| 2013-10-01 11:03:52 | BUILDING PLAN REVIEW |
| | PERMIT:13090663 |
| | ADD: 5600 N FLAGLER DR/ GARAGE |
| | CONT: MURRAY LOGAN |
| | TEL: (561)686-3948 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: SEPT. 30/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) THIS IS A 3 STORY STRUCTURE AND WILL REQUIRE A |
| | RESIDENT INSPECTOR. WILL ALSO REQUIRE (3) SETS OF |
| | PLANS. FBC* 109.3.7 RESIDENT INSPECTOR. SUBMIT |
| | INSPECTOR RESUME' AND LICENSE DOCUMENTS TO KEN CONRAD |
| | MANAGER OF THE RESIDENT INSPECTOR PROGRAM. A RESIDENT |
| | INSPECTOR PROGRAM IS REQUIRED, CONTACT KEN CONRAD AT; |
| | CHIEF BUILDING INSPECTOR |
| | KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 2) THE STRUCTURAL PLANS BY PE CLARENCE RHEAULT INDICATE |
| | THE EXPOSURE AS "C", PLEASE SEE THIS STRUCTURE IS |
| | WITHIN 600 FEET OF THE INTERCOASTAL AND QUALIFIES AS A |
| | "D" EXPOSURE. 2010 FBC-B 1609.4.3 EXPOSURE D. EXPOSURE |
| | D SHALL APPLY WHERE THE GROUND SURFACE ROUGHNESS, AS |
| | DEFINED BY SURFACE ROUGHNESS D, PREVAILS IN THE UPWIND |
| | DIRECTION FOR A DISTANCE OF AT LEAST 5,000 FEET (1524 |
| | M) OR 20 TIMES THE HEIGHT OF THE BUILDING, WHICHEVER IS |
| | GREATER. EXPOSURE D SHALL EXTEND INLAND FROM THE |
| | SHORELINE FOR A DISTANCE OF 600 FEET (183 M) OR 20 |
| | TIMES THE HEIGHT OF THE BUILDING, WHICHEVER IS GREATER |
| | FROM AN EXPOSURE D CONDITION AS DEFINED IN THE PREVIOUS |
| | SENTENCE. |
| | |