Sent To  
Notes
2013-11-30 15:40:46BUILDING PROVISO ROOFING:
 A SEPERATE ROOFING PERMIT, REVIEW WITH ASSOCIATED FEES
 WILL BE REQUIRED.
 SUBMITTED NOA 12-0625.02
 FIRESTONE ULTRA PLY TPO & TPO XR SINGLE PLY ROOF
 SYSTEMS OVER STEEL DECKS.
 NO SUB-SYSTEM IS HIGHLIGHTED. A-141- A-143 ROOF DECK
 INDICATES THE USE OF A FFIRESTONE SINGLE PLY SYSTEM,
 THE PERIMETER (ZONES 2 & 3) TO BE FULLY ADHERED, THE
 INTERIOR ZONE # 1 TO BE MECHANICALLY FASTENED. NONE OF
 THE SUB-SYSTEMS LISTED IN THE 63 PAGE REPORT ARE
 IDENTIFIED. PLEASE NOTE BOTH LIMITATION # 7 AND
 LIMITATION # 9 BOTH OCCUR IN THIS REPORT. WHEN THE
 SUB-SYSTEMS ARE IDENTIFIED AND IF LIMITATION #7 DOES
 REQUIRE ENHANCED FASTENING IN ZONES 2 & 3 A DESIGN
 PROFESSIONAL WILL NEED TO PRODUCE THE FASTENING
 SCHEDULE USING RAS 117.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2013-11-30 Cont ID  
Sent By jwitmer Date 2013-11-30 Time 15:26 Rev Time 0.00
Received By jwitmer Date 2013-11-30 Time 15:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2014-02-12 Cont ID  
Sent By shill Date 2014-02-12 Time 13:37 Rev Time 0.00
Received By shill Date 2014-02-12 Time 13:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2014-02-05 Cont ID  
Sent By eschneid Date 2014-02-05 Time 19:34 Rev Time 2.00
Received By eschneid Date 2014-02-05 Time 19:34 Sent To  
Notes
2014-02-05 20:09:00PASSED W/PROVISO
  
 1) ALL ROOFTOP MECHANICAL EQUIPMENT SHALL BE SCREENED
 PER THE DESIGN GUIDELINES. SHEET A-106 SHOWS ROOFTOP
 UNITS THAT ARE NOT SCREENED.
  
 2) BAY A1 HAS A DOORWAY ON THE SOUTH FACADE THAT DOES
 NOT SHOW UP ON ALL THE PLANS, INCLUDING ELEVATIONS.
 REVISED PLANS SHOWING SAME CONDITION REQUIRED PRIOR TO
 C.O.
  
 3) SEPARATE PERMITS, WITH PLANS, FOR SITE FURNITURE,
 BICYCLE RACKS, GENERATOR, SIGNS AND AWNINGS ARE
 REQUIRED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
2014-01-09 11:07:291/9/14

Review Stop Z ZONING
Rev No 2 Status F Date 2013-12-11 Cont ID  
Sent By eschneid Date 2013-12-11 Time 13:10 Rev Time 1.00
Received By eschneid Date 2013-12-11 Time 13:10 Sent To  
Notes
2013-12-11 14:02:02FAILED
  
 1) SHEETS A102 AND A103 WERE NOT CORRECTED TO REFLECT
 THE FINAL GENERATOR LOCATION.
  
 2) THE FOOTPRINT OF BUILDING A HAS CHANGED ON THE MOST
 RECENT PLANS RECEIVED BY THE ZONING DIVISION ON
 NOVEMBER 20, 2013 AS PART OF THE LATEST REVISED MINOR
 PD AMENDMENT. THE PERMIT PLANS SHALL MATCH THESE PLANS.
 ALL PLANS SHALL AGREE - FLOOR PLANS, ELEVATIONS, ROOF
 PLANS, SIDEWALK PLANS, ETC.
  
 3) SEPARATE PERMITS FOR GENERATOR, SIGNS AND AWNINGS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
2013-12-02 11:32:1512/2/13

Review Stop Z ZONING
Rev No 1 Status F Date 2013-11-06 Cont ID  
Sent By eschneid Date 2013-11-06 Time 12:05 Rev Time 2.00
Received By eschneid Date 2013-11-06 Time 12:05 Sent To  
Notes
2013-11-06 17:47:10FAILED
  
 1) THE GENERATOR ADJACENT TO TENANT A5 IS NOT SHOW ON
 SITE PLAN APPROVED LOCATION, NOR IS IT SHOWN WITH THE
 REQUIRED SCREEN ENCLOSURE.
  
 2) THE SITE LINE DRAWINGS WERE NOT INCLUDED TO VERIFY
 THE ROOFTOP EQUIPMENT SCREENING.
  
 3) PROVIDE A LINE OF SIGHT DRAWING FROM THE NORTH
 PROPERTY LINE.
  
 4) THE SUBMITTED ELEVATIONS ARE NOT THE APPROVED
 ELEVATIONS - DATED 9/25/13, WHICH SHOW WRAPPED PARAPET
 DETAILS.
  
 5) SEPARATE PERMITS FOR GENERATOR, SIGNS AND AWNINGS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2013-10-30 15:15:0810/29/13