Plan Review Details - Permit 13090100
Plan Review Stops For Permit 13090100
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-11-22 Cont ID  
Sent By jwitmer Date 2013-11-22 Time 10:53 Rev Time 0.00
Received By jwitmer Date 2013-11-22 Time 10:53 Sent To  
Notes
2013-11-22 10:57:30BUILDING PLAN REVIEW
 PERMIT: 13090100
 ADD: 1855 PALM BEACH LAKES SHELL B-II
 CONT: EMJ
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE:NOV. 22/2013
 ACTION:BUILDING PROVISO
  
 1) MISSING RESIDENT INSPECTOR PACKAGE, TILT WALL
 REQUIRES A RESIDENT INSPECTOR. FBC* 109.3.7 RESIDENT
 INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE DOCUMENTS TO KEN
 CONRAD MANAGER OF THE RESIDENT INSPECTOR PROGRAM. A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED, ON THIS
 PROJECT, DUE TO ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II CONSTRUCTION
 -- BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS OF
 CONSTRUCTION / TILT WALL
  
 A HOLD WILL BE PUT ON THE ISSUANCE OF THE PERMIT
 WITHOUT THE RESIDENT INSPECTOR PACKAGE APPROVED BY KEN
 CONRAD.
  
 KEN CONRAD
 TEL 561-805-6666
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-10-03 Cont ID  
Sent By jwitmer Date 2013-10-03 Time 11:00 Rev Time 0.00
Received By jwitmer Date 2013-10-03 Time 09:45 Sent To  
Notes
2013-10-03 10:33:49BUILDING PLAN REVIEW
 PERMIT: 13090100
 ADD: 1855 PALM BEACH LAKES SHELL BII
 CONT: EMJ
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: OCT. 03/2013
 ACTION: DENIED
  
 1) MISSING SOILS REPORT 2010 FBC-B / 1802.2.1
 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF
 THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1803.3.1 & 1803.6
 REPORTING.
  
 2) MISSING RESIDENT INSPECTOR PACKAGE, TILT WALL
 REQUIRES A RESIDENT INSPECTOR. FBC* 109.3.7 RESIDENT
 INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE DOCUMENTS TO KEN
 CONRAD MANAGER OFTHE RESIDENT INSPECTOR PROGRAM. A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED, ON THIS
 PROJECT, DUE TO ONE OR MORE OF THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQ FT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
 KEN CONRAD
 TEL 561-805-6666
 E-MAIL: [email protected]
  
 3) MISSING. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) MISSING 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, ROOF HATCHES .
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 5) STRUCTURAL SHEET UNDER TTHE COMPONENTS & CLADDING
 FIGURES 20 SQ FT MIN IN PRESSURES, FOR THE ROOFING
 PRODUCT APPROVAALS WE USE 10 SQ FT WITH THE HIGH
 PRESSURES, COMPONENTS & CLADDING 1609.6.4.4.1.
  
 6) A112 TENANT SPACE B11 IN THE REAR OF THE BUILDING IN
 THE STORAGE ROOM IT APPEARS TO HAVE 2 WALLS THAT
 PARTIALLY BLOCKS THE EGRESS PATH, PLEASE SHOW
 COMPLIANCE WITH 2010 FBC-B 1014.2.4 EXCEPTION # 2(1-4).
  
 7) A142 INDICATES A ROOF HATCH WITHIN 10'-0" OF THE
 EDGE OF THE ROOF, SHOW COMPLIANCE WITH 2010 FBC-B
 1013.6.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-12-20 Cont ID  
Sent By albarran Date 2013-12-20 Time 09:40 Rev Time 0.00
Received By albarran Date 2013-12-20 Time 07:58 Sent To  
Notes
2013-12-20 09:55:49THOUGH LIGHTING POWER DENSITY CALCULATIONS WERE NOT
 PROVIDED, I APPROVED THE PERMIT WITH THE STIPULATION
 THAT EACH TENANT SHALL PROVIDE SPECIFIC POWER DENSITY
 CALCULATIONS WITH THEIR RESPECTIVE BUILD-OUTS
 FIRE ALARM & LOW VOLTAGE PERMITS SHALL BE REQUIRED.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-12-09 Cont ID  
Sent By albarran Date 2013-12-09 Time 09:46 Rev Time 0.00
Received By albarran Date 2013-12-06 Time 16:54 Sent To  
Notes
2013-12-09 09:47:24THERE ARE MISSING PAGES ON THIS FILE, THEREFORE
 COMPLETE REVIEW IS NOT POSSIBLE
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-10-01 Cont ID  
Sent By dharvey Date 2013-10-01 Time 13:24 Rev Time 0.00
Received By dharvey Date 2013-10-01 Time 11:49 Sent To  
Notes
2013-10-01 11:49:56#13090100
 1855 PALM BEACH LAKES BLVD
 MALL OUT PARCEL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE GFP PROTECTION FOR THE ELECTRICAL SERVICE. NEC
 230-95
  
 VERIFY THE ELECTRICAL EQUIPMENT HAS SUFFICIENT
 INTERRUPTING RATING. INDICATE THE ELECTRICAL EQUIPMENT
 INTERRUPTING RATING ON THE PLANS. NEC 110.9
  
 VERIFY REQUIRED ACCESS AND WORKING CLEARANCES HAVE BEEN
 PROVIDED TO THE ELECTRICAL EQUIPMENT. NEC 110.26
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.22, 110.16, 110.22
  
 PROVIDE PANEL SCHEDULES FOR HVB2 AND LVB2.
  
 LIGHTING TIMERS REQUIRE BACKUP PROTECTION. FBC-EC
 505.2.4
  
 VERIFY THE LIGHTING SCENES, SEQUENCING AND CONTROLS
 MEET THE REQUIREMENTS OF FBC ENERGY CODE. FBC-EC 505.2
  
 PROVIDE LIGHTING POWER DENSITY COMPLIANCE CERTIFICATION
 ON ELECTRICAL PLANS. FBC-EC 505.503
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2013-10-29 Cont ID  
Sent By mgonzale Date 2013-10-29 Time   Rev Time 1.00
Received By mgonzale Date 2013-10-29 Time   Sent To I
Notes
2013-10-29 09:32:32NO OBJECTION OR CONFLICTS
2013-10-29 09:31:50ALL UTILITIES ARE PRIVATE.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-09-30 Cont ID  
Sent By scaldero Date 2013-09-30 Time 12:54 Rev Time 0.00
Received By scaldero Date 2013-09-30 Time 12:54 Sent To  
Notes
2013-09-30 12:54:03PERMIT # 13090100
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 STENCIL/PAINT REAR EXIT DOORS - "EXIT DOOR - DO NOT
 BLOCK".
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2014-02-05 Time   Rev Time 0.00
Received By rregueir Date 2014-01-07 Time 10:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-11 Cont ID  
Sent By rregueir Date 2013-12-20 Time 13:04 Rev Time 0.00
Received By rregueir Date 2013-11-13 Time 18:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2013-10-31 Time   Rev Time 0.00
Received By rregueir Date 2013-09-09 Time 09:05 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2013-12-04 Cont ID  
Sent By jwitmer Date 2013-12-04 Time 08:45 Rev Time 0.00
Received By jwitmer Date 2013-12-04 Time 08:45 Sent To  
Notes
2013-12-04 08:46:06P. B. CTY IMPACT FEE OFFICE:
 PLANS STAMPED NO FEES DUE
 RE: MU-2013-024550-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-11-22 Cont ID  
Sent By jwitmer Date 2013-11-22 Time 10:58 Rev Time 0.00
Received By jwitmer Date 2013-11-22 Time 10:58 Sent To  
Notes
2013-11-22 10:58:40BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-11-22 Cont ID  
Sent By jwitmer Date 2013-11-22 Time 10:58 Rev Time 0.00
Received By jwitmer Date 2013-11-22 Time 10:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-10-31 Cont ID  
Sent By rregueir Date 2013-10-31 Time 15:42 Rev Time 0.00
Received By rregueir Date 2013-10-31 Time 15:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-09-30 Cont ID  
Sent By lwagner Date 2013-09-30 Time 13:58 Rev Time 0.00
Received By lwagner Date 2013-09-30 Time 13:24 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2013-11-22 Cont ID  
Sent By jwitmer Date 2013-11-22 Time 11:00 Rev Time 0.00
Received By jwitmer Date 2013-11-22 Time 10:59 Sent To  
Notes
2013-11-22 11:06:31ROOFING PERMIT
 NOA 12-0514.04
 FIRESTONE TPO & TPO X R SINGLE PLY ROOF SYSTEM
  
 NOTE ROOF ZONE # 1 PAGE 28 FASTENING SYSTEM # 1
  
 PAGE 6 FULLY ADHERRED SYSTEM FOR ZONE # 2.
  
 PAGE 8 DEFINES ZONE 3 GENERAL LIMITATION #7 PARAPET
 OVER 3'-0" NO ZONE 3, CONSIDERED ZONE # 2.
  
 ROOF INSULATION DEFINED ON PAGE 12,
 R VALUE OF ROOF IS 30.
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2013-11-22 Cont ID  
Sent By jwitmer Date 2013-11-22 Time 10:59 Rev Time 0.00
Received By jwitmer Date 2013-11-22 Time 10:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2014-02-20 Cont ID  
Sent By rregueir Date 2014-02-20 Time 09:25 Rev Time 0.00
Received By rregueir Date 2014-02-19 Time 09:25 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2014-02-12 Cont ID  
Sent By eschneid Date 2014-02-05 Time 23:52 Rev Time 0.25
Received By eschneid Date 2014-02-05 Time 23:52 Sent To  
Notes
2014-01-09 11:09:411/9/14

Review Stop Z ZONING
Rev No 2 Status F Date 2013-12-11 Cont ID  
Sent By eschneid Date 2013-12-11 Time 10:18 Rev Time 1.00
Received By eschneid Date 2013-12-11 Time 10:18 Sent To  
Notes
2013-12-11 12:46:57FAILED
  
 1) THE PLAN LABLED AS 010_2110040-BII_A142_ROOF PLAN
 (1).PDF V2 IS ACUTALLY THE ROOF PLAN FOR BUILDING BI
 NOT BII. PROVIDE THE CORRECT PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
2013-12-02 11:15:0212/2/13

Review Stop Z ZONING
Rev No 1 Status F Date 2013-10-18 Cont ID  
Sent By eschneid Date 2013-10-18 Time 15:07 Rev Time 1.00
Received By eschneid Date 2013-10-18 Time 15:07 Sent To  
Notes
2013-10-18 15:14:55FAILED
  
 1) THE PERMIT SHALL INCLUDE THE SIGHT LINE DRAWINGS
 THAT VERIFY THE ROOFTOP MECHANICAL EQUIPMENT IS
 SCREENED FROM VIEW. THE DRAWINGS SHALL INCLUDE
 INFORMATION ON THE SIZE OF THE SPECIFIC ROOFTOP UNIT
 AND THE HEIGHT, INCLUDING THE CURB OF THE UNITS (MAY BE
 DONE IN CHART FORM).
  
 2) THE SIGHT LINE DRAWINGS SUPPLIED WITH THE ZONING
 APPLICATION SHOW NO SCREENING ISSUES, BUT ALSO GIVE NO
 INFORMATION ON THE SPECIFIC RTU TO CORRELATE THE UNIT
 SIZE WITH THE UNITS SHOWN ON THE BUILDING PERMIT PLANS.
 ADDITIONALLY, ONE OF THE UNITS ON BAY B01 IS CLOSER TO
 THE EDGE OF THE BUILDING ON THE PERMIT THAN AS IT IS
 SHOWN ON THE ZONING PLANS.
  
 3) PROVIDE A SITE PLAN/SURVEY WHICH SHOWS THE SETBACKS
 OF THE BUILIDING FROM THE WEST PROPERTY LINE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2013-09-30 10:25:029/30/13