Plan Review Details - Permit 13090090
Plan Review Stops For Permit 13090090
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-10-02 Cont ID  
Sent By dharvey Date 2013-10-02 Time 16:14 Rev Time 0.00
Received By dharvey Date 2013-10-02 Time 16:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-09-16 Cont ID  
Sent By dharvey Date 2013-09-16 Time 14:50 Rev Time 0.00
Received By dharvey Date 2013-09-16 Time 14:41 Sent To  
Notes
2013-09-16 14:50:28OVERCURRENT PROTECTION AND DISCONNECTING MEANS TO BE
 CONTAINED IN SAME ENCLOSURE OR IMMEDIATELY ADJACENT TO
 EACH OTHER. 230.91, 240.26
 PROVIDE INTERSYSTEM BONDING POINT 250.94
 PROVIDE DETAILS OF SERVICE BRACING PER FPL SERVICE
 STANDARDS MANUAL
 PROVIDE LABELING INFORMATION AND DOT/STATE OF FLORIDA
 MANUFACTURED BUILDING INFORMATION
 DEFINE PURPOSE AND USE OF TRAILER
 DOES THE TRAILER HAVE PLUMBING? PLUMBING PERMIT
 REQUIRED
 ENTRY STEPS? IS THIS UNIT ADA EXEMPT?
  
 DH

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-02 Cont ID  
Sent By dharvey Date 2013-10-02 Time 16:14 Rev Time 0.00
Received By dharvey Date 2013-10-01 Time 14:12 Sent To  
Notes
2013-10-02 16:14:56TO S HILL
2013-10-02 14:12:26SENT TO D HARVEY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-16 Cont ID  
Sent By dharvey Date 2013-09-16 Time 14:50 Rev Time 0.00
Received By dharvey Date 2013-09-05 Time 11:45 Sent To  
Notes
2013-09-16 14:53:59IN DENIED UNDER "K" DH
2013-09-05 11:45:20ROUTED TO ELECTRICAL LESS THAN 5000