Plan Review Details - Permit 13090392
Plan Review Stops For Permit 13090392
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2013-12-05 Cont ID  
Sent By shill Date 2013-12-05 Time 05:43 Rev Time 0.00
Received By shill Date 2013-12-05 Time 05:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2013-11-14 Cont ID  
Sent By shill Date 2013-11-14 Time 11:29 Rev Time 0.00
Received By shill Date 2013-11-14 Time 11:29 Sent To  
Notes
2013-11-14 11:30:21****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 COMMENTS FROM PREVIOUS LIST
  
 FBC FLORIDA BUILDING CODE 2010
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 3RD REVIEW, TEST NOT PROVIDED.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 3RD REVIEW, TEST NOT PROVIDED.
  
 3. OK
  
 4. OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-10-26 Cont ID  
Sent By shill Date 2013-10-26 Time 14:27 Rev Time 0.00
Received By shill Date 2013-10-26 Time 14:27 Sent To  
Notes
2013-10-26 14:29:38****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 COMMENTS FROM PREVIOUS LISTS NOT ADDRESSED. NO TEST
 REPORTS SUBMITTED, VALUE ISSUE NOT ADDRESSED.
  
 SPEC SHEET SHOWING STC AND ICC DATA FROM MANUFACTURER
 IS ***NOT*** THE SAME AS A COPY OF THE TEST. FLAME
 SPREAD INFORMATION/TEST NOT PROVIDED.
  
 PLEASE DO NOT RESUBMIT WITHOUT SPEAKING WITH ME UNLESS
 YOU UNDERSTAND THE COMMENTS. OR, HAVE THE
 MANUFACTURER'S TECHNICAL REPRESENTATIVE CONTACT ME.
  
 FBC FLORIDA BUILDING CODE 2010
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 4. VALUE TO INCLUDE LABOR AND MATERIALS FBC 107.
 PROVIDE A PLAN WHICH SHOWS AREAS TO HAVE NEW TILE
 INSTALLED, WITH SQUARE FOOT AREAS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-09-25 Cont ID  
Sent By shill Date 2013-09-25 Time 18:23 Rev Time 0.00
Received By shill Date 2013-09-25 Time 18:23 Sent To  
Notes
2013-09-25 18:24:42****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 COMMENTS FROM PREVIOUS LIST NOT ADDRESSED. NO TEST
 REPORTS SUBMITTED, VALUE ISSUE NOT ADDRESSED.
  
  
 FBC FLORIDA BUILDING CODE 2010
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 4. VALUE TO INCLUDE LABOR AND MATERIALS FBC 107.
 PROVIDE A PLAN WHICH SHOWS AREAS TO HAVE NEW TILE
 INSTALLED, WITH SQUARE FOOT AREAS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-09-14 Cont ID  
Sent By shill Date 2013-09-14 Time 14:28 Rev Time 0.00
Received By shill Date 2013-09-14 Time 14:27 Sent To  
Notes
2013-09-14 14:29:11****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2010
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 4. VALUE TO INCLUDE LABOR AND MATERIALS FBC 107.
 PROVIDE A PLAN WHICH SHOWS AREAS TO HAVE NEW TILE
 INSTALLED, WITH SQUARE FOOT AREAS.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-11-14 Cont ID  
Sent By shill Date 2013-11-14 Time 11:30 Rev Time 0.00
Received By shill Date 2013-10-30 Time 13:17 Sent To  
Notes
2013-10-30 13:18:02SENT TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-10-26 Cont ID  
Sent By shill Date 2013-10-26 Time 14:29 Rev Time 0.00
Received By shill Date 2013-10-22 Time 14:40 Sent To  
Notes
2013-10-22 14:41:06SENT TO SAMANTHA'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-09-25 Cont ID  
Sent By shill Date 2013-09-25 Time 18:24 Rev Time 0.00
Received By shill Date 2013-09-20 Time 16:59 Sent To  
Notes
2013-09-20 16:59:58SENT TO SAMANTHA'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-14 Cont ID  
Sent By shill Date 2013-09-14 Time 14:29 Rev Time 0.00
Received By shill Date 2013-09-13 Time 16:45 Sent To  
Notes
2013-09-13 16:47:29SENT TO BUILDING UNDER $5000 BOX.