Plan Review Details - Permit 13090608
Plan Review Stops For Permit 13090608
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-10-02 Cont ID  
Sent By rmcdouga Date 2013-10-02 Time 17:09 Rev Time 0.00
Received By rmcdouga Date 2013-10-02 Time 17:09 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-09-19 Cont ID  
Sent By rmcdouga Date 2013-09-19 Time 15:34 Rev Time 0.00
Received By rmcdouga Date 2013-09-19 Time 15:34 Sent To FIRE
Notes
2013-09-19 15:54:562010 FBC
  
 DENIED BY BUILDING
  
 1) COMBUSTIBLE MATERIALS ARE NOT PERMITTED IN CONCEALED
 SPACES OF BUILDINGS OF TYPE I CONSTRUCTION. FBC 717.5
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-10-11 Cont ID  
Sent By dharvey Date 2013-10-11 Time 08:29 Rev Time 0.00
Received By dharvey Date 2013-10-11 Time 08:06 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-10-02 Cont ID  
Sent By dharvey Date 2013-09-26 Time 10:45 Rev Time 0.00
Received By dharvey Date 2013-09-26 Time 10:44 Sent To  
Notes
2013-09-26 10:45:41PROVIDE LISTING AND SPECIFICATION OF RECESSED HI HAT
 CAN FOR THE INSTALLATION PROPOSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-10-11 Cont ID  
Sent By scaldero Date 2013-10-11 Time 13:06 Rev Time 0.00
Received By scaldero Date 2013-10-11 Time 13:06 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-10-07 Cont ID  
Sent By pleduc Date 2013-10-07 Time 14:41 Rev Time 0.00
Received By pleduc Date 2013-10-07 Time 14:55 Sent To  
Notes
2013-10-07 14:41:05THE CONSTRUCTION APPLICATION SHALL BE ILLUSTRATED IN
 DETAIL AND CLEARLY INDICATED ON THE PLANS INCLUDING
 SEPARATION DISTANCES FROM THE HIGH-HAT AND THE DRYWALL.
  
 THE SPECIFIED FIRE RATED SILICONE SHALL BE INDICATED ON
 THE PLAN WITH THE DETAILED APPLICATION INSTRUCTIONS.
 THE FIRE RATED SILICONE SHALL BE MEET THE
 REQUIRERMENRTS OF THE PROPOSED CONSTRUCTION
 APPLICATION.
  
 THE LISTING FOR THE HIGH-HAT SHALL SUPPORT (NOT
 CONFLICT) THE PROPOSED CONSTRUCTION APPLICATION.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-09-23 Cont ID  
Sent By lphilmor Date 2013-09-23 Time 12:50 Rev Time 0.00
Received By lphilmor Date 2013-09-23 Time 12:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-10-11 Cont ID  
Sent By scaldero Date 2013-10-11 Time 13:07 Rev Time 0.00
Received By scaldero Date 2013-10-10 Time 18:58 Sent To  
Notes
2013-10-10 18:59:03GAVE TO D HARVEY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-08 Cont ID  
Sent By scaldero Date 2013-10-08 Time 12:35 Rev Time 0.00
Received By scaldero Date 2013-10-02 Time 17:06 Sent To  
Notes
2013-10-02 16:56:43TO R MCDOUGALS DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-26 Cont ID  
Sent By dharvey Date 2013-09-26 Time 10:46 Rev Time 0.00
Received By dharvey Date 2013-09-19 Time 15:34 Sent To  
Notes
***NONE***