Plan Review Details - Permit 13090695
Plan Review Stops For Permit 13090695
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2014-05-01 Cont ID  
Sent By shill Date 2014-05-01 Time 09:02 Rev Time 0.00
Received By shill Date 2014-05-01 Time 09:02 Sent To  
Notes
2014-05-01 09:02:51STOREFRONT SHOP DRAWINGS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-04-14 Cont ID  
Sent By jwitmer Date 2014-04-14 Time 06:44 Rev Time 0.00
Received By jwitmer Date 2014-04-14 Time 05:55 Sent To  
Notes
2014-04-14 06:23:55BUILDING PLAN REVIEW
  
 PERMIT: 13090695
 SUBMITTAL:REV # 3 SHOP DRAWINGS/ EXTERIOR METAL STUDS &
 CANOPY FRAMING
 ADD: 1845 PALM BEACH LAKES SHELL C- WHOLE FOODS
 CONT: EMJ
 TEL: (561)373-3902
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE:MONDAY APRIL 14/2014
 ACTION:REVIEWED/ APPROVED
  
 WEST PALM BEACH OUTLET CENTER MALL
 BUILDING "C"
 SHOP DRAWINGS FOR THE EXTERIOR METAL STUD WALL & CANOPY
 FRAMING DESIGN
  
 PROVISO: WITHIN THIS REPORT ANY REFERANCE TO THE USE OF
 1.00 DIA. VERSAPIN GRIPSHANK FASTENERS FOR 1/2 INCH
 SHEATHING IS "VOID". NOT ENOUGH PENETRATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-03-24 Cont ID  
Sent By jwitmer Date 2014-03-24 Time 08:15 Rev Time 0.00
Received By jwitmer Date 2014-03-24 Time 07:20 Sent To  
Notes
2014-03-24 08:15:49BUILDING PLAN REVIEW
  
 PERMIT: 13090695
 SUBMITTAL: SHOP DRAWINGS/ EXTERIOR METAL STUDS &
 CANOPY FRAMING
 ADD: 1845 PALM BEACH LAKES SHELL C- WHOLE FOODS
 CONT: EMJ
 TEL: (561)373-3902
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE:MONDAY MARCH 24/2014
 ACTION:DENIED.
  
 1) SUBMITTED EXTERIOR FRAMING SHOP DRAWINGS INDICATE
 THE USE OF EXTERIOR SHEATHING PER ARCHITECTURAL SPECS.
 THE ARCHITECTURAL PLANS (A301) INDICATE THE INSTALATION
 OF 5/8 INCH CDX FIRE RETARDANT TREATED PLYWOOD FOR ALL
 EXTERIOR SHEATHING AND ALL WOOD BLOCKING TO BE FIRE
 RETARDANT TREATED FOR SIGNAGE. THERE IS NO MENTION OF
 THE PLYWOOD BEING REQUIRED ON THE SKETCHES, FIRE
 RETADANT TREATED PLYWOOD, 2010 FBC-B 603.1 EXCEPTION #
 1.2 DOES ALLOW FOR THE USE OF FIRE RETARDANT TREATED
 PLYWOOD ON EXTERIOR NON-BEARING WALLS WHERE THERE IS NO
 FIRE RATING REQUIRED.
  
  
 2) THE SECOND ISSUE SKETCH SK-3.00 INDICATES THE 5/8
 INCH EXTERIOR PLYWOOD TO BE FASTENED WITH 0.100 DIA.
 VERSAPIN GRIPSHANK FASTENERS. THE SK-3.00 INDICATES THE
 USE OF 0.100 DIA. VERAPIN GRIPSHANK FASTENERS. PLEASE
 PROVIDE THE SIZE OF THE FASTENER BY DIAMETER AND
 LENGTH. THE 0.100 DIAMETER GUN NAIL IS LESS THAN A
 NUMBER 6 COMMON NAIL PLEASE REVIEW 2010 FBC-B TABLE
 2304.6.1 THIS NAIL WILL NOT MEET THE WINDS FOR 125 MPH
 SINCE IT WILL REQUIRE A 1.5 INCH PENETRATION INTO THE
 FRAMING MEMBER.
  
 3) THE SECOND ISSUE SKETCH SK-3.00 INDICATES THE 5/8
 INCH EXTERIOR PLYWOOD TO BE FASTENED WITH 0.100 DIA.
 VERSAPIN GRIPSHANK FASTENERS. THE SK-3.00 INDICATES THE
 USE OF 0.100 DIA. VERAPIN GRIPSHANK FASTENERS. WHEN
 THESE FASTENERS ARE GOING TO BE FASTENING INTO FIRE
 RETARDANT TREATED PLYWOOD THE FASTENERS WILL NEED TO
 COMPLY WITH:
  
 2010 FBC-B 2304.9.5.1 FASTENERS AND CONNECTORS FOR
 PRESERVATIVE-TREATED WOOD.FASTENERS IN CONTACT WITH
 PRESERVATIVE-TREATED WOOD SHALL BE OF HOT-DIPPED
 ZINC-COATED GALVANIZED STEEL, STAINLESS STEEL, SILICON
 BRONZE OR COPPER. FASTENERS OTHER THAN NAILS, TIMBER
 RIVETS, WOOD SCREWS AND LAG SCREWS SHALL BE PERMITTED
 TO BE OF MECHANICALLY DEPOSITED ZINC-COATED STEEL WITH
 COATING WEIGHTS IN ACCORDANCE WITH ASTM B 695, CLASS 55
 MINIMUM. CONNECTORS THAT ARE USED IN EXTERIOR
 APPLICATIONS AND IN CONTACT WITH PRESERVATIVE-TREATED
 WOOD SHALL HAVE COATING TYPES AND WEIGHTS IN ACCORDANCE
 WITH THE TREATED WOOD OR CONNECTOR MANUFACTURER?S
 RECOMMENDATIONS. IN THE ABSENCE OF MANUFACTURER?S
 RECOMMENDATIONS, A MINIMUM OF ASTM A 653, TYPE G185
 ZINC-COATED GALVANIZED STEEL, OR EQUIVALENT, SHALL BE
 USED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-11-22 Cont ID  
Sent By jwitmer Date 2013-11-22 Time 11:45 Rev Time 0.00
Received By jwitmer Date 2013-11-22 Time 11:45 Sent To  
Notes
2013-11-22 11:46:54BUILDING PLAN REVIEW
 PERMIT: 13090695
 ADD: 1845 PALM BEACH LAKES SHELL C- WHOLE FOODS
 CONT: EMJ
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE:NOV. 22/2013
 ACTION:BUILDING PROVISO
  
 1) MISSING RESIDENT INSPECTOR PACKAGE, TILT WALL
 REQUIRES A RESIDENT INSPECTOR. FBC* 109.3.7 RESIDENT
 INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE DOCUMENTS TO KEN
 CONRAD MANAGER OF THE RESIDENT INSPECTOR PROGRAM. A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED, ON THIS
 PROJECT, DUE TO ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II CONSTRUCTION
 -- BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS OF
 CONSTRUCTION / TILT WALL
  
 A HOLD WILL BE PUT ON THE ISSUANCE OF THE PERMIT
 WITHOUT THE RESIDENT INSPECTOR PACKAGE APPROVED BY KEN
 CONRAD.
  
 KEN CONRAD
 TEL 561-805-6666
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-10-26 Cont ID  
Sent By jwitmer Date 2013-10-26 Time 12:57 Rev Time 0.00
Received By jwitmer Date 2013-10-26 Time 10:07 Sent To  
Notes
2013-10-26 12:55:31BUILDING PLAN REVIEW
 PERMIT:13090695
 ADD: 1845 PALM BEACH LAKES BLDG "C" WHOLE FOODS"
 CONT: TO BE DETERMINED
 TEL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: OCT. 26/ 2013
 ACTION: DENIED
  
 1) THE INFORMATION DESCRIBING THIS PROJECT IS NOT CLEAR
 AS TO IF THIS IS A SHELL ONLY PERMIT OR IF THIS IS A
 COMPLETE BUILDING BEING BUILT FOR WHOLE FOODS? THIS
 REVIEW WILL ASSUME IT IS A SHELL PERMIT ONLY!!!
  
 2) PB OUTLET MALLS:A LETTER FROM THE QUALIFIER OF BOTH
 THE SHELL CONTRACTOR (EMJ CORPORATION) AND TENANT
 BUILD-OUT CONTRACTOR MUST BE PROVIDED BEFORE TENANT
 BUILD-OUT PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 3) THIS JOB WILL REQUIRE A RESIDENT INSPECTOR SINCE
 TILT-UP CONSTRUCTION AND BEING TYPE II CONSTRUCTION.
 PLEASE CONTACT THE MANAGER OF THE RESIDENT INSPECTOR
 PROGRAM KEN CONRAD FOR THE REQUIRED INFORMATION AND
 PAPERWORK THAT WILL NEED TO BE FILED. 110.3.9. 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 2012
 KEN CONRAD MANAGER OF RESIDENT INSPECTOR PROGRAM
 TEL: (561) 805-6666
 E-MAIL: [email protected]
 THE BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE MADE
 BY OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109.
 HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO
 THEIR QUALIFICATIONS AND RELIABILITY. A CERTIFICATE
 CALLED FOR BY ANY PROVISION OF THE TECHNICAL
 CODES SHALL NOT BE BASED ON SUCH REPORTS UNLESS THE
 SAME ARE IN WRITING AND CERTIFIED BY A
 RESPONSIBLE OFFICER OF SUCH SERVICE.
  
 4) WITH THE REQUIREMENT OF A RESIDENT INSPECTOR, (2)
 SETS OF PLANS AND DOCUMENTS WILL BE REQUIRED BEFORE
 PERMIT ISSUANCE. ONE FOR THE FIELD, ONE FOR THE
 RESIDENT INSPECTOR.
  
 5) MISSING SOILS REPORT BY ECS COMPLETED JUNE 16/2012
 PROJECT # 25-1847-C. 1803.5.2 QUESTIONABLE SOIL.
  
 6) COVER SHEET INDICATE THE OCCUPANT LOAD AND THE
 REQUIRED EGRESS WIDTH PER OCCUPANT AT 0.2" / OCCUPANT
 FBC-B 1005.1 BUT THE PLANS LACK WHAT WIDTH IS PROVIDED
 NOR WIDTH REQUIRED.
  
 7) S002 DETAIL #7 INDICATES THE USE OF 5/8 INCH CDX
 PLYWOOD , THIS A TYPE IIB BUILDING 603.1.1 ONLY ALLOWS
 FOR THE USE OF FIRE RETARDANT TREATED PLYWOOD.
  
 8) SHEET S004 DETAIL FOR FOUNDATION EMBEDS INDICATES
 THE USE OF EMBEDS FOR TILT-WAL CONSTRUCTION BUT S-101
 DOES NOT PROVIDE THE LOCATION WHERE THE EMBEDS ARE TO
 BE PLACED. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
 THE EMBEDS ARE PART OF THE MWFRS MAIN WIND FORCE
 RESISTING SYSTEM.
  
 9) SHEET A141;
 A) THE ROOF HATCH IS LOCATED WITHIN 10'-0" OF THE EDGE
 OF THE ROOF PLEASE PROVIDE COMPLIANCE WITH FBC-B 1013.6
 ROOF ACCESS.
 GUARDS SHALL BE PROVIDED WHERE THE ROOF HATCH OPENING
 IS LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR
 OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN
 SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE
 FLOOR, ROOF OR GRADE BELOW. THE GUARD SHALL BE
 CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE 21
 INCHES (533 MM) IN DIAMETER.
  
 B) THE RTU-7 LOCATION THE PLANS INDICATE RECEIVING/
 ENCLOSED DOCK, IS THIS A SRIBNERS ERROR?
  
 C) RTU-2 INDICATES EXIT VESTIBULE, PLEASE PROVIDE
 ADDITIONAL INFORMATION, FBC-B 107.2.1.3.
  
 10) SHEET A-601 DOOR SCHEDULE AND FIRE RATINGS PLEASE
 REVIEW 2010 FBC-B TABLE 715.4 IS IN MINUTES & HOURS.
  
 11) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 12) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS., ROLL UP, SWING, SLIDING,
 METAL, LOUVER
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES AND ROOFING
 INSULATION
 (E)
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS
  
 13) FOR EACH OF THE VARIOUS PRODUCT APPROVALS LISTED
 ABOVE PLEASE INDICATE WHICH TYPE OF GLAZING, OR ROOFING
 SUBSYSTEM IS TO BE INSTALLED, CIRCLE TO IDENTIFY THE
 SYSTEM, AND ASSOCIATED PRESSURES.
  
 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-11-01 Cont ID  
Sent By albarran Date 2013-11-01 Time 16:45 Rev Time 0.00
Received By albarran Date 2013-11-01 Time 13:52 Sent To  
Notes
2013-11-01 16:46:22THE SCOPE OF THIS PERMIT IS FOR THE SHELL ONLY

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2013-10-29 Cont ID  
Sent By Mgonzale Date 2013-10-29 Time   Rev Time 0.25
Received By mgonzale Date 2013-10-29 Time   Sent To I
Notes
2013-10-29 09:36:42NO OBJECTIONS

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-12-03 Cont ID  
Sent By scaldero Date 2013-12-03 Time 14:44 Rev Time 0.00
Received By scaldero Date 2013-12-03 Time 14:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-10-30 Cont ID  
Sent By scaldero Date 2013-10-30 Time 15:52 Rev Time 0.00
Received By scaldero Date 2013-10-30 Time 15:52 Sent To  
Notes
2013-10-30 15:55:13PERMIT #13090695
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ****INSUFFICIENT NUMBER OF FIRE EXTINGUISHERS PROVIDED.
 ADDITIONAL FIRE EXTINGUISHERS NEEDED.*******
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 ****COMMENTS FOR STORE PERMIT, NOT SHELL PERMIT*****
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shill Date 2014-06-03 Time 12:10 Sent To  
Notes
2014-06-03 12:11:19STOREFRONT SHOPS TO JW DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-04-14 Cont ID  
Sent By jwitmer Date 2014-04-14 Time 06:35 Rev Time 0.00
Received By jwitmer Date 2014-04-03 Time 17:48 Sent To  
Notes
2014-04-03 17:49:27FRAMING DETAILS & CALCS SENT TO J. WITMER'S DESK FOR
 REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-04-14 Cont ID  
Sent By jwitmer Date 2014-03-24 Time 06:35 Rev Time 0.00
Received By jwitmer Date 2014-03-19 Time 11:55 Sent To  
Notes
2014-03-19 11:56:18SHOP DRAWINGS TO JW DESK
 EXT METAL STUD & CANOPY FRAMING
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-06 Cont ID  
Sent By rregueir Date 2013-12-06 Time 13:19 Rev Time 0.00
Received By rregueir Date 2013-11-20 Time 13:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-05 Cont ID  
Sent By shill Date 2013-11-12 Time 17:24 Rev Time 0.00
Received By shill Date 2013-09-23 Time 13:14 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2013-12-04 Cont ID  
Sent By jwitmer Date 2013-12-04 Time 08:54 Rev Time 0.00
Received By jwitmer Date 2013-12-04 Time 08:54 Sent To  
Notes
2013-12-04 08:54:38P. B. CTY IMPACT FEE OFFICE:
 PLANS STAMPED NO FEES DUE
 RE: MU-2013-024553-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-11-22 Cont ID  
Sent By jwitmer Date 2013-11-22 Time 11:43 Rev Time 0.00
Received By jwitmer Date 2013-11-22 Time 11:43 Sent To  
Notes
2013-11-22 11:43:46BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-11-22 Cont ID  
Sent By jwitmer Date 2013-11-22 Time 11:16 Rev Time 0.00
Received By jwitmer Date 2013-10-26 Time 13:07 Sent To  
Notes
2013-10-26 13:07:17BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-10-29 Cont ID  
Sent By rregueir Date 2013-10-29 Time 16:47 Rev Time 0.00
Received By rregueir Date 2013-10-29 Time 16:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-10-28 Cont ID  
Sent By lwagner Date 2013-10-28 Time 10:31 Rev Time 0.00
Received By lwagner Date 2013-10-28 Time 09:59 Sent To  
Notes
2013-10-28 10:33:01SEPARATE GAS PERMIT REQUIRED.
  
 ***PROVISO**
 GAS PIPE SHALL ENTER BUILDING ABOVE GRADE. FBC FUEL GAS
 404.4

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2013-11-22 Cont ID  
Sent By jwitmer Date 2013-11-22 Time 11:39 Rev Time 0.00
Received By jwitmer Date 2013-11-22 Time 11:38 Sent To  
Notes
2013-11-22 11:42:50ROOFING WILL REQUIRE A SEPERATE PERMIT, FEES AND
 ASSOCIATED FEES.
 SUBMITTED NOA:13-0422.07
 SILKA SARNAFIL PVC SINGLE PLY ROOFING OVER LIGHTWEIGHT
 CONCRETE DECKS
 NOTE 19 PAGE DOCUMENT, NO SUB-SYSTEM WAS IDENTIFIED,
 SEPARATE ROOF PERMIT AND REVIEW!!!!

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2013-11-22 Cont ID  
Sent By jwitmer Date 2013-11-22 Time 11:17 Rev Time 0.00
Received By jwitmer Date 2013-11-22 Time 11:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-12-06 Cont ID  
Sent By eschneid Date 2013-12-06 Time 15:10 Rev Time 0.00
Received By shill Date 2013-12-06 Time 15:10 Sent To  
Notes
2013-11-05 17:56:06MISTAKE OPEN SIGNATURE LINE BY ZONING - ES

Review Stop Z ZONING
Rev No 1 Status P Date 2013-11-05 Cont ID  
Sent By eschneid Date 2013-11-05 Time 17:53 Rev Time 2.00
Received By eschneid Date 2013-11-05 Time 17:53 Sent To  
Notes
2013-11-05 17:54:37SIGNS AND AWNING REQUIRE SEPARATE PERMITS.
  
 BENCHES SHALL BE APPROVEDBY THE CRIME PREVENTION
 OFFICER PRIOR TO INSTALLATION.
2013-10-30 15:16:1410/29/13