| 2013-09-12 14:33:22 | NOTE: | | | 1) NOTE: A2.0X FIRE SPRINKLER ROOM X-03 WALL TYPE 100 | | | IS A 1 HR RATED WALL, IF FIRE PUMP IS REQUIRED, A FIRE | | | PUMP ROOM REQUIRES A 2 HR FIRE RATING 2010 FBC-B | | | 913.2.1. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2013-12-12 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-12-12 |
Time |
17:10 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-12-11 |
Time |
17:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2013-09-24 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-09-24 |
Time |
12:40 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-09-19 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2013-09-19 14:02:49 | 13090267 | | | ELECTRIC REVISION FOR PB OUTLET MALL | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | VERIFY THE GROUNDING CIRCUIT FOR EMERGENCY LIGHT | | | CIRCUITS #26, 28, 30 LOCATED IN THE 480 V HOUSE PANEL | | | J3 HAS BE PROPERLY SIZED. NEC 250.122 (B) | | | | | | PROVIDE THE LISTING WITH SPECIFICATIONS FOR THE LIGHT | | | POLE ASSEMBLY WITH 200 VA TRANSFORMER POWER SUPPLY | | | SERVING A GFCI RECEPTACLE. NEC 110.3 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2013-09-18 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2013-09-18 |
Time |
17:43 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2013-09-18 |
Time |
17:43 |
Sent To |
|
|
| Notes |
| 2013-09-18 17:53:51 | 1721 PALM BEACH LAKES BLVD. - 10 BUILDINGS IN MALL | | | PERMIT #13090267 | | | MASTER #12100555 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | | | | *****PROVISO - THE CIVIL/SITE PLANS SHOW THE ENTIRE | | | MALL SITE FOR REFERENCE AND CLARIFICATION PURPOSES | | | ONLY: THE FOLLOWING COMMENTS MAY APPLY TO SITE WORK | | | LOCATED OUTSIDE THE SCOPE OF THIS PERMIT | | | (#12100555).***** | | | | | | REPEAT COMMENTS: | | | SHEET C403 & C405: NO FIRE LANE CURBS OR SIGNS LOCATED | | | ON PLAN FOR "H" BUILDINGS. INDICATE FIRE LANES ON BOTH | | | FRONT AND REAR OF BUILDINGS. | | | | | | SHEET C602: FIRE HYDRANTS WILL NEED TO BE INSTALLED AND | | | MAINTAINED WITH WORKING CLEARANCES OF 7'-6" TO THE | | | FRONT/SIDES AND 4'-0" TO THE REAR. ANY PARKING SPACES | | | LOCATED WITHIN THIS BUFFER ZONE WILL NEED TO BE | | | INDICATED AS "NO PARKING" STALLS. | | | | | | SHEET C602: FIRE DEPARTMENT CONNECTION FOR FUTURE | | | BUILDING "PBA #5" SHALL BE LOCATED WITHIN 150 FEET OF A | | | FIRE HYDRANT. | | | | | | | | | SUE ELLEN CALDERON | | | FIRE INSPECTOR & INVESTIGATOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2013-12-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2013-11-13 |
Time |
14:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-10-18 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2013-10-17 |
Time |
13:03 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2013-09-10 |
Time |
15:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2013-10-10 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2013-10-10 |
Time |
07:33 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2013-10-10 |
Time |
07:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2013-09-17 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2013-09-17 |
Time |
08:42 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2013-09-16 |
Time |
14:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2013-11-18 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2013-11-18 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2013-11-18 |
Time |
14:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2013-12-18 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2013-12-18 |
Time |
19:01 |
Rev Time |
3.00 |
| Received By |
eschneid |
Date |
2013-12-18 |
Time |
19:01 |
Sent To |
|
|
| Notes |
| 2013-12-18 19:03:56 | PASSED | | | | | | PLEASE NOTE THAT ALL THE CHANGES PART OF THIS REVISION | | | ARE REQUIRED TO BE SHOWN ON THE AS-BUILT SITE PLAN | | | AMENDMENT. THESE INCLUDE, BUT ARE NOT LIMITED TO THE | | | ITEMS BELOW: | | | | | | A. BLDG J-3 GENERATOR | | | B. BLDG J-4 RELOCATED TREES | | | C. BLDG J-6 NEW REAR DOOR | | | D. BLDG J-7 ENTRY | | | E. BLDG J-1 ENTRY BOLLARDS | | | | | | PLEASE NOTE THAT THERE ARE DISCREPANCIES BETWEEN THE | | | PLANS APPROVED AS PART OF THIS PERMIT AND THE "AS | | | BUILT" MINOR AMENDMENT SUBMITTED ON NOVEMBER 12. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | | | 2013-11-19 10:34:44 | 11/19/13 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2013-10-17 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2013-10-17 |
Time |
14:40 |
Rev Time |
6.00 |
| Received By |
eschneid |
Date |
2013-10-17 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2013-10-17 21:16:22 | FAILED | | | | | | 1) THE TRASH COMPACTOR (TC) ADJACENT TO BUILDING J-1 IS | | | NOT SCREENED BY THE SERVICE COURT WALL. THIS WAS SHOWN | | | IN THE CORRECT LOCATION ON THE CURRENTLY APPROVED | | | PERMIT PLAN. | | | | | | 2) A GENERATOR WAS ADDED IN THE SERVICE COURT NORTH OF | | | BUILDING J-3. HOW DOES THE CONSTRICTING THE AREA AFFECT | | | THE ABILITY TO PROVIDE TRASH AND LOADING FUNCTIONS IN | | | THE SERVICE COURT? | | | | | | 3) THE LINE OF SITE PLAN FOR BUILDING J5 NEEDS TO SHOW | | | IMPACT OF THE 12.5 TON RTU FROM THE NORTH. | | | | | | 4) THE LINE OF SITE PLAN FOR BUILDING J7 NEEDS TO SHOW | | | IMPACT OF THE 12.5 TON RTU FROM THE SOUTH. | | | | | | 5) THE LINE OF SITE PLAN FOR BUILDING J8 NEEDS TO SHOW | | | IMPACT OF THE 12.5 TON RTU FROM THE SOUTH AND THE 10 | | | TON RTUS THAT ARE OVER THE SERVICE BAYS (THE PARAPET | | | WALL IS CLOSER TO THE RTU HERE). | | | | | | 6) PLEASE PROVIDE THE HEIGHTS OF THE 20 AND 25 TON | | | RTUS. | | | | | | 7) THE EAST ELEVATION FOR BUILDING J6 DOES NOT | | | ACURATELY REFLECT THE CHANGES TO THE WEST ELEVATION. | | | | | | 8) SHEEST M216 AND M218 SHOW 2 OF THE RTU HAVING | | | DIFFERENT TONAGE THEN THE ROOF PLAN. | | | | | | 9) CHANGES REQUIRED TO BE SHOWN ON THE AS-BUILT SITE | | | PLAN AMENDMENT. | | | | | | A. BLDG J-3 GENERATOR | | | B. BLDG J-4 RELOCATED TREES | | | C. BLDG J-6 NEW REAR DOOR | | | D. BLDG J-7 ENTRY | | | E. BLDG J-1 ENTRY BOLLARDS | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | 2013-09-13 16:14:26 | 9/13/13 |
|
|