Plan Review Details - Permit 13090593
Plan Review Stops For Permit 13090593
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-12-03 Cont ID  
Sent By albarran Date 2013-12-03 Time 09:00 Rev Time 0.00
Received By albarran Date 2013-12-03 Time 08:59 Sent To I
Notes
2013-12-03 09:03:14THE REQUIRED EQUIPMENT CUT SHEETS WERE PROVIDED TO ME
 AS PREVIOUSLY REQUESTED. ALL PROPOSED EQUIPMENT PROVES
 TO BE COMPATIBLE BUT NO POWER SUPPLY WAS INDICATED.
 MAKE CERTAIN THE THE UL APPROVED POWER SUPPLY IS
 INSTALLED AND WORKING FOR INSPECTION.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-10-11 Cont ID  
Sent By dharvey Date 2013-10-11 Time 12:56 Rev Time 0.00
Received By dharvey Date 2013-10-11 Time 12:56 Sent To  
Notes
2013-10-11 12:56:45PREVIOUS COMMENT NEEDS TO BE ADDRESSED.
  
 PROVIDE CUT SHEETS.
 PLEASE PROVIDE INFORMATION ON THE CONTROL PANEL,
 INCLUDING INFORMATION FOR DEVICES LISTED FOR USE WITH
 THE PANEL.
 ALL DEVICES ARE T O BE LISTED FOR THE USE AND USED
 WITHIN THE LISTING.
  
 REVIEWED BY WDS.
 DENIED AT (G).
 CALLED CONTRACTOR AND LEFT MESSAGE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-10-04 Cont ID  
Sent By dharvey Date 2013-10-04 Time 07:00 Rev Time 0.00
Received By dharvey Date 2013-10-04 Time 06:19 Sent To  
Notes
2013-10-11 12:55:54PREVIOUS COMMENT NEEDS TO BE ADDRESSED.
  
 PROVIDE CUT SHEETS.
 PLEASE PROVIDE INFORMATION ON THE CONTROL PANEL,
 INCLUDING INFORMATION FOR DEVICES LISTED FOR USE WITH
 THE PANEL.
 ALL DEVICES ARE T O BE LISTED FOR THE USE AND USED
 WITHIN THE LISTING.
  
 REVIEWED BY WDS.
 DENIED AT (G).
 CALLED CONTRACTOR AND LEFT MESSAGE.
2013-10-04 07:00:32PLEASE PROVIDE INFORMATION ON THE CONTROL PANEL,
 INCLUDING INFORMATION FOR DEVICES LISTED FOR USE WITH
 THE PANEL.
 ALL DEVICES ARE T O BE LISTED FOR THE USE AND USED
 WITHIN THE LISTING.
  
 DOUG HARVEY
 561-805-6740
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-10-09 Cont ID  
Sent By scaldero Date 2013-10-09 Time 13:54 Rev Time 0.00
Received By scaldero Date 2013-10-09 Time 13:54 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-09-27 Cont ID  
Sent By wjolin Date 2013-09-27 Time 12:35 Rev Time 0.00
Received By wjolin Date 2013-09-27 Time 12:30 Sent To E
Notes
2013-09-27 12:35:001 HARVARD CIRCLE
 PERMIT #13090593
 MASTER #13030376
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLAN SHOWS 1 CARD READER, THE PLAN SCOPE OF WORK
 INDICATES 4 CARD READERS, AND THE PERMIT APPLICATION
 INDICATES 11 CARD READERS AND DOOR CONTROLLER. WHAT IS
 THE ACTUAL SCOPE OF WORK? PERMIT VALUE ON APPLICATION
 INDICATES A VALUE OF ONLY $1500.
  
 THE EMERGENCY PUSH BUTTON AND CARD READER ARE SHOWN ON
 THE WRONG SIDE OF THE DOUBLE DOORS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-03 Cont ID  
Sent By shill Date 2013-12-03 Time 17:43 Rev Time 0.00
Received By shill Date 2013-10-08 Time 09:08 Sent To  
Notes
2013-12-03 09:03:41SENT TO SK FOR PROCESSING
2013-10-09 09:08:56SENT TO FIRE SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-04 Cont ID  
Sent By dharvey Date 2013-10-04 Time 07:00 Rev Time 0.00
Received By dharvey Date 2013-09-19 Time 13:32 Sent To  
Notes
2013-09-19 13:32:50ROUTED TO FIRE