Plan Review Details - Permit 13090417
Plan Review Stops For Permit 13090417
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-10-30 Cont ID  
Sent By jwitmer Date 2013-10-30 Time 10:12 Rev Time 0.00
Received By jwitmer Date 2013-10-30 Time 09:45 Sent To FIRE
Notes
2013-10-30 10:15:08BUILDING PLAN REVIEW
 PERMIT:13090417
 ADD: 1751 PALM BEACH LAKES SUITE E111
 CONT: TBD
 TEL: (561)373-3902
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: WED OCT. 30/ 2013
 ACTION: BUILDING PROVISO
  
 1) PB OUTLET MALLS:
 BUILDING PROVISO:
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 2) BUILDING PROVISO:
 SHEET A1.2 DETAIL # 2 MICROWAVE, THE BOTTOM OF THE
 SHELF IS 44 INCHES FROM FINISH FLOOR.
 2010 FL ACCESS CODE, 309.3 HEIGHT. OPERABLE PARTS SHALL
 BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308.
 308.2.2 OBSTRUCTED HIGH REACH.
 WHERE A HIGH FORWARD REACH IS OVER AN OBSTRUCTION, THE
 CLEAR FLOOR SPACE SHALL EXTEND BENEATH THE ELEMENT FOR
 A DISTANCE NOT LESS THAN THE REQUIRED REACH DEPTH OVER
 THE OBSTRUCTION. THE HIGH FORWARD REACH SHALL BE 48
 INCHES (1220 MM) MAXIMUM WHERE THE REACH DEPTH IS 20
 INCHES (510 MM) MAXIMUM. WHERE THE REACH DEPTH EXCEEDS
 20 INCHES (510 MM), THE HIGH FORWARD REACH SHALL BE 44
 INCHES (1120 MM) MAXIMUM AND THE REACH DEPTH SHALL BE
 25 INCHES (635 MM) MAXIMUM.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-10-01 Cont ID  
Sent By jwitmer Date 2013-09-18 Time 08:08 Rev Time 0.00
Received By jwitmer Date 2013-09-18 Time 06:32 Sent To  
Notes
2013-09-18 07:06:48BUILDING PLAN REVIEW
 PERMIT:13090417
 ADD: 1751 PALM BEACH LAKES SUITE E111
 CONT: TBD
 TEL: (561)373-3902
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: WED SEPT 18/ 2013
 ACTION: BUILDING PROVISO
  
 1) PB OUTLET MALLS:
 BUILDING PROVISO:
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 2) BUILDING PROVISO:
 SHEET A1.0 BACK EXIT WILL REQUIRE COMPLIANCE WITH: 2010
 FBC 1014.2.4 EXCEPTION # 2, EGRESS THROUGH INTERVENING
 SPACES:
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA;
 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM;
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE; AND
 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED
 WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE
 REQUIRED WIDTH AND LEAD DIRECTLY FROM THE RETAIL AREA
 TO THE EXIT WITHOUT OBSTRUCTIONS.
  
 3) BUILDING PROVISO:
 SHEET A1.2 DETAIL # 2 MICROWAVE, THE BOTTOM OF THE
 SHELF IS 54 INCHES FROM FINISH FLOOR.
 2010 FL ACCESS CODE, 309.3 HEIGHT. OPERABLE PARTS SHALL
 BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308.
 308.2.2 OBSTRUCTED HIGH REACH.
 WHERE A HIGH FORWARD REACH IS OVER AN OBSTRUCTION, THE
 CLEAR FLOOR SPACE SHALL EXTEND BENEATH THE ELEMENT FOR
 A DISTANCE NOT LESS THAN THE REQUIRED REACH DEPTH OVER
 THE OBSTRUCTION. THE HIGH FORWARD REACH SHALL BE 48
 INCHES (1220 MM) MAXIMUM WHERE THE REACH DEPTH IS 20
 INCHES (510 MM) MAXIMUM. WHERE THE REACH DEPTH EXCEEDS
 20 INCHES (510 MM), THE HIGH FORWARD REACH SHALL BE 44
 INCHES (1120 MM) MAXIMUM AND THE REACH DEPTH SHALL BE
 25 INCHES (635 MM) MAXIMUM.
  
 4) BUILDING PROVISO:
 SHEET A8.0 DETAIL # 3. ACCESSIBLE BENCH IS MISSING
 BACK.
 903.4 BACK SUPPORT.
 THE BENCH SHALL PROVIDE FOR BACK SUPPORT OR SHALL BE
 AFFIXED TO A WALL. BACK SUPPORT SHALL BE 42 INCHES
 (1065 MM) LONG MINIMUM AND SHALL EXTEND FROM A POINT 2
 INCHES (51 MM) MAXIMUM ABOVE THE SEAT SURFACE TO A
 POINT 18 INCHES (455 MM) MINIMUM ABOVE THE SEAT
 SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES (64 MM)
 MAXIMUM FROM THE REAR EDGE OF THE SEAT MEASURED
 HORIZONTALLY.
 ADVISORY 903.4 BACK SUPPORT.
 TO ASSIST IN TRANSFERRING TO THE BENCH, CONSIDER
 PROVIDING GRAB BARS ON A WALL ADJACENT TO THE BENCH,
 BUT NOT ON THE SEAT BACK. IF PROVIDED, GRAB BARS CANNOT
 OBSTRUCT TRANSFER TO THE BENCH.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-10-17 Cont ID  
Sent By dharvey Date 2013-10-17 Time 14:51 Rev Time 0.00
Received By dharvey Date 2013-10-17 Time 14:12 Sent To  
Notes
2013-10-17 14:53:15RETURNED TO BIN B16 WAITING FOR FIRE REVIEW
 CORRECTIONS, BY: MA

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-10-31 Cont ID  
Sent By scaldero Date 2013-10-31 Time 15:35 Rev Time 0.00
Received By scaldero Date 2013-10-31 Time 15:35 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-09-19 Cont ID  
Sent By scaldero Date 2013-09-19 Time 15:14 Rev Time 0.00
Received By scaldero Date 2013-09-19 Time 15:13 Sent To  
Notes
2013-09-19 15:22:23PERMIT #13090417
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAIL COMMENT: PER NFPA 101, SECTION 36.2.5.11 EXIT
 ACCESS IN CLASS A AND CLASS B MERCANTILE OCCUPANCIES
 THAT ARE PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH 9.7.1.1(1), AND EXIT ACCESS IN ALL CLASS C
 MERCANTILE OCCUPANCIES, SHALL BE PERMITTED TO PASS
 THROUGH STOREROOMS, PROVIDED THAT ALL OF THE FOLLOWING
 CONDITIONS ARE MET:
 (1)NOT MORE THAN 50 PERCENT OF EXIT ACCESS SHALL BE
 PROVIDED THROUGH THE STOREROOM.
 (2)THE STOREROOM SHALL NOT BE SUBJECT TO LOCKING.
 (3)THE MAIN AISLE THROUGH THE STOREROOM SHALL BE NOT
 LESS THAN 44 IN. (1120 MM) WIDE.
 (4)THE PATH OF TRAVEL THROUGH THE STOREROOM SHALL BE
 DEFINED, DIRECT, AND CONTINUOUSLY MAINTAINED IN AN
 UNOBSTRUCTED CONDITION.
  
 THE SPEAKER SYSTEM WILL NEED TO BE TESTED AGAINST THE
 FIRE ALARM SYSTEM TO ENSURE THAT THE MINIMUM REQUIRED
 DECIBAL LEVELS OF THE FIRE ALARM SYSTEM ARE BEING MET.
 PENDING RESULTS OF FIELD INSPECTION/FIRE ALARM TEST,
 ADDITIONAL REQUIREMENTS MAY BE NEEDED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-31 Cont ID  
Sent By shill Date 2013-10-31 Time 17:14 Rev Time 0.00
Received By shill Date 2013-10-28 Time 15:40 Sent To  
Notes
2013-10-29 15:41:11SENT TO JIM'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-18 Cont ID  
Sent By rregueir Date 2013-10-17 Time 12:51 Rev Time 0.00
Received By rregueir Date 2013-09-16 Time 16:08 Sent To  
Notes
2013-09-17 07:00:19INCOMING SENT TO B-16. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-10-18 Cont ID  
Sent By rregueir Date 2013-09-26 Time 12:50 Rev Time 0.00
Received By rregueir Date 2013-09-26 Time 13:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-09-18 Cont ID  
Sent By lwagner Date 2013-09-18 Time 11:01 Rev Time 0.00
Received By lwagner Date 2013-09-18 Time 10:33 Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2013-09-18 Time   Rev Time 0.00
Received By ktucker Date 2013-09-19 Time 10:00 Sent To  
Notes
2013-09-19 10:00:48CRIME PREVENTION THROUGH ENVIRONMENTAL DESIGN
 THE CITY OF WEST PALM BEACH HAS RECOGNIZED THAT
 TRADITIONAL CRIME PREVENTION STRATEGIES ARE NOT ENOUGH
 IN TODAY?S SOCIETY AND A NEW APPROACH IS NEEDED. THE
 NAME OF THIS APPROACH IS CRIME PREVENTION THROUGH
 ENVIRONMENTAL DESIGN (CPTED). CPTED ACKNOWLEDGES THE
 MANNER IN WHICH PHYSICAL SPACE IS DESIGNED OR USED HAS
 A DIRECT BEARING ON CRIME AND SECURITY.
 THE PHYSICAL ENVIRONMENT HAS A DRAMATIC EFFECT ON OUR
 OWN BEHAVIOR AND THE WAY IN WHICH WE VIEW THE BEHAVIOR
 OF OTHERS. CPTED IS A CONCEPT SUPPORTED BY A SERIES OF
 OVERLAPPING PRINCIPLES BASED ON THE RELATIONSHIP OF THE
 BUILT ENVIRONMENT TO THE PRESENCE OR ABSENCE OF
 UNDESIRABLE BEHAVIOR. THE CPTED CONCEPT IS: ?THE PROPER
 DESIGN AND EFFECTIVE USE OF THE BUILT ENVIRONMENT CAN
 LEAD TO A REDUCTION IN THE INCIDENCE AND FEAR OF CRIME
 AND IMPROVEMENT IN THE QUALITY OF LIFE BY INCORPORATING
 ACCESS CONTROL, NATURAL SURVEILLANCE AND TERRITORIAL
 DEFENSIVE TACTICS.?
 CPTED THEORY IS BASED UPON THE CONTENTION THAT
 PLANNERS, DESIGNERS, ARCHITECTS, LANDSCAPERS AND LAW
 ENFORCEMENT CAN COOPERATIVELY CREATE A ?SAFE? CLIMATE
 WITHIN A BUILT ENVIRONMENT ? RIGHT FROM THE BEGINNING.
 SAFETY STRIKES AT THE VERY CORE OF WHAT IS GENERALLY
 REFERRED TO IN A COMMUNITY AS ?QUALITY OF LIFE.? A SAFE
 ENVIRONMENT IS ONE THAT REGULAR USERS PERCEIVE AS SAFE
 AND NON-USERS (CRIMINALS) PERCEIVE AS HIGHLY RISKY TO
 FREQUENT AND IN WHICH TO COMMIT CRIMES.
 THE WEST PALM BEACH POLICE DEPARTMENT HAS OUTLINED
 GUIDELINES WE WOULD LIKE TO SEE FOLLOWED. IN ADDITION
 TO THE GUIDELINES, WE ENCOURAGE YOU TO PLEASE ADOPT
 THESE MINIMUM STANDARDS:
  
 (1) A FULLY FUNCTIONING AND OPERATIONAL CCTV SYSTEM
 CAPABLE OF RECORDING AND RETRIEVING ON SITE, AN
 IDENTIFIABLE IMAGE TO ASSIST IN OFFENDER IDENTIFICATION
 AND APPREHENSION. MONITORS FOR THE SYSTEM SHOULD BE
 PLACED IN A MANAGER?S OFFICE OR BACK ROOM, WITH A
 MONITOR IN PUBLIC VIEW FROM THE SALES FLOOR.
 (2) CAMERA COVERAGE SHOULD BE AT SENSITIVE LOCATIONS:
 (A) DOORS THAT LEADS TO THE BACK OF HOUSE (B) HALLWAYS
 THAT LEAD TO REAR EXITS (C) SALES FLOOR (D) REGISTERS
 (LOW FOR FACIAL RECOGNITION) (E) FRONT ENTRY.
 (3) DOOR THAT LEADS TO THE BACK OF HOUSE AND EXITING
 REAR DOORS SHOULD BE ALARMED WITH A SENSOR AND VIEW
 FINDER.
 (4) SILENT PANIC ALARM UNDER EACH REGISTER, ONE IN THE
 BACK OF HOUSE WORK AREA
 (5) A SECURED DROP SAFE OR CASH MANAGEMENT DEVICE FOR
 RESTRICTED ACCESS TO MONEY/CASH RECEIPTS AT THE
 REGISTER AND A SECURED DROP SAFE OR CASH MANAGEMENT
 DEVICE IN THE STORAGE AREA.
 (6) CASH OUT AREA SHOULD BE IN THE FRONT OF THE STORE,
 CLOSE TO THE ENTRANCE.
 (7) SECURE THE REGISTERS TO THE COUNTER.
 (8) INSTALL ANTI-THEFT DEVICES INCLUDING SECURITY
 TOWERS AT ENTRANCES.
 (9) USE CONVEX MIRRORS IN CORNERS AND ANTI-THEFT TAGS
 ON MERCHANDISE.
 (10) HEIGHT MARKERS AT THE ENTRANCE AND EXIT.
 (11) EMPLOYEE ACCESS CONTROL ON ALL DOORS THAT LEAD
 INTO THE BACK.
 (12) WHERE WINDOW(S) ARE PRESENT, A CLEAR AND
 UNOBSTRUCTED VIEW FROM OUTSIDE THE STORE AND IN A
 NORMAL LINE OF SIGHT OF THE CASH REGISTER AND SALES
 TRANSACTION AREA
 (13) IF INSTALLING SWING GATE AT REGISTERS THEY SHOULD
 HAVE SIMPLE ACCESS CONTROL.
 (14) ALL SHOWCASES SHOULD HAVE LOCKS AND IN THE
 EXPENSIVE SHOWCASES, CONSIDER AN ALARM.
 (15) INTERIOR SHELVING AND DISPLAYS SHOULD BE NO HIGHER
 THAN FIVE FEET, EVEN LESS IN FRONT OF WINDOWS.
  
  
 OFFICER K. TUCKER-CARSILLO
 CRIME PREVENTION UNIT
 WEST PALM BEACH POLICE DEPT
 600 BANYAN BLVD
 WEST PALM BEACH, FL 33401
 (561) 822-1620 OFFICE
 (561) 822-1648 FAX
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2013-10-08 Cont ID  
Sent By eschnid Date 2013-10-08 Time 15:10 Rev Time 0.25
Received By eschneid Date 2013-10-08 Time 15:10 Sent To  
Notes
2013-10-08 15:11:32SIGNS REQUIRE SEPARATE PERMIT WITH PLANS.