Plan Review Details - Permit 13090021
Plan Review Stops For Permit 13090021
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-09-10 Cont ID  
Sent By jwitmer Date 2013-09-10 Time 14:58 Rev Time 0.00
Received By jwitmer Date 2013-09-10 Time 10:37 Sent To  
Notes
2013-09-10 16:39:18BUILDING PLAN REVIEW
 PERMIT: 13090021
 ADD: 5829 CORPORATE WAY
 CONT: JJ MORLEY ENTERPRISES
 TEL: (561)843-5325
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SEPTEMBER 10/ 2013
 ACTION: DENIED
  
 1) SHEET A1:
 1A) HEADING: SCOPE OF WORK (1) TO INSTALL A NEW 1 HOUR
 FIRE RATED CORRIDOR WALLS AND 1 HOUR FIRE RATED CEILING
 AS SHOWN ON PLANS. SHEET A1 DETAIL 1/ SHEET A2
 INDICATES THE USE OF A 1 HOUR FIRE RATED CEILING
 INSTEAD OF THE CORRIDOR WALLS GOING ALL THE WAY TO THE
 DECK ABOVE. THE DETAIL INDICATES THE CEILING TO FOLLOW
 THE UL LISTING 469. THE ONLY SHAFT WALL LISTED UNDER
 469 IS U-469 SHAFT WALL CONSTRUCTION FOR VERTICAL USE.
 THE 2010 FBC-B FIRE PARTITIONS 709.4 EXCEPTION # 3 DOES
 ALLOW FOR THE USE OF FIRE RATED WALL DESIGN TO BE USED
 FOR FIRE RATED CEILINGS AND THE UL- U 469 DOES NOT
 INDICATE HOW THIS CONSTRUCTION IS TO APPEAR, THE 2007
 FL CODE COMMENTARY FIGURE 708.4(2)(C) DOES SHOW HOW THE
 WALL MEMBERS, CEILING MEMBERS & DRYWALL LAPS ARE
 CONSTRUCTED TO MAINTAIN A 1 HOUR FIRE RATING.
  
 1B) DOOR NOTE # 5 INDICATES ALL DOORS SHALL HAVE LEVER
 TYPE HARDWARE. PLEASE PROVIDE THE HARDWARE TYPE ON THE
 EXISTING DOORS STIARWAYS, AND LOBBY AREA, THEY WILL
 ALSO NEED TO COMPLY WITH 2010 FBC-B 1008.1.10 PANIC
 HARDWARE REQUIRED WHEN SERVING A A OR E OCCUPANCY WITH
 AN OCCUPANT LOAD OF 50 OR MORE.
  
 1C) MULTI-PURPOSE ROOM SHOWS A NEW EXIT DOOR, PLEASE
 PROVIDE THE MEANS OF EXITING TO THE PUBLIC WAY,
 (LANDING & SIDEWALK) FOR THIS NEW DOOR AND THE EXTERIOR
 DOOR IN THE CAFETERIA. FBC- B 1027.6 ACCESS TO THE
 PUBLIC WAY.
  
 1D) THE NEW EXIT DOOR IN THE MULTI-MEDIA ROOM WILL
 REQUIRE PRODUCT APPROVAL PER : 2010 FBC FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31)(A) EXTERIOR DOORS & (31)(B) WINDOWS.
  
 1E) 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 1F) 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 1F) (1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED
 IN ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 1F) (2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE
 7-10.
  
 1F) (3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 1F) (4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 1F) (5) COMPONENTS & CLADDING PRESSURES POSITVE &
 NEGATIVE TABLE 1609.2(2) .
  
 1G) THE PLANS INDICATE EXISTING KITCHEN, THE LAST KNOWN
 USE INDICATED THIS TO BE A BREAK ROOM. PLEASE PROVIDE
 WHAT TYPE OF COOKING EQUIPMENT IS LOCATED IN THIS ROOM?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) INFORMATION REQUIRED BY 2010 FBC-B NOT LOCATED ON
 PLANS:
 2A) 443.2.2 PLAYGROUND & EQUIPMENT.
  
 2B) 443.2.3 OUTDOOR WAST CONTAINERS.
  
 2C) 443.3.2 GLARE FROM NATURAL LIGHT. 443.3.7.5 GLARE
 ELIMINATION.
  
 2D) 443.3.3 AGE NOT PROVIDED FOR EDUCATIONAL OCCUPANCY
  
 2E) 443.3.4. AGE NOT PROVIDED FOR EDUCATIONAL
 OCCUPANCY.
  
 2F) 443.3.5.2 TEACHER TOLIETS
  
 2G) 443.3.5.5 WALLS IN KITCHENS, SCULLERY,AND CAN WASH
 AREAS ARE TO BE IMPERVIOUS TO A HEIGHT OF AT LEAST
 6'-0".
  
 2H) 443.3.5.6 FLOOR DRAINS AND HOSE BIBBS. GROUP TOLIET
 ROOMS.
  
 2I) 443.3.6.5 CHEMICAL STORAGE.
  
 2J) 443.3.7 (1-5) LIGHTING
  
 3) SHEET A2:
 3A) ON THE 2ND FLOOR THE EXISITNG EMERGENCY WINDOWS
 PLEASE PROVIDE OPENING SIZE OF WINDOWS. FBC-B 1029.4.1.
  
 3B) SHEET A2 & LS 2 INDICATE THE USE OF A AREA OF
 RESCUE ASSISTANCE AND THE TWO WAY COMMUNICATION WITHIN
 THE STAIRWWELL. NOTE THE COOMUNICATION DEVICE IS
 LOCATED BEHIND THE OCCUPANT IN THE WHEELCHAIR. ALSO
 NOTE THEIR IS NO CCOMMUNICATION DEVICE INDICATED ON THE
 FIRSTFLOOR NOR IS THERE ANY IDENTIFICATION ON THE
 EXTERIOR FIRST FLOOR THEIR IS A AREA OF RESCUE
 ASSISTANCE.
  
 3C) PLEASE PROVIDE A CUT SECTION THROUGH THE STAIRWELL
 WHERE THE NEW AREA OF RESCUE PLATFORM IS LOCATED,
 PROVIDE THE CLEARANCE FROM THE STAIR TREAD TO THE
 LEADING EDGE OF THE PLATFORM. 2010 FBC-B 1009.2.
  
 3D) PLEASE PROVIDE THE STRUCTURAL DETAILS HOW THE
 PLATFORM AND GAURD RAILS WILL MEET FBC-B TABLE 1607.1
 LIVE LOADS, & 1607.7.1, 1607.7.1.1 & 1607.7.1.2.
  
 4) PLEASE PROVIDE WHERE AND ADDITIONAL $15,000.00 WILL
 BE USED IN UPDATING THE BUILDING TO MEET TODAYS
 STANDARDS IN ACCESSIBILITY, PLEASE REVIEW 202.4 AND
 202.4.1 DISPROPORTIONATE COST.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-09-16 Cont ID  
Sent By dharvey Date 2013-09-16 Time 14:39 Rev Time 0.00
Received By dharvey Date 2013-09-16 Time 14:39 Sent To  
Notes
2013-09-16 14:41:02FIRST REVIEW = 9-16-13
  
 PLEASE COMPLY WITH FLORIDA ENERGY CODE SECTION 505
 PERTAINING TO LIGHTING CONTROLS FOR ALL ELECTRICAL WORK
 COMPLETED UNDER THIS PERMIT.
 VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-09-05 Cont ID  
Sent By wjolin Date 2013-09-05 Time 19:39 Rev Time 0.00
Received By wjolin Date 2013-09-05 Time 18:04 Sent To  
Notes
2013-09-05 19:39:255829 CORPORATE WAY
 PERMIT #13090021
 REVIEW COMMENTS - FIRE DEPARTMENT
 REFERENCE: NFPA 101 - CHAPTER 13 EXISTING ASSEMBLY &
 CHAPTER 15 EXISTING EDUCATIONAL OCCUPANCIES
  
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2009 EDITION WITH FLORIDA AMENDMENTS.)
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 THE BUILDING IS DESIGNED AND FUNCTIONING AS A MULTIUSE
 NON-SEPARATED OCCUPANCY (ASSEMBLY, EDUCATIONAL AND
 BUSINESS OCCUPANCIES) . FOR NON-SEPARATED MIXED USE
 OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE SAFETY
 REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO THE
 BUILDING. PER SECTION 6.1.14.1.2, WHERE EXIT ACCESS
 FROM AN OCCUPANCY TRAVERSES ANOTHER OCCUPANCY, THE
 MULTIPLE OCCUPANCY SHALL BE TREATED AS A MIXED
 OCCUPANCY. CURRENTLY THE TWO LARGE ASSEMBLY ROOMS
 (MULTIPURPOSE AND CAFETERIA) HAVE EGRESS THAT TRAVERSES
 ANOTHER OCCUPANCY. PER SECTION 13.3.4, PROVIDE
 SPEAKER/STROBE NOTIFICATION APPLIANCES AS ASSEMBLY
 OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING 300
 OCCUPANTS SHALL RECEIVE FIRE ALARM NOTIFICATION BY
 VISIBLE SIGNALS AND VOICE ANNOUNCEMENTS.
  
 PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE
 NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN
 THE BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 EXISTING ENTRANCE LOBBY DOORS NOT EQUIPPED WITH PANIC
 HARDWARE. INDICATE ALL DOORS (NEW AND EXISTING) TO BE
 EQUIPPED WITH PANIC/FIRE EXIT HARDWARE. FOR ASSEMBLY
 AND EDUCATIONAL OCCUPANCIES WITH AN OCCUPANT LOAD OF
 100 OR MORE PERSONS (50 PERSONS PER THE FLORIDA
 BUILDING CODE), PANIC HARDWARE SHALL BE PROVIDED ON
 DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR
 LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE
 PANIC HARDWARE.
  
 EXISTING EXTERIOR EXIT DOOR FROM CAFETERIA WILL NEED A
 RAMP OR SIDEWALK AS THE CURRENT EXIT DISCHARGE HAS A
 STEP DOWN TO PAVERS SPACED ABOUT 2 FEET APART LEADING
 TO THE PARKING LOT.
  
 NO EMERGENCY LIGHTING PROVIDED FOR SECOND FLOOR
 CORRIDOR ADJACENT TO WOMENS' RESTROOM.
  
 PROVIDE A FURNITURE AND SEATING PLAN.
  
 PLANS INDICATE A KITCHEN. INDICATE WHAT COOKING
 EQUIPMENT IS INTENDED AND THE COOKING OPERATIONS THAT
 WILL BE PERFORMED.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE
 AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 PER SECTION 8.3.5.1, PENETRATIONS THROUGH A FIRE-RATED
 WALL ASSEMBLY SHALL BE PROTECTED BY A FIRESTOP SYSTEM
 OR DEVICE.
  
 NO MECHANICAL PLANS SUBMITTED SHOWING FIRE DAMPERS.
  
 POST PERMANENT SIGNAGE IN THE STAIRS INDICATING "NO
 STORAGE PERMITTED BY ORDER OF THE FIRE MARSHAL."
  
 PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY
 RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING
 NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-16 Cont ID  
Sent By shill Date 2013-09-16 Time 17:38 Rev Time 0.00
Received By shill Date 2013-09-03 Time 17:45 Sent To  
Notes
2013-09-03 17:45:51C15

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-09-10 Cont ID  
Sent By jwitmer Date 2013-09-10 Time 16:39 Rev Time 0.00
Received By jwitmer Date 2013-09-10 Time 16:39 Sent To  
Notes
2013-09-10 16:39:42BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-09-16 Cont ID  
Sent By lwagner Date 2013-09-16 Time 13:56 Rev Time 0.00
Received By lwagner Date 2013-09-16 Time 13:30 Sent To  
Notes
***NONE***