Plan Review Details - Permit 13090610
Plan Review Stops For Permit 13090610
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-10-26 Cont ID  
Sent By shill Date 2013-10-26 Time 16:40 Rev Time 0.00
Received By shill Date 2013-10-26 Time 16:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-10-16 Cont ID  
Sent By shill Date 2013-10-16 Time 07:42 Rev Time 0.00
Received By shill Date 2013-10-16 Time 07:41 Sent To  
Notes
2013-10-16 07:43:19****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2010
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 2ND REVIEW, SAME DOCUMENTS SUBMITTED (ASTM 492 AND ASTM
 E 84). PROVIDE TEST ASTM E 90.
  
 2. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109. VALUE IS TO INCLUDE LABOR AND MATERIALS, INCLUDING
 MATERIALS SUPPLIED BY THE OWNER.
  
 2ND REVIEW, CONTRACT NOT SIGNED BY OWNER AND NOT CLEAR
 AS TO WHETHER THIS IS INSTALLATION ONLY OR IF IT
 INCLUDES MATERIALS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-09-25 Cont ID  
Sent By shill Date 2013-09-25 Time 19:06 Rev Time 0.00
Received By shill Date 2013-09-25 Time 19:06 Sent To  
Notes
2013-09-25 19:06:57****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2010
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 2. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109. VALUE IS TO INCLUDE LABOR AND MATERIALS, INCLUDING
 MATERIALS SUPPLIED BY THE OWNER.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-10-26 Cont ID  
Sent By shill Date 2013-10-26 Time 16:40 Rev Time 0.00
Received By shill Date 2013-10-18 Time   Sent To  
Notes
2013-10-18 11:40:41<5000 BLDG

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-16 Cont ID  
Sent By shill Date 2013-10-16 Time 07:43 Rev Time 0.00
Received By shill Date 2013-10-02 Time 10:58 Sent To  
Notes
2013-10-02 10:58:52SENT TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-25 Cont ID  
Sent By shill Date 2013-09-25 Time 19:07 Rev Time 0.00
Received By shill Date 2013-09-19 Time 11:49 Sent To  
Notes
2013-09-20 11:49:33SENT TO BUILDING UNDER $5000 BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved