Plan Review Details - Permit 13090656
Plan Review Stops For Permit 13090656
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-01-06 Cont ID  
Sent By jwitmer Date 2014-01-06 Time 13:58 Rev Time 0.00
Received By jwitmer Date 2014-01-06 Time 13:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-09-27 Cont ID  
Sent By jwitmer Date 2013-09-27 Time 11:36 Rev Time 0.00
Received By jwitmer Date 2013-09-27 Time 11:36 Sent To  
Notes
2013-09-27 12:01:59BUILDING PLAN REVIEW
 PERMIT: 13090656
 ADD: 4310 BROADWAY
 CONT: CHARLES CULPPEPER
 TEL: (786)229-8862
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SEPT 27/2013
 ACTION: DENIED
  
 1) SHEET A1 & A2 NEITHER SHEET PROVIDE DETAILS IN
 REGARDS TO THE STRUCTURAL REQUIREMENTS FOR THE NEW
 LOCATION OF THE BACK EXIT DOOR. WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION. SECTION 107.3.5.1.1.8
 STRUCTURAL REQUIREMENTS, IF CBC PROVIDE DETIALS FOR
 COLUMNS & LINTEL, IF WOOD FRAME CONSTRUCTION THEN,
 HEADER SIZE, STUDS & JACKS, AND STRAPING BEING PART OF
 THE MWFRS.
  
 2) PROVIDE PRODUCT APPROVAL FOR EXTERIOR DOOR. 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) INTERIOR CBS WALL IS BEING REMOVED, NO INFORMATION
 HOW THE OPENING THAT IS BEING ENLARGED IS BEING
 RE-INFORCED? 107.2.1.3. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2014-01-16 Cont ID  
Sent By albarran Date 2014-01-16 Time 14:25 Rev Time 0.00
Received By albarran Date 2014-01-16 Time 14:25 Sent To I
Notes
2014-01-16 14:28:14ACCORDING TO THE GENERAL CONTRACTOR, THERE WILL BE NO
 ELECTRICAL WORK PERFORMED ON THE PROJECT. THEREFORE NO
 ELECTRICAL WORK WAS REVIEWED OR AUTHORIZED. THE PLANS
 ARE MARKED AS FOLLOWS:
 NOTICE:
 AS PER THE SCOPE OF THIS PERMIT, NO ELECTRICAL WORK
 IS PERMITTED AND THEREFORE AUTHORIZED.
 THE PERFORMANCE OF ANY ELECTRICAL WORK WITHOUT THE
 BENEFIT
 OF A PERMIT SHALL BE GROUNDS FOR A STOP WORK ORDER,
 UNDER
 FBC-B SECTION 115.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-10-24 Cont ID  
Sent By albarran Date 2013-10-24 Time 16:50 Rev Time 0.00
Received By albarran Date 2013-10-24 Time 16:49 Sent To I
Notes
2013-10-24 16:49:57NEED ELECTRICAL DRAWINGS FOR THE PROPOSED WORK. NEED A
 SITE PLAN AND ELEVATIONS AS WELL.
 SENT TO SH DESK

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-12-27 Cont ID  
Sent By wjolin Date 2013-12-27 Time 11:30 Rev Time 0.00
Received By wjolin Date 2013-12-27 Time 11:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-09-28 Cont ID  
Sent By wjolin Date 2013-09-28 Time 10:07 Rev Time 0.00
Received By wjolin Date 2013-09-28 Time 09:48 Sent To  
Notes
2013-09-28 10:07:204310 BROADWAY
 PERMIT #13090656
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 WHAT IS THE OCCUPANT LOAD FOR THIS SPACE? PER NFPA 101
 SECTION 7.2.1.4.2, DOORS ARE REQUIRED TO SWING IN THE
 DIRECTION OF EGRESS TRAVEL FOR AN OCCUPANT LOAD OF 50
 OR GREATER PERSONS.
  
 DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS,
 IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE.
  
 PER NFPA 101 SECTION 7.2.1.5.9, THE LOCK/LATCH
 RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE DOOR
 WITH NOT MORE THAN ONE RELEASING OPERATION. THE
 RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF
 OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF
 BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE
 TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
 TO OPERATE.
  
 THE EXISTING FLOOR PLAN DOES NOT SHOW ANY REAR WINDOWS;
 HOWEVER, THE NEW FLOOR PLANS INDICATE THREE NEW REAR
 WINDOWS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-02-04 Cont ID  
Sent By jwitmer Date 2014-02-04 Time 11:51 Rev Time 0.00
Received By jwitmer Date 2013-12-16 Time 14:20 Sent To  
Notes
2014-01-16 14:55:25RETURNED TO B8
  
2014-01-16 14:30:24SENT TO SH DESK
2013-12-17 14:21:06RESUBMITTAL SENT TO B8 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-24 Cont ID  
Sent By shill Date 2013-10-24 Time 17:26 Rev Time 0.00
Received By shill Date 2013-09-20 Time 08:57 Sent To  
Notes
2013-09-23 09:00:04B25

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2013-10-17 Cont ID  
Sent By hmoser Date 2013-10-17 Time 13:29 Rev Time 0.00
Received By hmoser Date 2013-10-17 Time 13:27 Sent To  
Notes
2013-10-17 13:29:20NO MECHANICAL WORK AT THIS TIME.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-02-03 Cont ID  
Sent By jwitmer Date 2014-02-03 Time 11:39 Rev Time 0.00
Received By jwitmer Date 2014-02-03 Time 11:39 Sent To  
Notes
2014-02-03 11:53:19PLUMBING PROVISO:
  
 HOOK UP OF NEW 3 COMPARTMENT SINK WILL REQUIRE INDIRECT
 WASTE
 THROUGH EITHER A AIR GAP OR AN AIR BREAK TO EITHER A
 FLOOR SINK OR
 HUB DRAIN PER 2010 FBC-P 802.1.8.
  
  
  
 PLUMBING PROVISO:
  
 HOOK UP OF NEW 3 COMPARTMENT SINK WILL REQUIRE INDIRECT
 WASTE
 THROUGH EITHER A AIR GAP OR AN AIR BREAK TO EITHER A
 FLOOR SINK OR
 HUB DRAIN PER 2010 FBC-P 802.1.8.

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-01-02 Cont ID  
Sent By lwagner Date 2014-01-02 Time 14:17 Rev Time 0.00
Received By lwagner Date 2014-01-02 Time 13:36 Sent To  
Notes
2014-01-02 13:38:58FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. IF NEW PLUMBING FIXTURES ARE BEING ADDED, A PLUMBING
 DRAWING WILL BE RQUIRED.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.3 PLUMBING
  
 2. IF THE SINK/S SHOWN ARE USED FOR GREASE-LADEN WASTE,
 THE WASTE SHALL BE ROUTED TO AN INTERCEPTOR.
 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC GREASE
 REMOVAL DEVICES REQUIRED.
 A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE
 SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES
 AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD
 PREPARATION AREAS, SUCH AS IN RESTAURANTS, HOTEL
 KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, FACTORY
 CAFETERIAS AND CLUBS. FIXTURES AND EQUIPMENT SHALL
 INCLUDE POT SINKS, PRERINSE SINKS; SOUP KETTLES OR
 SIMILAR DEVICES;WOK STATIONS; FLOOR DRAINS OR SINKS
 INTO WHICH KETTLES ARE DRAINED; AUTOMATIC HOOD WASH
 UNITS AND DISHWASHERS WITHOUT PRERINSE SINKS.GREASE
 INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES SHALL
 RECEIVE WASTE ONLY FROM FIXTURES AND EQUIPMENT THAT
 ALLOW FATS, OILS OR GREASE TO BE DISCHARGED.
  
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status N Date 2013-09-24 Cont ID  
Sent By ajones Date 2013-09-24 Time 11:34 Rev Time 0.00
Received By ajones Date 2013-09-24 Time 11:34 Sent To  
Notes
***NONE***