Plan Review Details - Permit 13090031
Plan Review Stops For Permit 13090031
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-11-07 Cont ID  
Sent By jwitmer Date 2013-11-07 Time 13:45 Rev Time 0.00
Received By jwitmer Date 2013-11-07 Time 13:45 Sent To  
Notes
2013-11-07 13:54:00BUILDING PLAN REVIEW
 PERMIT: 13090031
 ADD: 615 N DIXIE HWY
 CONT: BUTLER CONSTRUCTION
 TEL: (561))832-9700
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE;THURS. NOV. 07/ 2013
 ACTIONBUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
  
 1) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C): STOREFRONTS, CURTAIN WALLS, WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) PRE-ENGINEERED A/C STANDS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-09-25 Cont ID  
Sent By jwitmer Date 2013-09-25 Time 11:31 Rev Time 0.00
Received By jwitmer Date 2013-09-24 Time 14:53 Sent To  
Notes
2013-09-25 11:31:24BUILDING PLAN REVIEW
 PERMIT: 13090031
 ADD: 615 N DIXIE HWY
 CONT: BUTLER CONSTRUCTION
 TEL: (561))832-9700
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED SEPT 25/ 2013
 ACTION: DENIED
  
 1) STRUCTURAL SHEET S-2 INDICATES A SOILS REPORT BY
 TIERRA WAS COMPLETED ON JUNE 13/ 2013, PLEASE PROVIDE 2
 SIGNED AND SEALED ORIGINALS. 2010 FBC-B 1803.5.2..
  
 2) STRUCTURAL SHEET S-1 THE WALLS WITH MARKER TAGS MW,
 & MW-2 DO NOT INDICATE THE USE OF ANY VERTICAL STEEL,
 SIZE , SPACING AND OR QUANTITY OF STEEL IN THE
 BLOCKWORK. 2010 FBC-B 2108.2/ 3.3.3.3
 530 ASCE.
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C): STOREFRONTS, CURTAIN WALLS, WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) PRE-ENGINEERED A/C STANDS
  
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-10-17 Cont ID  
Sent By dharvey Date 2013-10-17 Time 17:12 Rev Time 0.00
Received By dharvey Date 2013-10-17 Time 15:50 Sent To  
Notes
2013-10-17 17:21:33THE FOLLOWING CORRECTIONS/ADJUSTMENTS NEED TO BE
 ADDRESSED:
 1. TAKING INTO ACCOUNT THE ADJUSTMENT FACTORS OF NEC
 310.15(B)(2)(A) REQUIRED FOR FOUR CURRENT CARRYING
 CONDUCTORS IN A RACEWAY AND THE VALUES AS PER NEC
 310.16, THIS FEEDER WILL ONLY WORK IF USING 90 DEGREE
 INSULATION.
 THE LESSER 75 DEGREE COLUMN LIMITS 500 MCM TO 380 AMP
 AND APPLYING THE CORRECTION FACTORS OF 310.15 OF 80%
 REDUCES THE AMPACITY OF THE CONDUCTOR TO ONLY 304 AMP.
  
 MAKE THE CORRESPONDING NOTES ON THE DRAWINGS

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2013-11-06 Cont ID  
Sent By mgonzale Date 2013-11-06 Time   Rev Time 0.25
Received By mgonzale Date 2013-11-06 Time   Sent To B
Notes
2013-11-06 15:35:25PASSED

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2013-10-11 Cont ID  
Sent By Mgonzale Date 2013-10-11 Time   Rev Time 0.25
Received By mgonzale Date 2013-10-11 Time   Sent To Z
Notes
2013-10-11 08:19:15A SEPARATE SUBMITTTAL IS REQUIRED FOR ENGINEERING.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES AND PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-09-11 Cont ID  
Sent By wjolin Date 2013-09-11 Time 18:39 Rev Time 0.00
Received By wjolin Date 2013-09-11 Time 18:07 Sent To  
Notes
2013-09-11 18:39:36615 NORTH DIXIE HIGHWAY
 PERMIT #13090031
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-11-12 Cont ID  
Sent By hmoser Date 2013-11-12 Time 09:52 Rev Time 0.00
Received By hmoser Date 2013-10-23 Time 12:31 Sent To  
Notes
2013-10-28 12:38:04C33
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-17 Cont ID  
Sent By rbrown Date 2013-10-17 Time 18:56 Rev Time 0.00
Received By rbrown Date 2013-09-03 Time 17:22 Sent To  
Notes
2013-09-03 17:22:18C22

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2013-11-12 Cont ID  
Sent By jwitmer Date 2013-11-12 Time 16:18 Rev Time 0.00
Received By jwitmer Date 2013-11-12 Time 16:18 Sent To  
Notes
2013-11-12 16:26:08PALM BEACH COUNTY IMPACT FEE ASSESSMENT:
 MU-2013-023975-0000
 $53,851.40
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-11-07 Cont ID  
Sent By jwitmer Date 2013-11-07 Time 13:55 Rev Time 0.00
Received By jwitmer Date 2013-11-07 Time 13:55 Sent To  
Notes
2013-11-07 13:55:44BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-09-25 Cont ID  
Sent By jwitmer Date 2013-09-25 Time 11:31 Rev Time 0.00
Received By jwitmer Date 2013-09-25 Time 11:31 Sent To  
Notes
2013-09-25 11:31:47BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-11-12 Cont ID  
Sent By hmoser Date 2013-11-12 Time 09:51 Rev Time 0.00
Received By hmoser Date 2013-11-12 Time 09:35 Sent To  
Notes
2013-11-12 09:51:35PASS PROVISO
 PROVIDE NOA FOR CONDENSER
 STAND BY FIRST INSPECTION
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-10-11 Cont ID  
Sent By hmoser Date 2013-10-11 Time 14:54 Rev Time 0.00
Received By hmoser Date 2013-10-11 Time 14:17 Sent To  
Notes
2013-10-11 14:54:01PLANS DENIED
 1) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS.
 (FOR FRESH AIR AND EXHAUST) 2010 FLORIDA ENERGY CODE.
 2) PROVIDE NOA FOR CONDENSER STAND.
 PER SECTION 107 FBC 2010
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-10-29 Cont ID  
Sent By lwagner Date 2013-10-29 Time 13:58 Rev Time 0.00
Received By lwagner Date 2013-10-29 Time 13:11 Sent To  
Notes
2013-10-29 13:33:20REVISION REQUIRED
  
 ***PROVISO***
 THE EVEVATOR SUMP PUMP SHALL BE INDIRECTLY
 CONNECTED TO THE SANITARY SYSTEM. 301.6
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-09-17 Cont ID  
Sent By lwagner Date 2013-09-17 Time 10:36 Rev Time 0.00
Received By lwagner Date 2013-09-17 Time 09:35 Sent To  
Notes
2013-09-17 10:33:59FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET P0.1: ON THE SANITARY ISO. THE 2ND FLOOR SINK
 IS REQUIRED TO CONNECT DOWNSTREAM OF THE RESTROOM WET
 VENT FOR THE WATER CLOSET & LAV.
 909.1 HORIZONTAL WET VENT PERMITTED.
 ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL IS PERMITTED TO BE
 VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE
 CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND
 FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION
 OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM
 FIXTURE DRAIN CONNECTION TO THE HORIZONTAL BRANCH
 DRAIN. EACH WET-VENTED FIXTURE DRAIN SHALL CONNECT
 INDEPENDENTLY TO THE HORIZONTAL WET VENT. ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT.
  
 2. SHEET P0.1: ON THE SANITARY ISO. THE SOIL STACK FOR
 THE 2ND FLOOR FIXTURES IS RUN THROUGH THE 1ST FLOOR
 RESTROOM.
 909.1 HORIZONTAL WET VENT PERMITTED.
 ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL IS PERMITTED TO BE
 VENTED BY A HORIZONTAL WET VENT...
  
 3. SHEET P0.1: THE EVEVATOR SUMP PUMP IS NOT PERMITTED
 TO BE DIRECTLY CONNECTED TO THE SANITARY SYSTEM.
 301.6 PROHIBITED LOCATIONS.
 PLUMBING SYSTEMS SHALL NOT BE LOCATED IN AN ELEVATOR
 SHAFT OR IN AN ELEVATOR EQUIPMENT ROOM.
  
 EXCEPTION: FLOOR DRAINS, SUMPS AND SUMP PUMPS SHALL BE
 PERMITTED AT THE BASE OF THE SHAFT, PROVIDED THAT THEY
 ARE INDIRECTLY CONNECTED TO THE PLUMBING SYSTEM AND
 COMPLY WITH SECTION 1003.4.
  
 4. SHEET P0.1: THE EVEVATOR SUMP PUMP WILL REQUIRE AN
 APPROVED OIL ALARM SYSTEM.
 1003.4 OIL SEPARATORS REQUIRED.
 AT REPAIR GARAGES, CAR-WASHING FACILITIES, AT FACTORIES
 WHERE OILY AND FLAMMABLE LIQUID WASTES ARE PRODUCED AND
 IN HYDRAULIC ELEVATOR PITS, SEPARATORS SHALL BE
 INSTALLED INTO WHICH ALL OIL-BEARING, GREASE-BEARING OR
 FLAMMABLE WASTES SHALL BE DISCHARGED BEFORE EMPTYING
 INTO THE BUILDING DRAINAGE SYSTEM OR OTHER POINT OF
 DISPOSAL.
  
 EXCEPTION: AN OIL SEPARATOR IS NOT REQUIRED IN
 HYDRAULIC ELEVATOR PITS WHERE AN APPROVED ALARM SYSTEM
 IS INSTALLED.
  
 5. SHEET P0.1: THE WATER PIPE ISO. SHOWS 1" WATER
 SERVICE. THE PLUMBING FIXTURE SCHEDULE CALLS FOR FLUSH
 VALVE TYPE WATER CLOSETS. FROM TABLE 603.1, 1 1/2" PIPE
 WOULD BE REQUIRED OR PLEASE PROVIDE CALCULATIONS.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2013-11-07 Cont ID  
Sent By jwitmer Date 2013-11-07 Time 13:54 Rev Time 0.00
Received By jwitmer Date 2013-11-07 Time 13:54 Sent To  
Notes
2013-11-07 13:55:20ROOFING/ BUILDING PLAN REVIEW
 PERMIT: 13090031
 ADD: 615 N DIXIE HWY
 CONT: BUTLER CONSTRUCTION
 TEL: (561))832-9700
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE;THURS. NOV. 07/ 2013
 ACTIONBUILDING PROVISO
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
  
 1) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES
  
  
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2013-11-01 Cont ID  
Sent By aaponte Date 2013-11-01 Time 15:21 Rev Time 0.00
Received By aaponte Date 2013-11-01 Time 15:21 Sent To  
Notes
2013-11-01 16:16:50PROVISO:
 1. LANDSCAPE DRAWINGS SHALL BE UPDATED TO REFLECT THE
 CONDITIONS OF APPROVAL FOR THE SALE OF THE CITY-OWNED
 PROPERTY.
 2. ALL THE APPROVALS FROM FDOT FOR THE DECELARATION
 LANE AND CURB CUT ALONG QUADRILLE BLVD SHALL BE
 OBTAINED BEFORE CO CAN BE ISSUED.
 3. UNITY OF TITLE FOR 615 N DIXIE HWAY WILL BE REQUIRED
 BEFORE FINAL CO.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
  
2013-10-30 14:49:1310/29/13

Review Stop Z ZONING
Rev No 1 Status F Date 2013-10-15 Cont ID  
Sent By aaponte Date 2013-10-15 Time 11:57 Rev Time 0.00
Received By aaponte Date 2013-10-15 Time 11:57 Sent To  
Notes
2013-10-15 13:20:331. PRIVATE OPEN SPACE SHALL BE MINIMUM 12% OF THE LOT
 AREA.
 2. PLEASE INDICATE PARKING CALCULATION SEPARATE FOR
 EACH PARCEL, AND MAKE A NOTE REGARDING THE LOCATION OF
 THE 13 SPACES REQUIRED FOR 615 N. DIXIE HWAY OFF-SITE
 AT 415 5TH STREET. PARKIGN REQUIREMENT IS 2.5
 SPACES/1000SF.
 3. TEXT ON HISTORIC MARKER SHALL BE APPROVED BY
 HISTORIC PRESERVATION PLANNER. PLEASE SUBMIT DRAFT.
 4. PLEASE SUBMIT A COPY OF THE FDOT APPROVAL FOR THE
 DECELARATION LANE AND THE PROPOSED LANDSCAPE ON THE
 QUADRILLE ROW. PORTION OF THE NEW SIDEWALK WILL BE NOW
 IN PRIVATE PROPERTY. A CONDITION SHALL BE INCLUDED TO
 REQUIRE THE SIDEWALK TO BE OPEN TO THE PUBLIC. IF THE
 SIDEWALK IS GOING TO BE DEDICATED TO FDOT, PLEASE SHOW
 BOUNDARIES.
 5. SIGNAGE SHALL BE SUBMITTED AS A SEPARATE PERMIT (SEC
 94-110(C)).
 6. PLEASE CONFIRM ROOF TREATMENT COMPLIES WITH CODE
 REQUIREMENTS FOR SOLAR REFLECTANCE INDEX IN SEC 94-109
 (ROOF TREATMENT).
 7. PLEASE CONFIRM PROPOSED GLASS IS NOT REFLECTIVE.
 8. CHANGES ON LANDSCAPE ACCORDING TO CITY COMMISSION
 APPROVAL SHALL BE REFLECTED ON PERMIT SET.
 9. PLEASE INDICATE WHERE IS THE LOCATION OF THE SCREEN
 WALL DETAIL AS NUMBER 5 IN PAGE A-0.1.
 10. A RESTRICTIVE COVENANT FOR THE OFF-SITE PARKING AND
 A CROSS ACCESS AGREEMENT WILL BE REQUIRED BEFORE FINAL
 CO CAN BE ISSUED.
 11. UNITY OF TITLE WILL BE REQUIRED FOR THE 615 N.
 DIXIE HWAY AND SLIVER PROPERTY.
 12. ROOF TOP EQUIPMENT SCREEN DETAIL IS MISLABELED ON
 ROOF PLAN.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822 1439.
  
  
2013-09-05 09:28:059/5/13