Plan Review Details - Permit 13090329
Plan Review Stops For Permit 13090329
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2015-06-25 Cont ID  
Sent By jwitmer Date 2015-06-25 Time 08:24 Rev Time 0.00
Received By jwitmer Date 2015-06-25 Time 07:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2015-04-09 Cont ID  
Sent By jwitmer Date 2015-04-09 Time 16:49 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2015-04-09 16:49:51) PROVISO:
 ROOFING ON THE MAIN ROOF WAS COMPLETED A FEW YEARS AGO.
 ROOFING CONTRACTOR WILL BE NEEDED FOR ROOF FLASHING OF
 NEW A/C CURBS, STANDS, ROOF HATCH AND ANY FLASHING WORK
 AT PARAPET WALL. ROOFING CONTRACTOR TO SUBMIT A
 SEPARATE ROOFING PRODUCT APPROVAL FOR TIE IN OF THE
 EXISSTING ROOF.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-03-31 Cont ID  
Sent By jwitmer Date 2015-03-31 Time   Rev Time 0.00
Received By jwitmer Date 2015-03-31 Time   Sent To  
Notes
2015-03-31 15:40:26BUILDING PLAN REVIEW
 PERMIT: 13090329
 ADD: 5011 BROADWAY
 CONT: TO BE DETERMINED
 TEL: (305)331-1400
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: TUES. MARCH 30/ 2015
 ACTION: DENIED
  
 NOTICE!!!!!! CHAPTER 553.80(2)(B) FLORIDA STATUTES
 STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF
 FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE TIMES
 FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1) SHEET A-1: COMPLIED>
 ,
 1B) 4TH REQUEST: SHEET A1 BUILDING DESIGN.THE RESPONSE
 COMMENTS STATE THE PLANS WERE UPDATED TO A 5-B W/
 SPRINKLERS, REQUIRING NO FIRE RATING. REVISED DATE
 3/16/15 STILL SHOWS THE BUILDING AS A TYPE III-B FIRE
 SPRINKLERED, PROTECTED.
  
 THE MINIMUM BUILDING TYPE OF CONSTRUCTION
 107.3.5.1.1(3) TABLE 503.
 SHEET A1 INDICATES THIS BUILDING IS DESIGNED AS A TYPE
 III-B FIRE SPRINKLERED PROTECTED (1 HOUR FIRE RATING).
 SEE 2007 CODE COMMENTARY FBC-B TABLE 601 OFTEN TYPE A
 OR B ARE REFEFFED TO AS PROTECTED AND UNPROTECTED
 CONSTRUCTION, RESPECTIVELY. PLEASE NOTE THIS
 TERMINOLOGY DOES NOT REFER TO WHETHER THE BUILDING IS
 SPRINKLERED OR NOT.
 THE A REFERS TO REQUIRED FIRE RATINGS FOR EXTERIOR
 WALLS PRIMARY STRUCTURAL FRAME, ROOF CONSTRUCTION AND
 SECONDARY MEMBERS. 2010 FBC-B TABLE 601 FOOTNOTE B
 PROVIDES REDUCTION IN HOURS, A TYPE BUILDING ALL
 REQUIRE A MINIMUM OF 1 HOUR FIRE RATING OF ROOF FRAMING
 MEMBERS, SEE BUILDING TYPE IIIA FOOTNOTES ,B, C &D.
 SHEET A8 THE STRUCTURAL ELEMENTS DOES NOT INDICATE ANY
 RATING ON STRUCTURAL MEMBERS.
  
 1C) 4TH REQUEST. THE RESPONSE LETTER INDICATES FIRE
 SPRINKLER SHOP DRAWINGS ARE ATTACHED. NOTE NO FIRE
 SPRINKLER PLANS ARE ATTACHED. THERE ARE (2) SETS OF
 FIRE ALAARM PLANS FOLDED NOT PART OF THE SUBMITTAL SET.
 WEST PALM BEACH ADMINISTRATIVE AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 EDITION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
 FIRE PROTECTION NOTES INDICATE THAT THE BUILDING IS TO
 BE FIRE SPRINKLERED, THE 2010 FBC-B 903.2.7 NEW WORK
 REQUIRES SPRINKLERS FOR MERCANTILE AREAS WITH A FIRE
 AREA GREATER THAN 12,000 SQ FT. NO FIRE SPRINKLER PLANS
 WERE SUBMITTED. 107.3.5.1.1( 5) FIRE SUPPRESSION. NOTES
 ON THE PLAN DO NOT CONSTITUTE COMPLIANCE WITH THIS
 SECTION. THERE HAS TO BE A DESIGN CRITERIA FOR THE
 SIZING OF THE UNDER GROUND FIRE MAIN THAT WILL BE
 REQUIRED TO COME INTO THIS BUILDING. NO SIZING HAS BEEN
 SUBMITTED.
  
 1D) PROVISO:
 ROOFING ON THE MAIN ROOF WAS COMPLETED A FEW YEARS AGO.
 ROOFING CONTRACTOR WILL BE NEEDED FOR ROOF FLASHING OF
 NEW A/C CURBS, STANDS, ROOF HATCH AND ANY FLASHING WORK
 AT PARAPET WALL. ROOFING CONTRACTOR TO SUBMIT A
 SEPARATE ROOFING PRODUCT APPROVAL FOR TIE IN OF THE
 EXISSTING ROOF.
  
  
 2-4) COMPLIED.
  
 5) PROVISO: NEW COOLERS AND FREZZERS ARE UNDER SEPARATE
 PERMIT. NOT PART OF THIS REVIEW.
  
 6) PROVISO: AWNINGS ARE UNDER A SEPARATE PERMIT, NOT
 PART OF THIS REVIEW AS WELL AS SIGNS.
  
 7-12 COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-11-10 Cont ID  
Sent By jwitmer Date 2014-11-10 Time 14:36 Rev Time 0.00
Received By jwitmer Date 2014-11-10 Time 09:08 Sent To  
Notes
2014-11-10 11:09:10BUILDING PLAN REVIEW
 PERMIT: 13090329
 ADD: 5011 BROADWAY
 CONT: TO BE DETERMINED
 TEL: (305)331-1400
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: MON. NOV. 11/ 2014
 ACTION: DENIED
  
 NOTICE!!!!!! CHAPTER 553.80(2)(B) FLORIDA STATUTES
 STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF
 FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE TIMES
 FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1) SHEET A-1:
 1A) COMPLIED>
 MISSING TO WHAT EDITION OF CODE THIS BUILDING DESIGN
 AND PERMIT WERE DESIGNED TO, 2010 FBC-B, 2010 FL
 EXISTING BUILDING CODE & 2010 FL ACCESSIBILITY CODE,
 1B) 3RD REQUEST:
 THE MINIMUM BUILDING TYPE OF CONSTRUCTION
 107.3.5.1.1(3) TABLE 503.
 SHEET A1 INDICATES THIS BUILDING IS DESIGNED AS A TYPE
 III-B FIRE SPRINKLERED PROTECTED (1 HOUR FIRE RATING).
 SEE 2007 CODE COMMENTARY FBC-B TABLE 601 OFTEN TYPE A
 OR B ARE REFEFFED TO AS PROTECTED AND UNPROTECTED
 CONSTRUCTION, RESPECTIVELY. PLEASE NOTE THIS
 TERMINOLOGY DOES NOT REFER TO WHETHER THE BUILDING IS
 SPRINKLERED OR NOT.
 THE A REFERS TO REQUIRED FIRE RATINGS FOR EXTERIOR
 WALLS PRIMARY STRUCTURAL FRAME, ROOF CONSTRUCTION AND
 SECONDARY MEMBERS. 2010 FBC-B TABLE 601 FOOTNOTE B
 PROVIDES REDUCTION IN HOURS, A TYPE BUILDING ALL
 REQUIRE A MINIMUM OF 1 HOUR FIRE RATING OF ROOF FRAMING
 MEMBERS, SEE BUILDING TYPE IIIA FOOTNOTES ,B, C &D.
 SHEET A8 THE STRUCTURAL ELEMENTS DOES NOT INDICATE ANY
 RATING ON STRUCTURAL MEMBERS.
  
 1C) 3RD REQUEST.
 WEST PALM BEACH ADMINISTRATIVE AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 EDITION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
 FIRE PROTECTION NOTES INDICATE THAT THE BUILDING IS TO
 BE FIRE SPRINKLERED, THE 2010 FBC-B 903.2.7 NEW WORK
 REQUIRES SPRINKLERS FOR MERCANTILE AREAS WITH A FIRE
 AREA GREATER THAN 12,000 SQ FT. NO FIRE SPRINKLER PLANS
 WERE SUBMITTED. 107.3.5.1.1( 5) FIRE SUPPRESSION. NOTES
 ON THE PLAN DO NOT CONSTITUTE COMPLIANCE WITH THIS
 SECTION. THERE HAS TO BE A DESIGN CRITERIA FOR THE
 SIZING OF THE UNDER GROUND FIRE MAIN THAT WILL BE
 REQUIRED TO COME INTO THIS BUILDING. NO SIZING HAS BEEN
 SUBMITTED.
  
 1D) NO WRITTEN RESPONCE. 2ND REQUEST,
 IS THERE GOING TO BE A NEW ROOF TO BE PUT ON UNDER THIS
 PROJECT, IF SO THIS WILL BECOME A LEVEL III ALTERATION
 AND WILL AFFECT FUTURE REVIEWS AND CODE REQUIREMENTS,
 THERE IS A NOTE THAT THE BACK OF THE BUILDING A NEW
 ROOF STRUCTURE AND ROOF TO BE APPLIED. SHEET A-12 NOTE
 ONE INDICATES TO ONLY TO REPAIR ALL NEW PENETRATIONS.
 REVIEW 2010 EXST BLDG CODE SECTION 611.1.1 NOT MORE
 THAN 25 PERCENT OF THE TOTAL ROOF AREA OR ROOF SECTION
 OF ANY EXISTING BUILDING OR STRUCTURE SHALL BE
 REPAIRED, REPLACED OR RECOVERED IN ANY 12 MONTH PERIOD
 UNLESS THE ENTIRE ROOFING SYSTEM OR ROOF SECTION
 CONFORMS TO REQUIREMENTS OF THIS CODE.
  
 2) SHEET A-3:
 2A-B) COMPLIED>
  
 2C) 3D REQUEST. SEMI-COMPLIED.
 FRONT ENTRY DOORS, INDICATE THEY ARE HORIZONTAL SLIDING
 DOORS, PLEASE PROVIDE COMPLIANCE WITH FBC-B 1008.1.10 /
 1008.1.10 PANIC AND FIRE EXIT HARDWARE. DOORS SERVING A
 GROUP H OCCUPANCY AND DOORS SERVING ROOMS OR SPACES
 WITH AN OCCUPANT LOAD OF 50 OR MORE IN A GROUP A OR E
 OCCUPANCY SHALL NOT BE PROVIDED WITH A LATCH OR LOCK
 UNLESS IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE, NOT
 JUST BREAK AWAY PANELS. SHEET A-7 INDICATES BREAK OUT
 PANELS BUT TO DATE NO PRODUCT APPROVALS HAVE BEEN
 SUBMITTED SHOWING PANIC OR FIRE EXIT HARDWARE.
  
 3) SHEET A-4:
 3A-B) COMPLIED>
  
  
  
  
  
 3C) COMPLIED. ;
  
 4) COMPLIED.
  
 5) PROVISO:
 SHEET A-8:
 5A) NEW COOLERS AND FREZZERS ARE UNDER SEPARATE PERMIT.
 NOT PART OF THIS REVIEW.
  
 5B) COMPLIED>
  
 6) PROVISO:
 SHEET A-9 AWNINGS ARE UNDER A SEPARATE PERMIT, NOT PART
 OF THIS REVIEW AS WELL AS SIGNS.
  
 7) S1 & S2:
 7A) 3RD REQUEST:
 SHEET A-8 & A-11 DETAIL B & E INDICATES BACK OF HOUSE
 FREZER LOCATION, EXISTING CBS WALLS W/ NEW ROOF
 STRUCTURE AND ROOFING. THE S-1 SHOWS THIS AREA WITH
 VARIOUS DETAILS.
 7A)(1) THE EXTERIOR WALL SECTION D/S2 IS A CUT SECTION
 THRU THE WALL BUT THE DETAIL IS FOR A HEADER THRU A
 WALL OPENING, WRONG DETAIL NOT FOR A WALL SECTION.
 107.2.1.3 DISCREPANCY IN PLANS.
  
 7A)(2) NONE OF THE DETAILS ON SHEET S-2 SHOW SIMILAR
 WALL, CONCRETE ROOF SECTION AND BEAM TO BE POURED INTO
 THE EXISTING CBS WALL AS SHOWN ON SHEET A-8 DETAIL E.
 NEITHER IS THERE SHOWN VERTICAL COLUMN PLACEMENT TYING
 THE FOOTER THRU TO THE ROOF SLAB MAKING THE MWFRS MAIN
 WIND FORCE RESISTING SYSTEM. MISSING DETAILS OR
 MISLABELED. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 7A)(3) SHEET S-1 THE CHICKEN COOLER & FREZZER DOES NOT
 HAVE ANY WALL TAGS IDENTIYING DWTAILS FOR CONSTRUCTION,
 COLUMNS, BEAMS & ROOF FRAMING/ SLAB MEMBERS. MISSING
 DETAILS OR MISLABELED. 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 7B) COMPLIED>
  
 8) COMPLIED>
  
 9) 2ND REQUEST ,2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR AUTOMATIC BYPASS DOORS SEMI COMPLIED,
 THE PRODUCT APPROVAL IS FOR BREAK AWAY DOORS BUT THEY
 DO NOT COMPLY WITH
 2010 FBC-B 1008.1.10 PANIC AND FIRE EXIT HARDWARE.
 DOORS SERVING A GROUP H OCCUPANCY AND DOORS SERVING
 ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN
 A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A
 LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 (D) ROOFING SYSTEMS, NO PRODUCT APPROVALS FOR WOOD
 DECKS
  
 NOA 13-0424.11
 P-12
 DECK TYPE:31 CONRETE DECK, INSULATED
 MAX DESIGN PRESS: -162 PSF LIMITAQTION #9
 FOR RECOVER VERIFY ONLY ONE ROOF & PULL TEST
  
 (G) NO PRODUCT APPROVALS SUBMITTED. PRE-ENGINEERED A/C
 STANDS
  
 10) THE FOLLOWING ITEMS WILL DEAL WITH ROOFING REPORTS
 BE ADVISED OF THE INFORMATION THAT WILL NEED TO BE
 HIGHLIGHTED BEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT; THIS ROOF IS MISSING OR NOT IN COMPLIANCE
 WITH THE FOLLOW ITEMS:
 (FLAT ROOF) NEW FLAT ROOF OVER FREZZER COMPARTMENT.
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. ___
 CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE USED.
 ___ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE ___
 .
 ___ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED FASTENER SPACING, PREPARED
 , SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
 ___ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
 11) NEW COMMENT. SHEET A-9 THE NORTH ELEVATION SHOWS A
 EXTERIOR WALL MOUNED LADDER THAT ALLOWS ENTRY INTO THE
 MECHANICAL MEZZANINE. THE PLANS DO NOT INDICATE HOW
 ACCESS TO THE ROOF TOP A/C UNITS. 2010 FBC-B 1509.6
 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES.
 WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH
 ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES (762 MM) HIGH.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-02-25 Cont ID  
Sent By jwitmer Date 2014-02-25 Time 07:42 Rev Time 0.00
Received By jwitmer Date 2014-02-25 Time 06:00 Sent To  
Notes
2014-02-25 06:04:43BUILDING PLAN REVIEW
 PERMIT: 13090329
 ADD: 5011 BROADWAY
 CONT: TO BE DETERMINED
 TEL: (305)331-1400
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUE. FEB. 25
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1) SHEET A-1:
 1A) COMPLIED>
 MISSING TO WHAT EDITION OF CODE THIS BUILDING DESIGN
 AND PERMIT WERE DESIGNED TO, 2010 FBC-B, 2010 FL
 EXISTING BUILDING CODE & 2010 FL ACCESSIBILITY CODE,
 1B) 2ND REQUEST:
 OCCUPANCY, EXIT & PLUMBING FACILITY DATA, MISSING THE
 MINIMUM BUILDING TYPE OF CONSTRUCTION 107.3.5.1.1(3)
 TABLE 503.
 LIFE SAFETY SHEET LS1 INDICATES THIS BUILDING IS
 DESIGNED AS A TYPE III PROTECTED (1 HOUR FIRE RATING)
 SEE FBC-B TABLE 601 FOR REQUIRED FIRE RATINGS FOR
 EXTERIOR WALLS PRIMARY STRUCTURAL FRAME, ROOF
 CONSTRUCTION AND SECONDARY MEMBERS. 2010 FBC-B TABLE
 601 FOOTNOTE B PROVIDES REDUCTION IN HOURS, A TYPE
 BUILDING ALL REQUIRE A MINIMUM OF 1 HOUR FIRE RATING OF
 ROOF FRAMING MEMBERS, SEE BUILDING TYPE IIIA FOOTNOTES
 ,B, C &D.
 SHEET A8 DOES NOT INDICATE ANY RATING ON STRUCTURAL
 MEMBERS.
  
 1C) 2ND REQUEST.
 WEST PALM BEACH ADMINISTRATIVE AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 EDITION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
 FIRE PROTECTION NOTES INDICATE THAT THE BUILDING IS TO
 BE FIRE SPRINKLERED, THE 2010 FBC-B 903.2.7 NEW WORK
 REQUIRES SPRINKLERS FOR MERCANTILE AREAS WITH A FIRE
 AREA GREATER THAN 12,000 SQ FT. NO FIRE SPRINKLER PLANS
 WERE SUBMITTED. 107.3.5.1.1( 5) FIRE SUPPRESSION.
  
 1D) 2ND REQUEST,
 IS THERE GOING TO BE A NEW ROOF TO BE PUT ON UNDER THIS
 PROJECT, IF SO THIS WILL BECOME A LEVEL III ALTERATION
 AND WILL AFFECT FUTURE REVIEWS AND CODE REQUIREMENTS,
 THERE IS A NOTE THAT THE BACK OF THE BUILDING A NEW
 ROOF STRUCTURE AND ROOF TO BE APPLIED. SHEET A-12 NOTE
 ONE INDICATES TO ONLY TO REPAIR ALL NEW PENETRATIONS.
 REVIEW 2010 EXST BLDG CODE SECTION 611.1.1 NOT MORE
 THAN 25 PERCENT OF THE TOTAL ROOF AREA OR ROOF SECTION
 OF ANY EXISTING BUILDING OR STRUCTURE SHALL BE
 REPAIRED, REPLACED OR RECOVERED IN ANY 12 MONTH PERIOD
 UNLESS THE ENTIRE ROOFING SYSTEM OR ROOF SECTION
 CONFORMS TO REQUIREMENTS OF THIS CODE.
  
 2) SHEET A-3:
 2A-B) COMPLIED>
  
 2C) 2ND REQUEST,
 FRONT ENTRY DOORS, INDICATE THEY ARE HORIZONTAL SLIDING
 DOORS, PLEASE PROVIDE COMPLIANCE WITH FBC-B 1008.1.10 /
 1008.1.10 PANIC AND FIRE EXIT HARDWARE. DOORS SERVING A
 GROUP H OCCUPANCY AND DOORS SERVING ROOMS OR SPACES
 WITH AN OCCUPANT LOAD OF 50 OR MORE IN A GROUP A OR E
 OCCUPANCY SHALL NOT BE PROVIDED WITH A LATCH OR LOCK
 UNLESS IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 3) SHEET A-4:
 3A-B) COMPLIED>
  
 3C) 2ND REQUEST;
 NOTE 88 INDICATES THE USE OF PROPANE TANKS ON SITE (2)
 100 GALLON ABOVE GROUND LP TANKS. [F] 414.6 OUTDOOR
 STORAGE, DISPENSING AND USE.
 THE OUTDOOR STORAGE, DISPENSING AND USE OF HAZARDOUS
 MATERIALS SHALL BE IN ACCORDANCE WITH THE FLORIDA FIRE
 PREVENTION CODE.
 PLEASE PROVIDE MSDS SHEETS. F] 414.6.1 WEATHER
 PROTECTION.
 WHERE WEATHER PROTECTION IS PROVIDED FOR SHELTERING
 OUTDOOR HAZARDOUS MATERIAL STORAGE OR USE AREAS, SUCH
 AREAS SHALL BE CONSIDERED OUTDOOR STORAGE OR USE WHEN
 THE WEATHER PROTECTION STRUCTURE COMPLIES WITH SECTIONS
 414.6.1.1 THROUGH 414.6.1.3.
  
 4) COMPLIED>
  
 5) PROVISO:
 SHEET A-8:
 5A) NEW COOLERS AND FREZZERS ARE UNDER SEPARATE PERMIT.
 NOT PART OF THIS REVIEW.
  
 5B) COMPLIED>
  
 6) PROVISO:
 SHEET A-9 AWNINGS ARE UNDER A SEPARATE PERMIT, NOT PART
 OF THIS REVIEW AS WELL AS SIGNS.
  
 7) S1 & S2:
 7A) 2ND REQUEST:
 NEITHER S1 OR S2 SHOW A NEW ROOFING SYSTEM, SHEET A-8 &
 A-11 DETAIL A INDICATES BACK OF HOUSE FREZER LOCATION,
 EXISTING CBS WALLS W/ NEW ROOF STRUCTURE AND ROOFING.
 PART OF THE MWFRS NO INFORMATION AS TO DESIGN ON ANY
 ARCHITECTURAL NOR STRUCTURAL SHEETS.
  
 7B) COMPLIED>
  
 8) COMPLIED>
  
 9) 2ND REQUEST ,2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR AUTOMATIC BYPASS DOORS SEMI COMPLIED,
 THE PRODUCT APPROVAL IS FOR BREAK AWAY DOORS BUT THEY
 DO NOT COMPLY WITH
 2010 FBC-B 1008.1.10 PANIC AND FIRE EXIT HARDWARE.
 DOORS SERVING A GROUP H OCCUPANCY AND DOORS SERVING
 ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN
 A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A
 LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 (D) ROOFING SYSTEMS
 NO PRODUCT APPROVALS FOR WOOD DECKS
  
 NOA 13-0424.11
 P-12
 DECK TYPE:31 CONRETE DECK, INSULATED
 MAX DESIGN PRESS: -162 PSF LIMITAQTION #9
 FOR RECOVER VERIFY ONLY ONE ROOF & PULL TEST
  
 (G) NO PRODUCT APPROVALS SUBMITTED. PRE-ENGINEERED A/C
 STANDS
  
 10) THE FOLLOWING ITEMS WILL DEAL WITH ROOFING REPORTS
 BE ADVISED OF THE INFORMATION THAT WILL NEED TO BE
 HIGHLIGHTED BEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT; THIS ROOF IS MISSING OR NOT IN COMPLIANCE
 WITH THE FOLLOW ITEMS:
 (FLAT ROOF)
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. ___
 CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE USED.
 ___ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE ___
 .
 ___ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED FASTENER SPACING, PREPARED
 , SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
 ___ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-10-01 Cont ID  
Sent By jwitmer Date 2013-10-01 Time 10:21 Rev Time 0.00
Received By jwitmer Date 2013-09-30 Time 16:27 Sent To  
Notes
2013-10-01 10:20:27BUILDING PLAN REVIEW
 PERMIT: 13090329
 ADD: 5011 BROADWAY
 CONT: TO BE DETERMINED
 TEL: (305)331-1400
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. FEB. 25/2014
 ACTION: DENIED
  
 1) SHEET A-1:
 1A) COMPLIED.
 MISSING TO WHAT EDITION OF CODE THIS BUILDING DESIGN
 AND PERMIT WERE DESIGNED TO, 2010 FBC-B, 2010 FL
 EXISTING BUILDING CODE & 2010 FL ACCESSIBILITY CODE,
  
  
 1B) 2ND REQUEST ,
 OCCUPANCY, EXIT & PLUMBING FACILITY DATA, MISSING THE
 MINIMUM BUILDING TYPE OF CONSTRUCTION 107.3.5.1.1(3)
 TABLE 503.
 LIFE SAFETY SHEET LS1 INDICATES THIS BUILDING IS
 DESIGNED AS A TYPE III PROTECTED/ IIIA (1 HOUR FIRE
 RATING) SEE FBC-B TABLE 601 FOR REQUIRED FIRE RATINGS
 FOR EXTERIOR WALLS PRIMARY STRUCTURAL FRAME, ROOF
 CONSTRUCTION AND SECONDARY MEMBERS, SEE FOOTNOTE B .
 SHEET A8 NOR S-2 STRUCTURAL NOTES # 9, DOES NOT
 INDICATE ANY RATING ON STRUCTURAL MEMBERS.
  
 1C) 2ND REQUEST,
 WEST PALM BEACH ADMINISTRATIVE AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 EDITION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS: 107.3.5.1.1 BUILDING
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE:
 SCHEMATIC FIRE SPRINKLERS
 STANDPIPES
 PRE-ENGINEERED SYSTEMS
  
 FIRE PROTECTION NOTES INDICATE THAT THE BUILDING IS TO
 BE FIRE SPRINKLERED, THE 2010 FBC-B 903.2.7 NEW WORK
 REQUIRES SPRINKLERS FOR MERCANTILE AREAS WITH A FIRE
 AREA GREATER THAN 12,000 SQ FT. NO FIRE SPRINKLER PLANS
 WERE SUBMITTED. 107.3.5.1.1( 5) FIRE SUPPRESSION.
 1D) IS THERE GOING TO BE A NEW ROOF TO BE PUT ON UNDER
 THIS PROJECT, IF SO THIS WILL BECOME A LEVEL III
 ALTERATION AND WILL AFFECT FUTURE REVIEWS AND CODE
 REQUIREMENTS, THERE IS A NOTE THAT THE BACK OF THE
 BUILDING A NEW ROOF STRUCTURE AND ROOF TO BE APPLIED.
 SHEET A-12 NOTE ONE INDICATES TO ONLY TO REPAIR ALL NEW
 PENETRATIONS. REVIEW 2010 EXST BLDG CODE SECTION
 611.1.1 NOT MORE THAN 25 PERCENT OF THE TOTAL ROOF AREA
 OR ROOF SECTION OF ANY EXISTING BUILDING OR STRUCTURE
 SHALL BE REPAIRED, REPLACED OR RECOVERED IN ANY 12
 MONTH PERIOD UNLESS THE ENTIRE ROOFING SYSTEM OR ROOF
 SECTION CONFORMS TO REQUIREMENTS OF THIS CODE.
  
 2) SHEET A-3:
 2A-B) COMPLIED>
  
 2C) 2ND REQUEST. FRONT ENTRY DOORS, INDICATE THEY ARE
 HORIZONTAL SLIDING DOORS, PLEASE PROVIDE COMPLIANCE
 WITH FBC-B 1008.1.10
 1008.1.10 PANIC AND FIRE EXIT HARDWARE.
 DOORS SERVING A GROUP H OCCUPANCY AND DOORS SERVING
 ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN
 A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A
 LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
 NOA 13-0530 ARE A BREAK OUT DOOR, SHEET # 4 SHOWS
 HORIZONTAL MUTTINS, SHEET # 7 A 3 POINT KEYED DOOR.
  
 3) SHEET A-4:
 3A) PLANS SHOW THE CUSTOMER SERVICE COUNTER WITH A
 SYMBLE FOR ACCESSIBLILITY SIDE APPROACH BUT NO COUNTER
 HEIGHT IS GIVEN, SHEET A-10 DETAIL B INDICATES THE
 COUNTER HEIGHT OF 42 " PLEASE SHOW COMPLIANCE WITH 2010
 ACCESS CODE 904.4.1 OR 904.4.2.
  
 3B) PLEASE REVIEW THE SIDE APPROACH FOR THE DRINKING
 FOUNTAINS, THIS IS ONLY A EXCEPTION FOR CHILDRENS USE,
 SEE 2010 FL ACCESS CODE 602.2. 602.2 CLEAR FLOOR SPACE.
 UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH
 AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED. THE PLANS SHOULD
 SHOW A FORWARD APPROACH AND CENTERED ON THE UNIT.
  
 3C) 2ND REQUEST,
 NOTE 88 INDICATES THE USE OF PROPANE TANKS ON SITE (2)
 100 GALLON ABOVE GROUND LP TANKS. [F] 414.6 OUTDOOR
 STORAGE, DISPENSING AND USE.
 THE OUTDOOR STORAGE, DISPENSING AND USE OF HAZARDOUS
 MATERIALS SHALL BE IN ACCORDANCE WITH THE FLORIDA FIRE
 PREVENTION CODE.
 PLEASE PROVIDE MSDS SHEETS. F] 414.6.1 WEATHER
 PROTECTION.
 WHERE WEATHER PROTECTION IS PROVIDED FOR SHELTERING
 OUTDOOR HAZARDOUS MATERIAL STORAGE OR USE AREAS, SUCH
 AREAS SHALL BE CONSIDERED OUTDOOR STORAGE OR USE WHEN
 THE WEATHER PROTECTION STRUCTURE COMPLIES WITH SECTIONS
 414.6.1.1 THROUGH 414.6.1.3.
  
 4) COMPLIED>
 SHEET A7DOOR & WINDOW ELEVATION FRONT ENTRY BY-PASS
 DOORS INDICATE A TRANSOM ABOVE, DETAIL 8 INDICATES THE
 USE OF A 4X6 STEEL TUBE, THE STRUCTURAL PLANS DO NOT
 INDICATE SUCH A DETAIL NOR DESIGN CONDITIONS.
 2010 FBC-B 1715.5.5 MULLIONS OCCURRING BETWEEN
 INDIVIDUAL WINDOW AND GLASS DOOR ASSEMBLIES. 1715.5.5.1
 MULLIONS. 1715.5.5.2 LOAD TRANSFER.
 1715.5.5.3 DEFLECTION & 1715.5.5.4 STRUCTURAL SAFETY
 FACTOR.
  
 5) PROVISO:
 SHEET A-8:
 5A) NEW COOLERS AND FREZZERS ARE UNDER SEPARATE PERMIT.
 NOT PART OF THIS REVIEW.
  
 5B) 2ND REQUEST,
 SHEET A8 & A11 BOTH INDICATE A NEW CONCRETE SLAB FOR
 THE ROOF DECK, TO SEE STRUCTURAL PLANS, NO ROOF DECK
 DETAIL?
 PLEASE PROVIDE A ROOF PLAN INDICATING WHICH PORTIONS OF
 THE ROOFFRAMING ARE BAR JOIST AND WHICH ARE 2X? AND
 THERE SPACING? 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 6) PROVISO>
 SHEET A-9 AWNINGS ARE UNDER A SEPARATE PERMIT, NOT PART
 OF THIS REVIEW AS WELL AS SIGNS.
  
 7) S1 & S2:
 7A) NEITHER S1 OR S2 SHOW A NEW ROOFING SYSTEM, SHEET
 A-1 & A-11 DETAIL A INDICATES BACK OF HOUSE FREZER
 LOCATION, EXISTING CBS WALLS W/ NEW ROOF STRUCTURE AND
 ROOFING. PART OF THE MWFRS NO INFORMATION AS TO DESIGN
 ON ANY ARCHITECTURAL NOR STRUCTURAL SHEETS.
  
 7B)COMPLIED>
 WIND DESIGN.
  
 8) COMPLIED>
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) 2ND REQUEST, 2010 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.-AUTOMATIC BYPASS,
  
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 NO ROOFING APPAROVALS FOR WOOD DECK W/ WOOD JOIST
  
 NOA 13-0424.11
 GAF CONVENTIONAL BUILT UP ROOF SYSTEM W/ CONCRETE DECK
 P. 12
 DECK TYPE 31: CONCRETE DECK, INSULATED
 MAXIMUM DESIGN PRESSURE -162 PSF LIMITATION # 9
 IF A ROOF OVER VERIFY ONE ROOFING SYSTEM, AND PULL TEST
 REQUIRED.
  
 (G) NO PRE-ENGINEERED A/C STANDS PRODUCT APPROVALS
 SUBMITTED.
  
 10) SEMI-COMPLIED.
 THE FOLLOWING ITEMS WILL DEAL WITH ROOFING REPORTS BE
 ADVISED OF THE INFORMATION THAT WILL NEED TO BE
 HIGHLIGHTED BEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT; THIS ROOF IS MISSING OR NOT IN COMPLIANCE
 WITH THE FOLLOW ITEMS:
 (FLAT ROOF)
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. ___
 CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE USED.
 ___ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE ___
 .
 ___ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED FASTENER SPACING, PREPARED
 , SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
 ___ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
 11) 2ND REQUEST.
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-05-07 Cont ID  
Sent By skennedy Date 2015-05-07 Time 11:47 Rev Time 0.00
Received By skennedy Date 2015-05-07 Time 11:47 Sent To  
Notes
2015-05-07 14:29:13THE EXTENT OF THIS REVIEW WAS LIMITED ONLY TO THE
 VERIFICATION OF THE PREVIOUSLY REQUIRED CORRECTIONS
 FROM DAVE HAYES' REVIEW
2015-05-07 11:48:26REVIEW BY MIKE ALBARRAN PX3353

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-11-04 Cont ID  
Sent By dhayes Date 2014-11-03 Time 15:55 Rev Time 0.00
Received By dhayes Date 2014-11-03 Time 15:55 Sent To  
Notes
2014-11-04 09:39:5211/3/2014
 PROJECT: TROPICAL SUPERMARKET
 PERMIT#: 13090329
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) RISER DIAGRAM AND PANEL SCHEDULES DOES NOT MATCH UP
 WITH RISER DIAGRAM KEY NOTES. VOLTAGE OF ELECTRICAL
 SYSTEM IN NOTE A IS INDICATED AT 277/480V 3PH 4 WIRE
 BUT EVERYWHERE ELSE IS INDICATED AT 120/208V 3PH 4
 WIRE. REVISE PLANS ACORDINGLY. 2010 WPB AMENDMENTS TO
 THE FBC 107.2.1
  
 2) THE RISER DIAGRAM KEY NOTES, LETTER AND NUMBER
 IDENTIFICATION MARKERS ARE BARELY LEGIBLE.
 CLARIFICATION REQUIRED. 2010 WPB AMENDMENTS TO THE FBC
 107.2.1
  
 3) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 4) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16, 110.22
  
 5) CLARIFY LOCATION AND SOURCE FOR ROOFTOP
 REFRIGERATION RACK DISCONNECT. RISER DIAGRAM INDICATES
 A TAP RULE IS UTILIZED TO FEED AN 800AMP DISCONNECT
 FROM A 1600AMP MTS GROUPED WITH SERVICE EQUIPMENT THAT
 THEN FEEDS THE REFRIGERATION RACK. CLARIFICATION IS
 REQUIED. INDICATE ON THE ELECTRICAL PLANS, WHERE IS THE
 REFRIGERATION RACK DISCONNECT LOCATED? HOW IS IT FED
 AND FROM WHERE? 2010 WPB AMENDMENTS TO THE FBC 107.2.1
  
 6) VERIFY SUFFICIENT ACCESS AND WORKING SPACE IS
 PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT,
 SPECIFICALLY AT THE MEZNINNINE, TO PERMIT READY AND
 SAFE OPERATION AND MAINTENANCE OF SUCH EQUIPMENT. NEC
 110.26
  
 7) PROVIDE A COMPLETE LIGHTING SUMMARY INDICATING
 COMPLIANCE WITH THE FBC ENERGY CONSERVATION 505.3.
  
 8) EMERGENCY ILLUMINATION SHALL INCLUDE ALL REQUIRED
 MEANS OF EGRESS LIGHTING, ILLUMINATED EXIT SIGNS, AND
 ALL OTHER LIGHTS SPECIFIED AS NECESSARY TO PROVIDE
 REQUIRED ILLUMINATION. EMERGENCY LIGHTING SYSTEMS SHALL
 BE DESIGNED AND INSTALLED SO THAT THE FAILURE OF ANY
 INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING OUT OF
 A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE THAT
 REQUIRES EMERGENCY ILLUMINATION. NEC 700.16
  
 9) THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES. THE BRANCH CIRCUIT THAT FEEDS UNIT EQUIPMENT
 SHALL BE CLEARLY IDENTIFIED AT THE DISTRIBUTION PANEL.
 EMERGENCY LUMINAIRES THAT OBTAIN POWER FROM A UNIT
 EQUIPMENT AND ARE NOT PART OF THE UNIT EQUIPMENT SHALL
 BE WIRED TO THE UNIT EQUIPMENT AS REQUIRED BY 700.9 AND
 BY ONE OF THE WIRING METHODS OF NEC CHAPTER 3. NEC
 700.12(F)
  
 10) VERIFY ALL ELECTRIC UNDER THE HOOD TO BE
 DISONNECTED UPON ACTIVATION OF THE FIRE SUPRESSION
 SYSTEM. NFPA 1, SECTION 50.4.6.1
  
 11) PROVIDE THE SIGN WITH AT LEAST ONE OUTLET SUPPLIED
 BY A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT
 SUPPLIES NO OTHER LOAD. NEC 600.5
  
 12) VERIFY THE SIGN HAS AN EXTERNALLY OPERABLE SWITCH
 OR CIRCUIT BREAKER THAT WILL OPEN ALL UNGROUNDED
 CONDUCTORS WITHIN SIGHT OF THE SIGN OR OUTLINE LIGHTING
 SYSTEM THAT IT CONTROLS. NEC 600.6(A)(1)
  
 13) VERIFY THE SIGN IS CONTROLLED BY A TIMER AS
 REQUIRED BY FBC-E 505.2.4.
  
 14) PROVIDE A DEDICATED BRANCH CIRCUIT FOR THE FIRE
 ALARM SYSTEM. NFPA 72, 10.5.5
  
 15) A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 IS REQUIRED FOR GENERATOR, HOOD, FIRE ALARM, SECURITY
 SYSTEM, CCTV, ACCESS CONTROL, NETWORK, POS, AND
 COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
2014-10-15 11:41:01NEW SHEETS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-10-29 Cont ID  
Sent By albarran Date 2013-10-29 Time 18:12 Rev Time 0.00
Received By albarran Date 2013-10-29 Time 16:27 Sent To  
Notes
2013-10-29 18:15:47AS PER THE PLANS, A SEPARATE PERMIT AND SUBMITTAL
 PACKAGE WILL BE REQUIRED FOR THE FIRE ALARM.
 SENT BACK TO BIN FOR FURTHER REVIEWS

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2015-07-06 Cont ID  
Sent By pleduc Date 2015-07-06 Time   Rev Time 0.00
Received By pleduc Date 2015-07-06 Time 16:28 Sent To  
Notes
2015-07-06 16:29:21RESTAMPED BY FIRE PREVENTION

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2015-03-26 Cont ID  
Sent By pleduc Date 2015-03-26 Time   Rev Time 0.00
Received By pleduc Date 2015-03-26 Time 13:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2014-10-23 Cont ID  
Sent By pleduc Date 2014-10-23 Time   Rev Time 0.00
Received By pleduc Date 2014-10-23 Time 11:25 Sent To  
Notes
2014-10-23 12:28:54THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE TWO PREVIOUS RECORDED FIRE COMMENTS NOTED THAT THE
 PLAN WAS FAILED DUE TO NO SPRINKLER OR FIRE ALARM
 DRAWINGS ARE INCLUDED.
  
 SPRINKLER AND FIRE ALARM PLANS WERE NOT SUBMITTED AS A
 PART OF THIS SUBMITTAL AND HAS BEEN DENIED. PLEASE NOTE
 THE PREVIOUS SUBMIITED COMMENTS OF FIRE AND PROVIDE THE
 DOCUMENTS ACCORDINGLY.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2014-02-25 Cont ID  
Sent By wjolin Date 2014-02-25 Time 13:29 Rev Time 0.00
Received By wjolin Date 2014-02-25 Time 11:11 Sent To  
Notes
2014-02-25 13:29:495011 BROADWAY
 PERMIT #13090329
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. FOR ISSUANCE
 OF A GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF
 THE FLORIDA BUILDING CODE REQUIRES SEALED FIRE
 PROTECTION CONSTRUCTION DOCUMENTS FOR THE DESIGN OR
 ALTERATION OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER
 FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-09-20 Cont ID  
Sent By lphilmor Date 2013-09-20 Time 14:58 Rev Time 0.00
Received By lphilmor Date 2013-09-19 Time 15:10 Sent To  
Notes
2013-09-20 14:16:435011 BROADWAY
 PERMIT #
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1. PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
 2. UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION
 OF THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS
 3. PER NFPA 101, 2010 ED - 36.2.5.2.1 DEAD-END
 CORRIDORS ARE NOT TO EXCEED 20 FT.
 4. SHOW LOCATION OF TYPE K FIRE EXTINGUISHER.
 5.PLANS INDICATE THAT THE BUILDING WILL HAVE AN
 APPROVED AUTOMATIC SUPERVISED SPRINKLER SYSTEM, BUT NO
 SPRINKLER LAYOUT IS PROVIDED.
  
  
 LAUREN PHILMORE
 FIRE INSPECTOR II / INVESTIGATOR I
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4783
  
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2015-04-17 Cont ID  
Sent By tklarge Date 2015-04-17 Time 12:01 Rev Time 0.00
Received By tklarge Date 2015-04-17 Time 11:08 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2014-10-27 Cont ID  
Sent By tklarge Date 2014-10-27 Time 11:45 Rev Time 0.00
Received By tklarge Date 2014-10-27 Time 11:35 Sent To  
Notes
2014-10-27 11:45:261) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS
 EQUIPMENT / APPLIANCES. EQUIPMENT / APPLIANCES SHALL BE
 LISTED AND LABELED PER THE 2010 FL. GAS CODE SEC.
 301.3.
 2) THE GAS PIPING IS UNDERSIZED FOR THE TOTAL LOAD
 CONNECTED THERETO. THE MAXIMUM LOAD FOR A 1" LINE AT 50
 FT. WITH 552,000 BTU LOAD IS 480,000 BTU'S. THE MINIMUM
 SIZE SHALL BE 1 1/4" PER TABLE 402.4 (26 ) OF THE 2010
 FGC.
 3) THE SEDIMENT TRAPS SHALL BE INSTALLED IN ACCORDANCE
 WITH THE 2010 FGC SEC.408.4.408.4 SEDIMENT TRAP.
 WHERE A SEDIMENT TRAP IS NOT INCORPORATED AS PART OF
 THE APPLIANCE , A SEDIMENT TRAP SHALL BE INSTALLED
 DOWNSTREAM OF THE APPLIANCE SHUTOFF VALVE AS CLOSE TO
 THE INLET OF THE APPLIANCE AS PRACTICAL. THE SEDIMENT
 TRAP SHALL BE EITHER A TEE FITTING HAVING A CAPPED
 NIPPLE OF ANY LENGTH INSTALLED VERTICALLY IN THE
 BOTTOMMOST OPENING OF THE TEE OR OTHER DEVICE APPROVED
 AS AN EFFECTIVE SEDIMENT TRAP. ILLUMINATING APPLIANCES,
 RANGES, CLOTHES DRYERS AND OUTDOOR GRILLS NEED NOT BE
 SO EQUIPPED.
 4) SUBMIT DETAILS FOR THE ANCHORING OF THE LP TANKS.
 TANKS SHALL BE ANCHORED TO WITHSTAND THE WIND LOADS PER
 THE 2010 FBC SEC.1609.
 5) THE LOCATION OF THE LP TANKS IN RELATION TO BUILDING
 OPENINGS LOCATED BELOW THE RELIEF VALVE OF THE TANKS
 AND THE DISTANCE AWAY FROM ANY SOURCE OF IGNITION SHALL
 COMPLY W/NFPA 58, SEC.6.3.7 (1) AND (2). SHOW THE
 DISTANCE OGF THE LP TANKS FROM THE DOOR AND ANY SOURCE
 OF IGNITION.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
2014-10-15 11:39:47NEW SHEET P-4 SUBMITTED. JG.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2014-02-25 Cont ID  
Sent By jwitmer Date 2014-02-25 Time 08:19 Rev Time 0.00
Received By jwitmer Date 2014-02-25 Time 08:00 Sent To  
Notes
2014-02-25 08:19:01GAS PLAN ON SHEET P4 CODE COMPLIANT,
 WILL REQUIRE A SEPARATE PERMIT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2013-09-18 Cont ID  
Sent By lwagner Date 2013-09-18 Time 14:29 Rev Time 0.00
Received By lwagner Date 2013-09-18 Time 13:55 Sent To  
Notes
2013-09-18 14:28:53FBC 2010 FUEL GAS REVIEW #1
 DENIED:
  
 1. SHEET P-4: PLEASE SHOW THE POSITION OF THE 2ND STAGE
 REGULATOR.
  
 2. SHEET P-4: PLEASE INCLUDE THE FBC 2010 FUEL GAS CODE
 TABLE USED FOR THE GAS CALCULATIONS. IF TABLE 402.4(26)
 IS BEING USED, THE SUPPLY PIPE WOULD REQUIRE 1" PIPE
 FOR 542,000 BTU AT 30 FEET.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-07-24 Cont ID  
Sent By lmarchan Date 2015-07-10 Time 09:25 Rev Time 0.00
Received By lmarchan Date 2015-06-03 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-04-17 Cont ID  
Sent By   Date 2015-04-17 Time   Rev Time 0.00
Received By shill Date 2015-03-19 Time 08:07 Sent To  
Notes
2015-03-20 08:10:48C32
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-11-25 Cont ID  
Sent By skennedy Date 2014-11-25 Time 17:31 Rev Time 0.00
Received By skennedy Date 2014-10-14 Time 11:32 Sent To  
Notes
2014-10-15 11:33:24RE-SUBMITTAL SENT TO C4 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-03-10 Cont ID  
Sent By hmoser Date 2014-03-10 Time 14:20 Rev Time 0.00
Received By hmoser Date 2014-01-31 Time 09:14 Sent To  
Notes
2014-01-31 09:16:26INCOMING SENT TO C-04 BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-30 Cont ID  
Sent By shill Date 2013-10-30 Time 17:26 Rev Time 0.00
Received By shill Date 2013-09-11 Time 08:54 Sent To  
Notes
2013-09-13 08:54:46SENT TO C4 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2015-06-17 Cont ID  
Sent By ccole Date 2015-06-17 Time 15:10 Rev Time 0.00
Received By ccole Date 2015-06-17 Time 15:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2015-05-14 Cont ID  
Sent By skennedy Date 2015-05-14 Time 12:10 Rev Time 0.00
Received By skennedy Date 2015-03-19 Time 12:09 Sent To  
Notes
2015-05-14 12:22:54REVIEW BY CHRIS COLE
  
 1) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN AND SUBMIT
 SPECS FOR THE EXHAUST FAN AT THE DUMPSTER ENCLOSURE.
 2) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE
 RTU CURBS, THE REFRIGERATION CONDENSER STAND, AND THE
 ROOF TOP EXHAUST AND SUPPLY FANS.
 INCLUDE THE UNIT ATTACHMENT DETAILS TO THE CURBS AND
 STANDS, AND SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE
 NOA FOR THE CONDENSER STAND.
 3) PURSUANT TO PLANNING AND ZONING COMMENTS, AND
 SECTION 304.11 FMC-2010, PROVIDE EITHER A 42" HIGH
 PARAPET OR GUARD AT ANY ROOF EDGES WITHIN 10' OF THE
 HVAC EQUIPMENT.
 4) PLACE NOTES ON THE PLAN INDICATING SEPARATE PERMITS
 WILL BE OBTAINED FOR THE KITCHEN HOODS, AND FOR THE
 REFRIGERATION.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-11-03 Cont ID  
Sent By hmoser Date 2014-11-03 Time 08:33 Rev Time 0.00
Received By hmoser Date 2014-10-31 Time 14:10 Sent To  
Notes
2014-10-31 14:51:19PASS PROVISO
 COMMERCIAL HOOD AND REFRIGERATION ARE NOT INCLUDED IN
 THIS REVIEW.
 SEPARATE APPLICATION, PLAN AND PERMIT REQUIRED.
  
 PROVIDE A DETAIL FROM THE ENGINEER ON CURB TIE DOWN TO
 ROOF
 AND RTU TIE DOWN TO CURB PER SECTION 301.12 WIND
 RESISTANCE.
 2010 FBC (M) ( AT FIRST INSPECTION)
  
 REFER TO SECTION 304.11 GUARDS.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-03-10 Cont ID  
Sent By hmoser Date 2014-03-10 Time 14:07 Rev Time 0.00
Received By hmoser Date 2014-03-10 Time 14:07 Sent To  
Notes
2014-03-10 14:20:081) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS.
 2010 FLORIDA ENERGY CODE.
 2) HOOD, WALK IN COOLERS AND REFRIGERATION
 REQUIRE SEPARATE PERMITS AND PLANS.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-10-10 Cont ID  
Sent By hmoser Date 2013-10-10 Time 10:26 Rev Time 0.00
Received By hmoser Date 2013-10-10 Time 08:49 Sent To  
Notes
2013-10-10 10:26:53PLANS DENIED
 1) EXHAUST FAN #4 IS NOT ON VENTILATION
 SCHEDULE. PAGE M-4 OF THE PLAN.
 2) PLAN SHOW EXHAUST FAN 4 DISCHARGING
 OVER FISH COOLER ON PAGE M-1 OF PLAN.
 REFER TO SECTION 501.2 EXHAUST DISCHARGE
 2010 FBC (M)
 3) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS
 ( FOR FRESH AIR AND EXHAUST) 2010 FLORIDA ENERGY CODE.
 4) HOOD AND COOLERS AND REFRIGERATION REQUIRE SEPARATE
 APPLICATION PLANS AND PERMITS
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 5 Status P Date 2015-07-08 Cont ID  
Sent By tklarge Date 2015-07-06 Time 14:10 Rev Time 0.00
Received By tklarge Date 2015-07-06 Time 14:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2015-04-17 Cont ID  
Sent By tklarge Date 2015-04-17 Time 11:07 Rev Time 0.00
Received By tklarge Date 2015-04-17 Time 09:06 Sent To  
Notes
2015-04-17 10:43:501) SHT. A-6 - THE CLEAR FLOOR SPACE FOR THE DRINKING
 FOUNTAIN DOES NOT COMPLY WITH THE 2010 FL.
 ACCESSIBILITY CODE SEC.602. THE CLEAR FLOOR SPACE SHALL
 BE CENTERED ON THE UNIT. THE PLANS SHOW THE CLEAR FLOOR
 SPACE CENTERED ON BOTH DRINKING FOUNTAINS AS A WHOLE.
 THE CLEAR FLOOR SPACE SHALL BE CENTERED ON THE LOW UNIT
 PER THIS CODE SECTION.AS DESIGNED THERE IS NOT 15
 INCHES TO THE CENTER OF THE LOW UNIT.
 2) THE VENT FOR THE FLOOR DRAIN IN THE MEZZANINE SHALL
 CONNECT TO THE HORIZONTAL DRAIN ABOVE THE CENTERLINE OF
 THE HORIZONTAL DRAIN PIPE. AS DRAWN, IT IS A FLAT, DRY
 VENT WHICH IS PROHIBITED BY THE PLUMBING CODE.SEC.
 905.3.
  
 PLEASE CONTACT ME SO WE CAN DISCUSS THESE ITEMS TO GET
 THEM RECTIFIED SO I CAN APPROVE THE PLUMBING PORTION OF
 THE REVIEW. THANK YOU.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2014-10-27 Cont ID  
Sent By tklarge Date 2014-10-27 Time 13:10 Rev Time 0.00
Received By tklarge Date 2014-10-27 Time 11:46 Sent To  
Notes
2014-10-27 13:10:26WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 1) SHT. A-6 - THE ELEVATION DETAILS ON THE PLAN ARE
 NOTED AS BEING ON SHT. A-5. REVISE ALL THE DETAILS TO
 SHOW SHT. A-6 WHICH IS THE PAGE WHERE THEY ARE LOCATED.
 2) NONE OF THE ELEVATIONS ON SHT. A-6 CORRELATE WITH
 THE FLOOR PLAN.
 3) THE FLUSH VALVE ON THE WATER CLOSET IN THE WOMEN'S
 RESTROOM SHALL BE ON THE WIDE SIDE OF THE WATER CLOSET
 PER THE 2010 FBC, ACCESSIBILITY, SEC. 604.6.
 4) THE TOILET PAPER DISPENSER SHALL BE LOCATED A
 MINIMUM OF 7" AND A MAXIMUM OF 9" IN FRONT OF THE WATER
 CLOSET MEASURED TO THE CENTERLINE OF THE DISPENSER.
 5) SHOW THE DIMENSIONS OF THE REQUIRED CLEAR FLOOR
 SPACE FOR THE LAVATORY AND THE WATER CLOSET IN THE
 TOILET ROOMS. COMPLY WITH SECS. 305.3 AND 604.3.1.
 6) SHT. A-6 - ELEVATION 9/A-5 - THIS ELEVATION DOESN'T
 CORRELATE WITH ANY OF THE TOILET ROOMS. DELETE THIS
 ELEVATION.
 7) SHT. A-6- ELEVATION "C" - SHOW THE HEIGHT OF THE
 SPOUT ON THE DRINKING FOUNTAIN FOR STANDING PERSONS PER
 THE 2010 FL. ACCESSIBILITY CODE SEC. 602.7.
 8) SHT. A-6 - KNEE AND TOE CLEARANCES FOR THE
 ACCESSIBLE DRINKING FOUNTAIN SHALL BE A MIN. OF 30
 INCHES WIDE PER THE 2010 FAC SECS. 305.3, 306.2.5,
 306.3.5. THE CLEAR FLOOR SPACE SHALL BE CENTERED ON THE
 UNIT. AS DESIGNED, THE DRINKING FOUNTAINS DO NOT COMPLY
 WITH THESE CODE SECTIONS.
 9) THE VENT FOR THE DUMPSTER SHALL COMPLY WITH THE 2010
 FLORIDA PLUMBING CODE SEC.905.3. A FLAT, DRY VENT IS
 NOT PERMITTED.
 10) THE DISCHARGE FROM THE REFRIGERATED CASES SHALL NOT
 DISCHARGE TO THE GREASY WASTE SYSTEM PER THE 2010 FPC
 SEC.1003.2.
 11) ANY INDIRECT WASTE THAT EXCEEDS 2 FT. IN LENGTH
 HORIZONTALLY OR 4 FT. IN TOTAL DEVELOPED LENGTH SHALL
 BE TRAPPED PER THE 2010 FBC SEC.802.2.
 12) SUBMIT CALCULATIONS FOR THE GREASE TRAP IN
 ACCORDANCE WITH SEC. 1003.5.1.
 13) SHT. P-1 - REFERS TO DETAIL 3/P-1 FOR FRENCH DRAIN
 DETAIL.THERE IS NO SUCH DETAIL ON THE PLAN.
 14) THE FLOOR DRAIN IN THE THE MEZZANINE EXCEEDS THE
 DISTANCE FROM A VENT PER TABLE 906.1. 2010 FPC .
 15) LABEL THE MOP SINK AS SUCH ON THE SANITARY RISER.
 16) SHT. P-2- SHOW ALL THE INDIRECT WASTES TO THE FLOOR
 DRAINS ON SHT. P-2.
 17) SHT. P-4 - ALL HOSE BIBBS SHALL BE EQUIPPED WITH
 SHUTOFF VALVES PER SEC. 606.2 (2) OF 2010 FPC.
 18) SUBMIT INFO ON THE TRAP PRIMER VALVES FOR THE FLOOR
 DRAINS. THE WATER RISER SHOWS SHUTOFF VALVES ON THE
 TRAP PRIMER LINES. 1002.4.TRAP SEAL PRIMER VALVES SHALL
 COMPLY W/ ASSE 1018 OR ASSE 1044.
 19) THE TRAP SEAL LINE FOR THE FLOOR DRAIN BY ESPRESSO
 MACHINE IS NOT SHOWN ON THE WATER RISER.
 20) SUBMIT SPECIFICATIONS FOR THE WATER HEATER.SHOW THE
 SIZE OF THE PAN AND PAN DRAIN ON THE DETAIL. THE PAN
 AND DRAIN SHALL COMPLY W/ SEC. 504.7.1
 21) A MEANS OF CONTROLLING INCREASED PRESSURE DUE TO
 THERMAL EXPANSION SHALL BE PROVIDED PER 2010 FPC
 SEC.607.3
 22) THE HOT WATER RECIRCULATING LINE SHALL COMPLY W/
 2010 FPC SEC.607.2 & SEC. 504.6 OF THE FL. ENERGY CODE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-02-25 Cont ID  
Sent By jwitmer Date 2014-02-25 Time 09:33 Rev Time 0.00
Received By jwitmer Date 2014-02-25 Time 08:20 Sent To  
Notes
2014-02-25 08:31:51PLUMBING PLAN REVIEW
 PERMIT: 13090329
 ADD: 5011 BROADWAY
 CONT: TO BE DETERMINED
 TEL: (305)331-1400
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010
 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: TUE. FEB. 25
 ACTION: DENIED
  
 1) 2ND REQUEST,
 SHEET P-1 PLEASE PROVIDE CALCULATIONS FOR THE SIZING OF
 THE GREASE INTERCEPTOR SIZE. 2010 FBC-PLUMBING TABLE
 1003.5.1.
  
 2) COMPLIED.
  
 3) THE FISH FREEZER IS NOT INDICATED TO HAVE A TRAP
 PRIMER NOR ANY OTHER WASTE WATER THAT WOULD PROVIDE
 LIQUIDS TO SEAL THE TRAP.
 2010 FBC-P 1002.4 TRAP SEALS.
 EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS
 THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102
 MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO
 ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO
 LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE
 INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE
 TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A
 TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR
 ASSE 1044.
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-09-18 Cont ID  
Sent By lwagner Date 2013-09-18 Time 15:02 Rev Time 0.00
Received By lwagner Date 2013-09-18 Time 12:04 Sent To  
Notes
2013-09-18 13:55:04FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET P-1: PLEASE PROVIDE CALCULATIONS FOR THE
 GREASE INTERCEPTOR SIZE.
 *NOTE: A 750 GALLON GREASE INTERCEPTOR WILL TYPICALLY
 REQUIRE 30 MINUTES RETENTION TIME ALLOWING 25 GALLONS
 FLOW. WITH THE AMOUNT OF DRAINS CONNECTED, THERE
 APPEARS TO BE MORE THAN 25 GALLONS PER MINUTE FLOW TO
 THE GREASE INTERCEPTOR.
  
 2. SHEET P-1 & P-2: AN AIR GAP IS REQUIRED FOR THE
 DAIRY, FISH, MEAT, PRODUCE, AND KITCHEN COOLER FLOOR
 DRAINS OR EXCEPTION.
 802.1.2 FLOOR DRAINS IN FOOD STORAGE AREAS.
 FLOOR DRAINS LOCATED WITHIN WALK-IN REFRIGERATORS OR
 FREEZERS IN FOOD SERVICE AND FOOD ESTABLISHMENTS SHALL
 BE INDIRECTLY CONNECTED TO THE SANITARY DRAINAGE SYSTEM
 BY MEANS OF AN AIR GAP. WHERE A FLOOR DRAIN IS LOCATED
 WITHIN AN AREA SUBJECT TO FREEZING, THE WASTE LINE
 SERVING THE FLOOR DRAIN SHALL NOT BE TRAPPED AND SHALL
 INDIRECTLY DISCHARGE INTO A WASTE RECEPTOR LOCATED
 OUTSIDE OF THE AREA SUBJECT TO FREEZING.
  
 EXCEPTION: WHERE PROTECTED AGAINST BACKFLOW BY A
 BACKWATER VALVE, SUCH FLOOR DRAINS SHALL BE INDIRECTLY
 CONNECTED TO THE SANITARY DRAINAGE SYSTEM BY MEANS OF
 AN AIR BREAK OR AN AIR GAP.
  
 3. FLOOR DRAINS THAT ARE NOT WASTE RECEIVERS REQUIRE
 TRAP PRIMERS.
 1002.4 TRAP SEALS.
 EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS
 THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102
 MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO
 ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO
 LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE
 INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE
 TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A
 TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR
 ASSE 1044.
  
 4. SHEET P-4 ALL HOSE BIBBS WILL REQUIRE SEPARATE SHUT
 OFF VALVES.
 606.2 LOCATION OF SHUTOFF VALVES.
 ...ON THE WATER SUPPLY PIPE TO EACH SILLCOCK IN OTHER
 THAN ONE- AND TWO-FAMILY RESIDENTIAL OCCUPANCIES.
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  
  
  

Review Stop Z ZONING
Rev No 6 Status P Date 2015-08-31 Cont ID  
Sent By eschneid Date 2015-08-27 Time 16:45 Rev Time 3.00
Received By eschneid Date 2015-08-27 Time 16:45 Sent To B
Notes
2015-08-27 17:00:04CONDITIONAL APPROVAL
  
 THE FOLLOWING SPECIFIC CONDITIONS APPLY TO THE ZONING
 APPROVAL:
  
 1) PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 FOR THE RENOVATION OF THE SUPERMARKET AT 5011 BROADWAY:
 A. A LANDSCAPE PERMIT, WHICH INCLUDES A LANDSCAPE PLAN,
 SHALL BE SUBMITTED TO THE CONSTRUCTION SERVICES
 DIVISION FOR REVIEW.
 B. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED
 LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL
 LANDSCAPE INSPECTION (502).
 C. AN IRRIGATION PERMIT SHALL BE SUBMITTED TO THE
 CONSTRUCTION SERVICES DIVISION FOR REVIEW.
 D. THE IRRIGATION SHALL BE INSTALLED IN ACCORDANCE WITH
 THE APPROVED IRRIGATION PERMIT AND PASS A PLUMBING
 FINAL INSPECTION (703).
 E. A BUILDING PERMIT FOR THE DUMPSTER ENCLOSURE, WHICH
 COMPLIES WITH THE BROADWAY MIXED USE DISTRICT
 REGULATIONS, SHALL BE SUBMITTED TO THE CONSTRUCTION
 SERVICES DIVISION FOR REVIEW.
 F. THE DUMPSTER ENCLOSURE SHALL BE INSTALLED IN
 ACCORDANCE WITH THE APPROVED BUILDING PERMIT AND PASS A
 FINAL INSPECTION (104).
 G. A PARKING LOT PERMIT, INCLUDING THE NEW STRIPING AND
 CURBING, SHALL BE SUBMITTED TO THE CONSTRUCTION
 SERVICES DIVISION FOR REVIEW.
 H. THE PARKING LOT SHALL BE INSTALLED IN ACCORDANCE
 WITH THE APPROVED PARKING LOT PERMIT AND PASS A FINAL
 INSPECTION (104).
 I. A BUILDING PERMIT FOR THE BICYCLE RACKS SHALL BE
 SUBMITTED TO THE CONSTRUCTION SERVICES DIVISION FOR
 REVIEW.
 J. THE BICYCLE RACKS SHALL BE INSTALLED IN ACCORDANCE
 WITH THE APPROVED BUILDING PERMIT AND PASS A FINAL
 INSPECTION (104).
 K. THE BROADWAY FACADE SHALL HAVE CLEAR GLAZED AREAS,
 ALONG A MINIMUM OF 70 PERCENT OF ITS FACADE LENGTH,
 BETWEEN TWO AND EIGHT FEET FROM THE GROUND IN
 ACCORDANCE WITH SECTION 94-221(D)(5) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS OR AN ALTERNATIVE AMOUNT
 OF GLAZING IN ACCORDANCE WITH A VARIANCE THAT HAS BEEN
 APPROVED BY THE ZONING BOARD OF APPEALS AFTER FILING OF
 AN APPLICATION. THE FINAL GLAZING LAYOUT SHALL BE
 APPROVED AS EITHER A REVISION TO PERMIT NO. 13090329 OR
 AS A SEPARATE STOREFRONT PERMIT AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 2) THE FOLLOWING SEPARATE PERMITS, WITH PLANS, ARE
 REQUIRED:
  
 A. AWNINGS
 B. SIGNAGE
 C. SITE LIGHTING
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446

Review Stop Z ZONING
Rev No 5 Status F Date 2015-07-10 Cont ID  
Sent By eschneid Date 2015-07-10 Time 11:07 Rev Time 2.00
Received By eschneid Date 2015-06-30 Time 16:46 Sent To  
Notes
2015-06-30 16:46:53FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) REPEAT COMMENT: THE PLANS SHOW THE DEMOLITION OF THE
 EXTERIOR WALL ALONG BROADWAY AND ITS REPLACEMENT WITH
 STOREFRONT GLAZING AND A NEW WALL. THE BMUD REGULATIONS
 REQUIRE THAT STOREFRONTS HAVE CLEAR GLAZED AREAS, ALONG
 A MINIMUM OF 70 PERCENT OF ITS FACADE LENGTH, BETWEEN
 TWO AND EIGHT FEET FROM THE GROUND - SECTION
 94-221(D)(5). THE GLAZING CALCULATION PROVIDED ON SHEET
 A-9 SHOWS ONLY 46.97 PERCENT GLAZING. THE PLANS DO NOT
 SHOW THE PROVISION OF THE MINIMUM 70 PERCENT GLAZING
 BETWEEN TWO AND EIGHT FEET AS PART OF THE CONSTRUCTION
 OF THE NEW EASTERN WALL OF THE BUILDING.
  
 2) THE CONDITIONAL APPROVAL FORM FOR THIS PERMIT OR
 PERMITS FOR THIS ITEMS LISTED BELOW SHALL BE COMPETED
 AND RETURNED TO THE PLANNING DIVISION PRIOR TO ZONING
 APPROVAL OF THIS PERMIT:
 A. LANDSCAPE - RENOVATIONS EXCEED 50% OF THE BUILDING
 VALUE SO COMPLIANT LANDSCAPE IS REQUIRED. PLEASE NOTE
 THAT THE CITY REQUIRES THAT A LANDSCAPE ARCHITECT SIGN
 AND SEAL LANDSCAPE PLANS. PLEASE MAKE SURE TO INCLUDE A
 CERTIFIED COST ESTIMATE FOR THE LANDSCAPE MATERIAL AND
 INSTALLATION SHOWN ON THE LANDSCAPE PLAN.
 B. IRRIGATION
 C. PARKING LOT - CURBING AND STRIPING.
 D. DUMPSTER ENCLOSURE - PLEASE NOTE THAT THE DUMPSTER
 ENCLOSURE REQUIRES A 12 FOOT 6 INCH OPENING (NO
 DIMENSION PROVIDED). THE OVERALL DUMPSTER ENCLOSURE
 DEPTH DOES NOT MEET CITY STANDARDS. DUMPSTERS FOR FOOD
 SERVICE BUSINESSES SHALL BE FULLY ENCLOSED AND
 AIR-CONDITIONED - SECTION 94-221(D)(10). IF THE
 BUILDING CODE INVALIDATES THE REQUIREMENT TO
 AIR-CONDITION THE ENCLOSURE (VERIFICATION SHALL BE
 PROVIDED), THEN A FAN MAY BE USED. HOWEVER, THE FAN
 (MECHANICAL EQUIPMENT) SHALL BE SCREENED IN ACCORDANCE
 WITH SECTION 94-221(D)(8).
 E. BICYCLE PARKING - THE BICYCLE RACK STYLE SHOWN ON
 SHEET A-3 CONFORMS TO CITY STANDARDS; HOWEVER, TWO
 ELEMENTS (TO PARK FOUR BICYCLES REQUIRES 6.5 FEET FROM
 THE BUILDING WITH THE FIRST ELEMENT INSTALLED 24 INCHES
 FROM THE BUILDING) NOT 5.5 FEET AS SHOWN. PLEASE NOTE
 THAT THE AMOUNT OF BICYCLE PARKING IS BASED ON THE
 REQUIRED PARKING FOR A PROPERTY. WHILE THIS SITE IS
 NON-CONFORMING AS TO PARKING, THE USE REQUIRES 45
 PARKING SPACES, WHICH TRANSLATES INTO THREE REQUIRED
 BICYCLE PARKING SPACES. THIS ONLY REQUIRES TWO ELEMENTS
 (EACH SUPPORTS TWO BICYCLES), SO INSTALLING ONE ELEMENT
 INSTEAD OF TWO AT EACH LOCATION WOULD PROVIDE THE
 MINIMUM REQUIRED ROOM FOR A CUSTOMER, OR EMPLOYEE, TO
 PARK A BICYCLE. IF THE OWNER WISHES TO PROVIDE MORE
 ELEMENTS NOW OR IN THE FUTURE (IF IT IS NOTED THAT
 THERE IS A DEMAND FOR BICYCLE PARKING), THEN THEY COULD
 CONTINUE DOWN THE "NEW CONCRETE WALKWAY" AS LONG AS
 THERE IS AT LEAST SIX (6) FEET OF DEPTH PROVIDED FOR
 EACH "BICYCLE PAD". SHEETS A-3, A-3 AND A-4 NEED TO BE
 CORRECTLY SHOW THE CORRECT BICYCLE PARKING LAYOUT AS
 PART OF THE BUILDING PERMIT FOR THE BICYCLE PARKING.
  
 3) THE FOLLOWING SEPARATE PERMITS, WITH PLANS, ARE
 REQUIRED:
  
 A. AWNINGS
 B. SIGNAGE
 C. SITE LIGHTING
  
 4) THANK YOU FOR PROVIDING THE CODE REQUIRED EIGHT (8)
 FOOT WIDE SIDEWALK ALONG BROADWAY. PLEASE NOTE THAT THE
 WIDENING OF THE SIDEWALK DOES NOT PERMIT THE NARROWING
 OF THE TERMINAL LANDSCAPE ISLAND TO LESS THAN THE
 REQUIRED FIVE (5) FEET IN WIDTH. PLEASE NOTE THAT THE
 WIDTH SHALL BE MEASURED FROM THE PLANTED AREA OF THE
 TERMINAL ISLAND, AND NOT INCLUDE THE CURBING. THE SITE
 PLAN SHOWS A 29.75 FOOT WIDE DRIVEWAY ONTO 49TH STREET
 THAT CAN BE NARROWED TO PROVIDE THE ADDITIONAL TERMINAL
 ISLAND WIDTH. THESE ITEMS SHALL BE CORRECTLY DEPICTED
 ON THE LANDSCAPE AND PARKING LOT PERMITS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 4 Status F Date 2015-05-05 Cont ID  
Sent By eschneid Date 2015-05-05 Time 15:53 Rev Time 3.00
Received By eschneid Date 2015-05-05 Time 08:43 Sent To  
Notes
2015-05-05 15:54:19FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) REPEAT COMMENT: THE BROADWAY MIXED USE DISTRICT
 REGULATIONS REQUIRE THAT ALL PROPERTIES SHALL BE
 BROUGHT INTO COMPLIANCE WITH THE LANDSCAPE REGULATIONS
 IN ARTICLE XXIV, CONCURRENTLY WITH EXTERIOR BUILDING
 IMPROVEMENTS EXCEEDING $10,000 - SECTION 94-219(D)(9).
 ADDITIONALLY, THE PERMIT VALUE OF $400,000 EXCEEDS 50%
 OF THE BUILDING VALUE ($407,097 ACCORDING TO PAPA), SO
 THE SITE IS REQUIRED TO BE BROUGHT INTO LANDSCAPE
 COMPLIANCE. THE LANDSCAPE PLAN SHALL BE SUBMITTED AS A
 SEPARATE LANDSCAPE PERMIT. IN ACCORDANCE WITH THE
 ZONING AND LAND DEVELOPMENT REGULATIONS, THE LANDSCAPE
 PLAN SHALL BE SIGNED AND SEALED BY A REGISTERED
 LANDSCAPE ARCHITECT, NOT AN ENGINEER. ADDITIONALLY, THE
 LANDSCAPE PLAN SHALL VERIFY COMPLIANCE WITH THE
 REQUIREMENTS OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 2) REPEAT COMMENT: THE PLANS SHOW THE DEMOLITION OF THE
 EXTERIOR WALL ALONG BROADWAY AND ITS REPLACEMENT WITH
 STOREFRONT GLAZING AND A NEW WALL. THE BMUD REGULATIONS
 REQUIRE THAT STOREFRONTS HAVE CLEAR GLAZED AREAS, ALONG
 A MINIMUM OF 70 PERCENT OF ITS FACADE LENGTH, BETWEEN
 TWO AND EIGHT FEET FROM THE GROUND. PLEASE PROVIDE THE
 FACADE GLAZING CALCULATIONS BETWEEN TWO AND EIGHT FEET
 TO VERIFY THAT THE 70 PERCENT HAS BEEN MET - SECTION
 94-221(D)(5). THE GLAZING CALCULATION PROVIDED ON SHEET
 A-9 SHOWS ONLY 46.97 PERCENT GLAZING.
  
 3) REVISED COMMENT: SHEET A-3 SHOWS THE EMERGENCY SWING
 FOR DOOR TYPE A AS SWINGING FROM THE MIDDLE OUT. THE
 DOOR SCHEDULE DESCRIPTION AND THE DOOR ELEVATION ON
 SHEET A-7 SHOW THE SIDE LITES WITH THE HINGED SWING.
 PLEASE CLARIFY AND CORRECT DRAWINGS AS NECESSARY.
 PLEASE NOTE THAT THIS TYPE OF CONFIGURATION DOES MEET
 THE INTENT OF SECTION 94-221(D)(6)F FOR A GROCERY
 STORE.
  
 4) REVISED COMMENT: DUMPSTERS FOR FOOD SERVICE
 BUSINESSES SHALL BE FULLY ENCLOSED AND AIR-CONDITIONED
 - SECTION 94-221(D)(10). PLEASE REMEMBER THAT THE
 MECHANICAL EQUIPMENT ON THE ROOF OF THE DUMPSTER
 ENCLOSURE SHALL BE SCREENED IN ACCORDANCE WITH SECTION
 94-221(D)(8).
  
 5) REPEAT COMMENT: SIDEWALKS ALONG BROADWAY SHALL BE A
 MINIMUM IF EIGHT FEET IN CLEAR WIDTH, WHERE THE
 BUILDING DOES NOT CURRENTLY EXIST. THIS SHALL BE
 INCLUDED WITH THE LANDSCAPE AND PAVING PERMITS -
 SECTION 94-221(B)(6).
  
 6) THE FOLLOWING SEPARATE PERMITS, WITH PLANS, ARE
 REQUIRED PRIOR TO BE SUBMITTED BEFORE ZONING WILL
 APPROVE THIS PERMIT:
 A. LANDSCAPE - PLEASE NOTE THAT THE CITY REQUIRES THAT
 A LANDSCAPE ARCHITECT SIGN AND SEAL LANDSCAPE PLANS.
 THE PLANS SUBMITTED WITH THE INTERIOR RENOVATION PERMIT
 WERE SIGNED AND SEALED BY AN ENGINEER. THE LANDSCAPE
 PLANS ARE NOT REVIEWED AS PART OF THE BUILDING
 RENOVATION, BUT AS PART OF A SEPARATE PERMIT SUBMITTAL.
 PLEASE MAKE SURE TO INCLUDE A CERTIFIED COST ESTIMATE
 FOR THE LANDSCAPE MATERIAL AND INSTALLATION SHOWN ON
 THE LANDSCAPE PLAN.
 B. IRRIGATION
 C. PARKING LOT
 D. DUMPSTER ENCLOSURE - PLEASE NOTE THAT THE DUMPSTER
 ENCLOSURE REQUIRES A 12 FOOT 6 INCH OPENING (NO
 DIMENSION PROVIDED). THE OVERALL DUMPSTER ENCLOSURE
 DEPTH DOES NOT MEET CITY STANDARDS.
  
 7) THE FOLLOWING SEPARATE PERMITS, WITH PLANS, ARE
 REQUIRED:
  
 A. AWNINGS
 B. SIGNAGE
 C. SITE LIGHTING
  
 8) REVISED COMMENT: THANK YOU FOR PROVIDING A BICYCLE
 RACK. HOWEVER, THE CITY DOES NOT PERMIT THE WAVE TYPE
 OF BICYCLE RACK. THE CITY PERMITS POST AND LOOP,
 INVERTED "U" AND "A" TYPE BICYCLE RACKS. PLEASE CONTACT
 ZONING STAFF FOR THE SPECIFIC REQUIREMENTS, TO INCLUDE
 THE PAD SIZE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  

Review Stop Z ZONING
Rev No 3 Status F Date 2014-11-25 Cont ID  
Sent By eschneid Date 2014-11-25 Time 15:29 Rev Time 5.00
Received By eschneid Date 2014-11-24 Time 15:48 Sent To  
Notes
2014-11-25 15:30:51FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) THE BROADWAY MIXED USE DISTRICT REGULATIONS REQUIRE
 THAT ALL PROPERTIES SHALL BE BROUGHT INTO COMPLIANCE
 WITH THE LANDSCAPE REGULATIONS IN ARTICLE XXIV,
 CONCURRENTLY WITH EXTERIOR BUILDING IMPROVEMENTS
 EXCEEDING $10,000 - SECTION 94-219(D)(9). ADDITIONALLY,
 THE PERMIT VALUE OF $400,000 EXCEEDS 50% OF THE
 BUILDING VALUE ($407,097 ACCORDING TO PAPA), SO THE
 SITE IS REQUIRED TO BE BROUGHT INTO LANDSCAPE
 COMPLIANCE. THE LANDSCAPE PLAN SHALL BE SUBMITTED AS A
 SEPARATE LANDSCAPE PERMIT. IN ACCORDANCE WITH THE
 ZONING AND LAND DEVELOPMENT REGULATIONS, THE LANDSCAPE
 PLAN SHALL BE SIGNED AND SEALED BY A REGISTERED
 LANDSCAPE ARCHITECT, NOT AN ENGINEER. ADDITIONALLY, THE
 LANDSCAPE PLAN SHALL VERIFY COMPLIANCE WITH THE
 REQUIREMENTS OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 2) THE PRINCIPAL PEDESTRIAN ENTRANCE TO THE BUILDING IS
 NOT FACING THE BROADWAY FRONTAGE LINE AS REQUIRED BY
 SECTION 94-221(D)(4).
  
 3) THE PLANS SHOW THE DEMOLITION OF THE EXTERIOR WALL
 ALONG BROADWAY AND ITS REPLACEMENT WITH STOREFRONT
 GLAZING AND A NEW WALL. THE BMUD REGULATIONS REQUIRE
 THAT STOREFRONTS HAVE CLEAR GLAZED AREAS, ALONG A
 MINIMUM OF 70 PERCENT OF ITS FACADE LENGTH, BETWEEN TWO
 AND EIGHT FEET FROM THE GROUND. PLEASE PROVIDE THE
 FA?ADE GLAZING CALCULATIONS BETWEEN TWO AND EIGHT FEET
 TO VERIFY THAT THE 70 PERCENT HAS BEEN MET - SECTION
 94-221(D)(5).
  
 4) WINDOW AND DOOR OPENINGS SHALL BE VERTICAL OR SQUARE
 IN PROPORTION. - THE WINDOWS FACING BROADWAY (NORTH
 PORTION OF FACADE) ARE NOT VERTICAL OR SQUARE IN
 PROPORTION - SECTION 94-221(D)(6)B.
  
 5) MULTIPLE WINDOWS IN THE SAME ROUGH OPENING SHALL BE
 SEPARATED BY A FOUR-INCH WIDE POST AND SIT ON ONE
 CONTINUOUS SILL. - THE WINDOWS FACING BROADWAY (NORTH
 PORTION OF FACADE) ARE NOT SEPARATED BY A FOUR-INCH
 WIDE POST - SECTION 94-221(D)(6)D.
  
 6) ALL EXTERIOR DOORS SHALL BE HINGED, EXCEPT GARAGE
 DOORS - THE AUTOMATIC DOOR, AS SPECIFIED, DOES NOT MEET
 THIS CRITERIA. PREVIOUS PLANS HAD SHOWN A SLIDING GLASS
 DOOR THAT HAD HINGES FOR EMERGENCY USE - SECTION
 94-221(D)(6)F.
  
 7) MECHANICAL SYSTEMS AND BACKFLOW PREVENTERS SHALL BE
 SCREENED FROM VIEW ON ALL SIDES TO THE FULL HEIGHT OF
 THE STRUCTURE BY LANDSCAPING OR BUILT ELEMENTS DESIGNED
 AS AN INTEGRAL PART OF THE BUILDING ARCHITECTURE. - NO
 SIGHT LINE FOR THE PROPERTIES TO THE WEST OR SOUTH TO
 VERIFY THAT THIS REQUIREMENT IS MET FOR THE ROOFTOP
 MECHANICAL EQUIPMENT AND NO INFORMATION ON WHERE AND
 HOW THE BACKFLOW PREVENTER WILL BE SCREENED IS PROVIDE
 - SECTION 94-221(D)(8).
  
 8) FLAT ROOFS SHALL BE ENCLOSED BY A PARAPET NO LESS
 THAN 42 INCHES IN HEIGHT. THE PLANS DO NOT SHOW A 42
 INCH HIGH PARAPET AROUND THE ENTIRE FLAT ROOF - SECTION
 94-221(D)(9).
  
 9) DUMPSTERS FOR FOOD SERVICE BUSINESSES SHALL BE FULLY
 ENCLOSED AND AIR-CONDITIONED - SECTION 94-221(D)(10).
  
 10) AUTOMATIC FOOD AND DRINK MACHINES AND THE ICE
 MACHINE MAY NOT BE LOCATED OUTSIDE OF THE BUILDING -
 SECTION 94-219(D)(10).
  
 11) THE PROPANE TANK AT THE REAR OF THE BUILDING SHALL
 BE SCREENED IN ACCORDANCE WITH SECTION 94-444(B)
  
 12) SIDEWALKS ALONG BROADWAY SHALL BE A MINIMUM IF
 EIGHT FEET IN CLEAR WIDTH. THIS SHALL BE INCLUDED WITH
 THE LANDSCAPE PERMIT - SECTION 94-221(B)(6).
  
 13) THE FOLLOWING SEPARATE PERMITS, WITH PLANS, ARE
 REQUIRED PRIOR TO BE SUBMITTED PRIOR TO ZONING APPROVAL
 OF THIS PERMIT:
 A. LANDSCAPE - PLEASE NOTE THAT THE CITY REQUIRES THAT
 A LANDSCAPE ARCHITECT SIGN AND SEAL LANDSCAPE PLANS.
 THE PLANS SUBMITTED WITH THE INTERIOR RENOVATION PERMIT
 WERE SIGNED AND SEALED BY AN ENGINEER.
 B. IRRIGATION
 C. PARKING LOT
 D. DUMPSTER ENCLOSURE - PLEASE NOTE THAT THE DUMPSTER
 ENCLOSURE REQUIRES A 12 FOOT 6 INCH OPENING, NOT 10
 FEET AS SHOWN. THE OVERALL DUMPSTER ENCLOSURE SIZE DOES
 NOT MEET CITY STANDARDS.
  
 14) THE FOLLOWING SEPARATE PERMITS, WITH PLANS, ARE
 REQUIRED:
  
 A. AWNINGS - PLEASE NOTE: AWNINGS AT THE SIDEWALK LEVEL
 SHALL PROJECT A MINIMUM OF FOUR FEET FROM THE BUILDING
 FA?ADE AND VALANCES SHALL NOT EXCEED EIGHT INCHES IN
 HEIGHT. THE PROPOSED AWNINGS DO NOT COMPLY WITH EITHER
 OF THESE STANDARDS.
 B. SIGNAGE
 C. SITE LIGHTING
  
 15) STAFF SUGGESTS INCLUDING BICYCLE RACKS FOR BOTH
 EMPLOYEE AND CUSTOMER USE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
2014-11-24 15:48:18IN REVIEW

Review Stop Z ZONING
Rev No 2 Status F Date 2014-03-05 Cont ID  
Sent By eschneid Date 2014-03-05 Time 13:57 Rev Time 2.00
Received By eschneid Date 2014-03-05 Time 13:56 Sent To  
Notes
2014-03-05 16:02:18FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) REPEAT COMMENT: THE RENOVATIONS EXPAND THE SQUARE
 FOOTAGE OF THE SUPERMARKET IN EXCESS OF 10,000 SQUARE
 FEET, THUS REQUIRING APPROVAL OF A CLASS B SPECIAL USE
 PERMIT. PLEASE NOTE THAT THE PREVIOUSLY APPROVED CLASS
 B SPECIAL USE PERMIT APPROVED FOR THE SUPERMARKET
 EXPANSION EXPIRED IN JANUARY OF 2011.
  
 2) REPEAT COMMENT: THE BROADWAY MIXED USE DISTRICT
 REGULATIONS REQUIRE THAT ALL PROPERTIES SHALL BE
 BROUGHT INTO COMPLIANCE WITH THE LANDSCAPE REGULATIONS
 IN ARTICLE XXIV, CONCURRENTLY WITH EXTERIOR BUILDING
 IMPROVEMENTS EXCEEDING $10,000. ADDITIONALLY, THE
 PERMIT VALUE OF $400,000 EXCEEDS 50% OF THE BUILDING
 VALUE ($407,097 ACCORDING TO PAPA), SO THE SITE IS
 REQUIRED TO BE BROUGHT INTO LANDSCAPE COMPLIANCE. THE
 LANDSCAPE PLAN SHALL BE SUBMITTED AS A SEPARATE
 LANDSCAPE PERMIT. IN ACCORDANCE WITH THE ZONING AND
 LAND DEVELOPMENT REGULATIONS, THE LANDSCAPE PLAN SHALL
 BE SIGNED AND SEALED BY A REGISTERED LANDSCAPE
 ARCHITECT, NOT AN ENGINEER. ADDITIONALLY, THE LANDSCAPE
 PLAN SHALL VERIFY COMPLIANCE WITH THE REQUIREMENTS OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS.
  
 3) REPEAT COMMENT: THE PLAN CONTINUES TO FAIL TO MEET
 MULTIPLE ELEMENTS OF THE BMUD REGULATIONS FOUND IN
 SECTIONS 94-219 AND 94-221 OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS. STAFF IS NOT GOING TO ITEMIZE
 THE LIST AS IT IS TOO LONG, THE APPLICANT SHALL REVIEW
 AND FOLLOW THE BROADWAY MIXED USE DISTRICT 2
 REGULATIONS TO ENSURE THAT THE DESIGN COMPLIES. THE
 FOLLOWING ITEMS WERE IMMEDIATELY IDENTIFIED BY STAFF AS
 NOT BEING IN COMPLIANCE WHICH WERE NOT CHANGED FROM THE
 PREVIOUS SET OF PLANS AT WHICH POINT THE ZONING STAFF
 STOPPED THE REVIEW UNTIL THE APPLICANT RESUBMITS PLANS
 THAT COMPLY WITH ALL ZONING REGULATIONS.
  
 A. THE PRINCIPAL PEDESTRIAN ENTRANCE IS NOT FACING THE
 BROADWAY FRONTAGE LINE - SECTION 94-221(D)(4).
 B. MECHANICAL SYSTEMS SHALL BE SCREENED FROM VIEW ON
 ALL SIDES TO THE FULL HEIGHT OF THE STRUCTURE BY
 LANDSCAPING OR BUILT ELEMENTS DESIGNED AS AN INTEGRAL
 PART OF THE BUILDING ARCHITECTURE - SECTION
 94-221(D)(8).
  
 4) REPEAT COMMENT: HE PARKING, DUMPSTER, SIGNS,
 LANDSCAPE AND AWNINGS ARE REQUIRED TO MEET CITY CODE
 REQUIREMENTS AND SHALL ALL BE SUBMITTED UNDER SEPARATE
 PERMITS, WITH PLANS.
  
 5) REPEAT COMMENT: PLEASE NOTE THAT THE CORNER OF 49TH
 AND BROADWAY IS A LOCATION OF PUBLIC OPEN SPACE AND
 SHALL BE IMPROVED AS SUCH. THE PLANNING DIVISION HAS
 PREVIOUSLY APPROVED PLANS FOR THE PUBLIC OPEN SPACE.
  
 CONTACT ERIC SCHNEIDER @ (561)822-1435.
  
2014-02-10 16:14:072/10/14

Review Stop Z ZONING
Rev No 1 Status F Date 2013-10-02 Cont ID  
Sent By eschneid Date 2013-10-02 Time 14:29 Rev Time 1.00
Received By eschneid Date 2013-10-02 Time 14:29 Sent To  
Notes
2013-10-02 15:12:34FAILED
  
 1) PROVIDE TWO COPIES OF A SURVEY, LESS THAN ONE YEAR
 OLD, SHOWING ALL EXISTING CONDITIONS AND EASEMENTS.
  
 2) THE RENOVATIONS EXPAND THE SQUARE FOOTAGE OF THE
 SUPERMARKET IN EXCESS OF 10,000 SQUARE FEET, THUS
 REQUIRING APPROVAL OF A CLASS B SPECIAL USE PERMIT.
 PLEASE NOTE THAT THE PREVIOUSLY APPROVED CLASS B
 SPECIAL USE PERMIT APPROVED FOR THE SUPERMARKET
 EXPANSION EXPIRED IN JANUARY OF 2011.
  
 3) THE BROADWAY MIXED USE DISTRICT REGULATIONS REQUIRE
 THAT ALL PROPERTIES SHALL BE BROUGHT INTO COMPLIANCE
 WITH THE LANDSCAPE REGULATIONS IN ARTICLE XXIV,
 CONCURRENTLY WITH EXTERIOR BUILDING IMPROVEMENTS
 EXCEEDING $10,000. ADDITIONALLY, THE PERMIT VALUE OF
 $400,000 EXCEEDS 50% OF THE BUILDING VALUE ($407,097
 ACCORDING TO PAPA), SO THE SITE IS REQUIRED TO BE
 BROUGHT INTO LANDSCAPE COMPLIANCE. THE SUBMITTED PLAN
 DOES NOT MEET THE CITY'S LANDSCAPE REQUIREMENTS. THE
 ZONING DIVISION HAS PREVIOUSLY APPROVED LANDSCAPE PLANS
 FOR THE SITE.
  
 4) THE PLAN FAILS TO MEET MULTIPLE ELEMENTS OF THE BMUD
 REGULATIONS FOUND IN SECTIONS 94-219 AND 94-221 OF THE
 ZONING AND LAND DEVELOPMENT REGULATIONS. STAFF IS NOT
 GOING TO ITEMIZE THE LIST AS IT IS TOO LONG - THE
 APPLICANT SHALL FOLLOW THE CODE.
  
 5) THE PARKING, DUMPSTER, SIGNS, LANDSCAPE AND AWNINGS
 ARE REQUIRED TO MEET CITY CODE REQUIREMENTS AND SHALL
 ALL BE SUBMITTED UNDER SEPARATE PERMITS, WITH PLANS.
  
 6) PLEASE NOTE THAT THE CORNER OF 49TH AND BROADWAY IS
 A LOCATION OF PUBLIC OPEN SPACE AND SHALL BE IMPROVED
 AS SUCH. THE PLANNING DIVISION HAS PREVIOUSLY APPROVED
 PLANS FOR THE PUBLIC OPEN SPACE.
  
 CONTACT ERIC SCHNEIDER @ (561)822-1435.
2013-09-16 19:03:379/16/13