Plan Review Details - Permit 13090267
Plan Review Stops For Permit 13090267
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-11-21 Cont ID  
Sent By jwitmer Date 2013-11-21 Time 07:27 Rev Time 0.00
Received By jwitmer Date 2013-11-21 Time 07:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-09-12 Cont ID  
Sent By jwitmer Date 2013-09-12 Time 14:47 Rev Time 0.00
Received By jwitmer Date 2013-09-12 Time 12:32 Sent To  
Notes
2013-09-12 14:33:22NOTE:
 1) NOTE: A2.0X FIRE SPRINKLER ROOM X-03 WALL TYPE 100
 IS A 1 HR RATED WALL, IF FIRE PUMP IS REQUIRED, A FIRE
 PUMP ROOM REQUIRES A 2 HR FIRE RATING 2010 FBC-B
 913.2.1.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-12-12 Cont ID  
Sent By dharvey Date 2013-12-12 Time 17:10 Rev Time 0.00
Received By dharvey Date 2013-12-11 Time 17:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-09-24 Cont ID  
Sent By dharvey Date 2013-09-24 Time 12:40 Rev Time 0.00
Received By dharvey Date 2013-09-19 Time 14:02 Sent To  
Notes
2013-09-19 14:02:4913090267
 ELECTRIC REVISION FOR PB OUTLET MALL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 VERIFY THE GROUNDING CIRCUIT FOR EMERGENCY LIGHT
 CIRCUITS #26, 28, 30 LOCATED IN THE 480 V HOUSE PANEL
 J3 HAS BE PROPERLY SIZED. NEC 250.122 (B)
  
 PROVIDE THE LISTING WITH SPECIFICATIONS FOR THE LIGHT
 POLE ASSEMBLY WITH 200 VA TRANSFORMER POWER SUPPLY
 SERVING A GFCI RECEPTACLE. NEC 110.3
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-09-18 Cont ID  
Sent By scaldero Date 2013-09-18 Time 17:43 Rev Time 0.00
Received By scaldero Date 2013-09-18 Time 17:43 Sent To  
Notes
2013-09-18 17:53:511721 PALM BEACH LAKES BLVD. - 10 BUILDINGS IN MALL
 PERMIT #13090267
 MASTER #12100555
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 *****PROVISO - THE CIVIL/SITE PLANS SHOW THE ENTIRE
 MALL SITE FOR REFERENCE AND CLARIFICATION PURPOSES
 ONLY: THE FOLLOWING COMMENTS MAY APPLY TO SITE WORK
 LOCATED OUTSIDE THE SCOPE OF THIS PERMIT
 (#12100555).*****
  
 REPEAT COMMENTS:
 SHEET C403 & C405: NO FIRE LANE CURBS OR SIGNS LOCATED
 ON PLAN FOR "H" BUILDINGS. INDICATE FIRE LANES ON BOTH
 FRONT AND REAR OF BUILDINGS.
  
 SHEET C602: FIRE HYDRANTS WILL NEED TO BE INSTALLED AND
 MAINTAINED WITH WORKING CLEARANCES OF 7'-6" TO THE
 FRONT/SIDES AND 4'-0" TO THE REAR. ANY PARKING SPACES
 LOCATED WITHIN THIS BUFFER ZONE WILL NEED TO BE
 INDICATED AS "NO PARKING" STALLS.
  
 SHEET C602: FIRE DEPARTMENT CONNECTION FOR FUTURE
 BUILDING "PBA #5" SHALL BE LOCATED WITHIN 150 FEET OF A
 FIRE HYDRANT.
  
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2013-12-18 Time   Rev Time 0.00
Received By rregueir Date 2013-11-13 Time 14:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-18 Cont ID  
Sent By rregueir Date 2013-10-17 Time 13:03 Rev Time 0.00
Received By rregueir Date 2013-09-10 Time 15:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-10-10 Cont ID  
Sent By rregueir Date 2013-10-10 Time 07:33 Rev Time 0.00
Received By rregueir Date 2013-10-10 Time 07:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-09-17 Cont ID  
Sent By lwagner Date 2013-09-17 Time 08:42 Rev Time 0.00
Received By lwagner Date 2013-09-16 Time 14:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-11-18 Cont ID  
Sent By rregueir Date 2013-11-18 Time 14:34 Rev Time 0.00
Received By rregueir Date 2013-11-18 Time 14:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2013-12-18 Cont ID  
Sent By eschneid Date 2013-12-18 Time 19:01 Rev Time 3.00
Received By eschneid Date 2013-12-18 Time 19:01 Sent To  
Notes
2013-12-18 19:03:56PASSED
  
 PLEASE NOTE THAT ALL THE CHANGES PART OF THIS REVISION
 ARE REQUIRED TO BE SHOWN ON THE AS-BUILT SITE PLAN
 AMENDMENT. THESE INCLUDE, BUT ARE NOT LIMITED TO THE
 ITEMS BELOW:
  
 A. BLDG J-3 GENERATOR
 B. BLDG J-4 RELOCATED TREES
 C. BLDG J-6 NEW REAR DOOR
 D. BLDG J-7 ENTRY
 E. BLDG J-1 ENTRY BOLLARDS
  
 PLEASE NOTE THAT THERE ARE DISCREPANCIES BETWEEN THE
 PLANS APPROVED AS PART OF THIS PERMIT AND THE "AS
 BUILT" MINOR AMENDMENT SUBMITTED ON NOVEMBER 12.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
2013-11-19 10:34:4411/19/13

Review Stop Z ZONING
Rev No 1 Status F Date 2013-10-17 Cont ID  
Sent By eschneid Date 2013-10-17 Time 14:40 Rev Time 6.00
Received By eschneid Date 2013-10-17 Time 14:40 Sent To  
Notes
2013-10-17 21:16:22FAILED
  
 1) THE TRASH COMPACTOR (TC) ADJACENT TO BUILDING J-1 IS
 NOT SCREENED BY THE SERVICE COURT WALL. THIS WAS SHOWN
 IN THE CORRECT LOCATION ON THE CURRENTLY APPROVED
 PERMIT PLAN.
  
 2) A GENERATOR WAS ADDED IN THE SERVICE COURT NORTH OF
 BUILDING J-3. HOW DOES THE CONSTRICTING THE AREA AFFECT
 THE ABILITY TO PROVIDE TRASH AND LOADING FUNCTIONS IN
 THE SERVICE COURT?
  
 3) THE LINE OF SITE PLAN FOR BUILDING J5 NEEDS TO SHOW
 IMPACT OF THE 12.5 TON RTU FROM THE NORTH.
  
 4) THE LINE OF SITE PLAN FOR BUILDING J7 NEEDS TO SHOW
 IMPACT OF THE 12.5 TON RTU FROM THE SOUTH.
  
 5) THE LINE OF SITE PLAN FOR BUILDING J8 NEEDS TO SHOW
 IMPACT OF THE 12.5 TON RTU FROM THE SOUTH AND THE 10
 TON RTUS THAT ARE OVER THE SERVICE BAYS (THE PARAPET
 WALL IS CLOSER TO THE RTU HERE).
  
 6) PLEASE PROVIDE THE HEIGHTS OF THE 20 AND 25 TON
 RTUS.
  
 7) THE EAST ELEVATION FOR BUILDING J6 DOES NOT
 ACURATELY REFLECT THE CHANGES TO THE WEST ELEVATION.
  
 8) SHEEST M216 AND M218 SHOW 2 OF THE RTU HAVING
 DIFFERENT TONAGE THEN THE ROOF PLAN.
  
 9) CHANGES REQUIRED TO BE SHOWN ON THE AS-BUILT SITE
 PLAN AMENDMENT.
  
 A. BLDG J-3 GENERATOR
 B. BLDG J-4 RELOCATED TREES
 C. BLDG J-6 NEW REAR DOOR
 D. BLDG J-7 ENTRY
 E. BLDG J-1 ENTRY BOLLARDS
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.