| Plan Review Stops For Permit 13090100 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2013-11-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-11-22 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-11-22 |
Time |
10:53 |
Sent To |
|
|
| Notes |
| 2013-11-22 10:57:30 | BUILDING PLAN REVIEW | | | PERMIT: 13090100 | | | ADD: 1855 PALM BEACH LAKES SHELL B-II | | | CONT: EMJ | | | TEL: (561 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 2ND REVIEW | | | DATE:NOV. 22/2013 | | | ACTION:BUILDING PROVISO | | | | | | 1) MISSING RESIDENT INSPECTOR PACKAGE, TILT WALL | | | REQUIRES A RESIDENT INSPECTOR. FBC* 109.3.7 RESIDENT | | | INSPECTOR. | | | SUBMIT INSPECTOR RESUME' AND LICENSE DOCUMENTS TO KEN | | | CONRAD MANAGER OF THE RESIDENT INSPECTOR PROGRAM. A | | | RESIDENT INSPECTOR PROGRAM IS REQUIRED, ON THIS | | | PROJECT, DUE TO ONE OR MORE OF THE FOLLOWING: | | | - BUILDINGS/ADDITIONS OF TYPE I OR II CONSTRUCTION | | | -- BUILDING/STRUCTURES OF UNUSUAL DESIGN OR METHODS OF | | | CONSTRUCTION / TILT WALL | | | | | | A HOLD WILL BE PUT ON THE ISSUANCE OF THE PERMIT | | | WITHOUT THE RESIDENT INSPECTOR PACKAGE APPROVED BY KEN | | | CONRAD. | | | | | | KEN CONRAD | | | TEL 561-805-6666 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2013-10-03 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-10-03 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-10-03 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2013-10-03 10:33:49 | BUILDING PLAN REVIEW | | | PERMIT: 13090100 | | | ADD: 1855 PALM BEACH LAKES SHELL BII | | | CONT: EMJ | | | TEL: (561 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: OCT. 03/2013 | | | ACTION: DENIED | | | | | | 1) MISSING SOILS REPORT 2010 FBC-B / 1802.2.1 | | | QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF | | | THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE | | | SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE | | | BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY | | | INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY | | | WITH THE PROVISIONS OF SECTIONS 1803.3.1 & 1803.6 | | | REPORTING. | | | | | | 2) MISSING RESIDENT INSPECTOR PACKAGE, TILT WALL | | | REQUIRES A RESIDENT INSPECTOR. FBC* 109.3.7 RESIDENT | | | INSPECTOR. | | | SUBMIT INSPECTOR RESUME' AND LICENSE DOCUMENTS TO KEN | | | CONRAD MANAGER OFTHE RESIDENT INSPECTOR PROGRAM. A | | | RESIDENT INSPECTOR PROGRAM IS REQUIRED, ON THIS | | | PROJECT, DUE TO ONE OR MORE OF THE FOLLOWING: | | | - BUILDINGS/ADDITIONS OF TYPE I OR II | | | CONSTRUCTION | | | - ANY MAJOR STRUCTURAL ALTERATIONS | | | - STRUCTURES IN WHICH THE CONCRETE | | | DESIGN IS BASED ON COMPRESSIVE | | | STRENGTH (F'C) IN EXCESS OF 3000 PSI | | | - PILE DRIVING | | | - BUILDINGS OVER 20,000 SQ FT IN AREA | | | - BUILDINGS OVER 2 STORIES IN HEIGHT | | | - BUILDING/STRUCTURES OF UNUSUAL DESIGN | | | OR METHODS OF CONSTRUCTION | | | KEN CONRAD | | | TEL 561-805-6666 | | | E-MAIL: [email protected] | | | | | | 3) MISSING. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE | | | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 | | | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR | | | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, | | | SHOP DRAWINGS ETC.. | | | | | | 4) MISSING 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, | | | 1609.6.4.41 COMPONENTS & CLADDING | | | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. | | | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION | | | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: | | | (31)(A) EXTERIOR DOORS, ROOF HATCHES . | | | (B) WINDOWS | | | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL | | | LOUVERS, EFIS SYSTEMS, | | | (D) ROOFING PRODUCTS AND ASSEMBLIES | | | (E) SHUTTERS | | | (F) SKYLIGHTS | | | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C | | | STANDS | | | | | | 5) STRUCTURAL SHEET UNDER TTHE COMPONENTS & CLADDING | | | FIGURES 20 SQ FT MIN IN PRESSURES, FOR THE ROOFING | | | PRODUCT APPROVAALS WE USE 10 SQ FT WITH THE HIGH | | | PRESSURES, COMPONENTS & CLADDING 1609.6.4.4.1. | | | | | | 6) A112 TENANT SPACE B11 IN THE REAR OF THE BUILDING IN | | | THE STORAGE ROOM IT APPEARS TO HAVE 2 WALLS THAT | | | PARTIALLY BLOCKS THE EGRESS PATH, PLEASE SHOW | | | COMPLIANCE WITH 2010 FBC-B 1014.2.4 EXCEPTION # 2(1-4). | | | | | | 7) A142 INDICATES A ROOF HATCH WITHIN 10'-0" OF THE | | | EDGE OF THE ROOF, SHOW COMPLIANCE WITH 2010 FBC-B | | | 1013.6. | | | | | | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2013-12-20 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2013-12-20 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2013-12-20 |
Time |
07:58 |
Sent To |
|
|
| Notes |
| 2013-12-20 09:55:49 | THOUGH LIGHTING POWER DENSITY CALCULATIONS WERE NOT | | | PROVIDED, I APPROVED THE PERMIT WITH THE STIPULATION | | | THAT EACH TENANT SHALL PROVIDE SPECIFIC POWER DENSITY | | | CALCULATIONS WITH THEIR RESPECTIVE BUILD-OUTS | | | FIRE ALARM & LOW VOLTAGE PERMITS SHALL BE REQUIRED. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2013-12-09 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2013-12-09 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2013-12-06 |
Time |
16:54 |
Sent To |
|
|
| Notes |
| 2013-12-09 09:47:24 | THERE ARE MISSING PAGES ON THIS FILE, THEREFORE | | | COMPLETE REVIEW IS NOT POSSIBLE | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2013-10-01 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-10-01 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-10-01 |
Time |
11:49 |
Sent To |
|
|
| Notes |
| 2013-10-01 11:49:56 | #13090100 | | | 1855 PALM BEACH LAKES BLVD | | | MALL OUT PARCEL | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PROVIDE GFP PROTECTION FOR THE ELECTRICAL SERVICE. NEC | | | 230-95 | | | | | | VERIFY THE ELECTRICAL EQUIPMENT HAS SUFFICIENT | | | INTERRUPTING RATING. INDICATE THE ELECTRICAL EQUIPMENT | | | INTERRUPTING RATING ON THE PLANS. NEC 110.9 | | | | | | VERIFY REQUIRED ACCESS AND WORKING CLEARANCES HAVE BEEN | | | PROVIDED TO THE ELECTRICAL EQUIPMENT. NEC 110.26 | | | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION | | | FOR THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC | | | 110.22, 110.16, 110.22 | | | | | | PROVIDE PANEL SCHEDULES FOR HVB2 AND LVB2. | | | | | | LIGHTING TIMERS REQUIRE BACKUP PROTECTION. FBC-EC | | | 505.2.4 | | | | | | VERIFY THE LIGHTING SCENES, SEQUENCING AND CONTROLS | | | MEET THE REQUIREMENTS OF FBC ENERGY CODE. FBC-EC 505.2 | | | | | | PROVIDE LIGHTING POWER DENSITY COMPLIANCE CERTIFICATION | | | ON ELECTRICAL PLANS. FBC-EC 505.503 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2013-10-29 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2013-10-29 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2013-10-29 |
Time |
|
Sent To |
I |
|
| Notes |
| 2013-10-29 09:32:32 | NO OBJECTION OR CONFLICTS | | 2013-10-29 09:31:50 | ALL UTILITIES ARE PRIVATE. | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2013-09-30 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2013-09-30 |
Time |
12:54 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2013-09-30 |
Time |
12:54 |
Sent To |
|
|
| Notes |
| 2013-09-30 12:54:03 | PERMIT # 13090100 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A | | | LOCK/UNLOCK INDICATOR. | | | | | | EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH | | | SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL | | | OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN | | | HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE | | | SPACED NOT MORE THAN 15 FEET ON CENTER. | | | | | | STENCIL/PAINT REAR EXIT DOORS - "EXIT DOOR - DO NOT | | | BLOCK". | | | | | | SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE | | | FIRE ALARM AND SPRINKLER SYSTEM. | | | | | | SUE ELLEN CALDERON | | | FIRE INSPECTOR & INVESTIGATOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2014-02-05 |
Time |
|
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2014-01-07 |
Time |
10:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-12-11 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2013-12-20 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2013-11-13 |
Time |
18:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2013-10-31 |
Time |
|
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2013-09-09 |
Time |
09:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
N |
Date |
2013-12-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-12-04 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-12-04 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2013-12-04 08:46:06 | P. B. CTY IMPACT FEE OFFICE: | | | PLANS STAMPED NO FEES DUE | | | RE: MU-2013-024550-0000 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2013-11-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-11-22 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-11-22 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2013-11-22 10:58:40 | BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF | | | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2013-11-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-11-22 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-11-22 |
Time |
10:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2013-10-31 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2013-10-31 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2013-10-31 |
Time |
15:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2013-09-30 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2013-09-30 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2013-09-30 |
Time |
13:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2013-11-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-11-22 |
Time |
11:00 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-11-22 |
Time |
10:59 |
Sent To |
|
|
| Notes |
| 2013-11-22 11:06:31 | ROOFING PERMIT | | | NOA 12-0514.04 | | | FIRESTONE TPO & TPO X R SINGLE PLY ROOF SYSTEM | | | | | | NOTE ROOF ZONE # 1 PAGE 28 FASTENING SYSTEM # 1 | | | | | | PAGE 6 FULLY ADHERRED SYSTEM FOR ZONE # 2. | | | | | | PAGE 8 DEFINES ZONE 3 GENERAL LIMITATION #7 PARAPET | | | OVER 3'-0" NO ZONE 3, CONSIDERED ZONE # 2. | | | | | | ROOF INSULATION DEFINED ON PAGE 12, | | | R VALUE OF ROOF IS 30. | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2013-11-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-11-22 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-11-22 |
Time |
10:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2014-02-20 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2014-02-20 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2014-02-19 |
Time |
09:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2014-02-12 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2014-02-05 |
Time |
23:52 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2014-02-05 |
Time |
23:52 |
Sent To |
|
|
| Notes |
| 2014-01-09 11:09:41 | 1/9/14 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2013-12-11 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2013-12-11 |
Time |
10:18 |
Rev Time |
1.00 |
| Received By |
eschneid |
Date |
2013-12-11 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2013-12-11 12:46:57 | FAILED | | | | | | 1) THE PLAN LABLED AS 010_2110040-BII_A142_ROOF PLAN | | | (1).PDF V2 IS ACUTALLY THE ROOF PLAN FOR BUILDING BI | | | NOT BII. PROVIDE THE CORRECT PLANS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | | | 2013-12-02 11:15:02 | 12/2/13 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2013-10-18 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2013-10-18 |
Time |
15:07 |
Rev Time |
1.00 |
| Received By |
eschneid |
Date |
2013-10-18 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2013-10-18 15:14:55 | FAILED | | | | | | 1) THE PERMIT SHALL INCLUDE THE SIGHT LINE DRAWINGS | | | THAT VERIFY THE ROOFTOP MECHANICAL EQUIPMENT IS | | | SCREENED FROM VIEW. THE DRAWINGS SHALL INCLUDE | | | INFORMATION ON THE SIZE OF THE SPECIFIC ROOFTOP UNIT | | | AND THE HEIGHT, INCLUDING THE CURB OF THE UNITS (MAY BE | | | DONE IN CHART FORM). | | | | | | 2) THE SIGHT LINE DRAWINGS SUPPLIED WITH THE ZONING | | | APPLICATION SHOW NO SCREENING ISSUES, BUT ALSO GIVE NO | | | INFORMATION ON THE SPECIFIC RTU TO CORRELATE THE UNIT | | | SIZE WITH THE UNITS SHOWN ON THE BUILDING PERMIT PLANS. | | | ADDITIONALLY, ONE OF THE UNITS ON BAY B01 IS CLOSER TO | | | THE EDGE OF THE BUILDING ON THE PERMIT THAN AS IT IS | | | SHOWN ON THE ZONING PLANS. | | | | | | 3) PROVIDE A SITE PLAN/SURVEY WHICH SHOWS THE SETBACKS | | | OF THE BUILIDING FROM THE WEST PROPERTY LINE. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | 2013-09-30 10:25:02 | 9/30/13 |
|
|