| 2014-01-19 11:34:07 | BUILDING PLAN REVIEW |
| | PERMIT:13081230 |
| | ADD: 300 PALM BEACH LAKES |
| | CONT: DALL CONSRUCTION CO |
| | TEL: (305)458-8314 |
| | 2010 FLORIDA BUILDING CODE W |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: SUNDAY JAN. 19/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REQUEST, THIS BUILDING MEETS THE DEFINITION OF A |
| | THRESHOLD BUILDING. THRESHOLD INSPECTION PLAN FL S. S. |
| | 553.71(7) " THRESHOLD BUILDING" MEANING ANY BUILDING |
| | WHICH IS GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, |
| | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS |
| | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 |
| | SQ FT IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN |
| | 500 PERSONS. |
| | |
| | SUNDAY JAN 19/2014 E-MAILED CONTRACTOR DALL |
| | COSTRUCTION, CONTACT ADOLFO YANES: [email protected] |
| | THE GUIDELINES AND POLICIES FOR PROJECTS CONCERNING |
| | SPECIAL INSPECTORS AND RESIDENT INSPECTORS WITH THE |
| | CITY OF WEST PALM BEACH AMENDMENTS |
| | REVISED MARCH 2010 07:29 AM ALL REQUIRED FORMS ARE |
| | WITHIN THIS DOCUMENT FOR THE THRESHOLD AGREEMENT. |
| | |
| | 1A) 2ND REQUEST 109.3.6.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A SPECIAL INSPECTOR TO PERFORM STRUCTURAL |
| | INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A |
| | WRITTEN STRUCTURAL INSPECTION PLAN PREPARED BY THE |
| | ENGINEER OF RECORD. THE STRUCTURAL WRITTEN INSPECTION |
| | PLAN MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO |
| | THE ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION |
| | OF A THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| | INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| | PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| | ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| | DOCUMENTS. |
| | |
| | 1B) 2ND REQUEST, THRESHOLD INSPECTOR: WPB AMENDMENT |
| | 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| | REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE |
| | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT KEN |
| | CONRAD MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT |
| | (561)805-6666 FOR FURTHER INFORMATION AND FORMS BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 1C) 2ND REQUEST.THRESHOLD BLDG, REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 110.3.7.4.4 |
| | ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE |
| | SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| | ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE APPLICABLE FIRE-SAFETY |
| | STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| | |
| | 1D) 2ND REQUEST. A PLAN REVIEW STOP (THRESHOLD) WILL BE |
| | PUT ON THIS PROJECT UNTIL THESE ITEMS ARE COMPLETED AS |
| | REQUESTED BY THE CHIEF BUILDING INSPECTOR KEN CONRAD: |
| | PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 1E) 2ND REQUEST.THE CONTRACTOR WILL PRODUCE A JOB |
| | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS |
| | MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| | [email protected] |
| | |
| | 1F) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE |
| | PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS |
| | PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL |
| | CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL |
| | OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE |
| | RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED. |
| | UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED |
| | FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 1G) 2ND REQUEST, MISSING PLUMBING SHEETS P-3.1, P-4.1 & |
| | P-4.2. 109.3.6 THRESHOLD BUILDINGS, OPERATING |
| | GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT |
| | THE DESIGNER HAS REQUIRED ON THE PLANS OR |
| | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING |
| | PENETRATIONS, FOR WALLS AND CEILINGS. |
| | |
| | 1H) COMPLIED. THREE SETS OF PLANS AND PRODUCT TESTING |
| | REPORTS WILL BE REQUIRED, SINCE THIS IS A THRESHOLD |
| | BUILDING. |
| | |
| | 2) SHEET A0.0 PROJECT DATA: |
| | |
| | 2A) COMPLIED. PLEASE PROVIDE YOUR MINIMUM BUILDING |
| | DESIGN NOT OR IA OR IB. 2010 FBC-B TABLE 503. |
| | |
| | 2B 2ND REQUEST, THE RESPONCE SHEET INDICATES THIS WILL |
| | BE CONSIDERED ONE BUILDING BUT UNDER THE HEADING |
| | PROJECT DESCRIPTION THE SCOPE OF WORK TO BE COMPLETED |
| | IS ON (2) FIVE STORY BUILDINGS. |
| | ORIGINAL COMMENT. PLEASE CLARIFY IF THIS PERMIT IS FOR |
| | ONE BUILDING WITH 2 WINGS OR IF THIS PERIMIT IS TO BE |
| | FOR 2 BUILDINGS WITH A CONNECTING CORRIDOR. UNDER THE |
| | HEADING PROJECT DESCRIPTION IT IS LISTED AS (2) 5 STORY |
| | BUILDINGS. PLEASE NOTE THE HISTORIC BUILDING OR WING IS |
| | THE EST ONE THAT HAS TWO VERTICAL EXITS. THE WEST |
| | BUILDING OR WING ONLY HAS ONE VERTICAL EXIT. THE OTHER |
| | ISSUE THAT NEEDS TO BE REVIEWED, IS FBC-B 503.1.2 |
| | TWO BUILDINGS ON THE SAME LOT. IF THIS IS TO BE |
| | CONSIDERED ONE BUILDING THERE ARE NO FIRE SEPERATION |
| | ISSUES. IF THE DESIGN IS INTENDED TO BE TWO BUILDINGS |
| | WITH A CONNECTING CORRIDOR, SKY BRIDGE ETC.. THEN AN |
| | ASSUMED PROPERTY LINE HAS TO BE ASSIGNED AND BUILDING |
| | OPENINGS TO BE REVIEWED. |
| | |
| | 2C) 2ND REQUEST. ORIGINAL COMMENT: THE EAST WING OR |
| | BUILDING IS LISTED AS A 5 STORY BUILDING, THE ROOF TOP |
| | IS INDICATED TO BE USED AS A ROOFTOP DECK WITH ROOF |
| | TRELLIS ABOVE, PLEASE REVIEW 2010 FBC-B 1509.2.3 |
| | PENTHOUSES OR BULKHEADS USED FOR PURPOSES OTHER THAN |
| | PERMITTED BY THIS SECTION SHALL CONFORM TO THE |
| | REQUIREMENTS OF THIS CODE FOR AN ADDITIONAL STORY OR A |
| | 6 STORY BUILDING. |
| | 1/19/2014 THE 2010 FBC-B DOES NOT HAVE A CODE |
| | COMMENTARY BUT THE 2007 FBC-B DOES, AND ON THIS CODE |
| | ISSUE THE COMMENTARY STATES: IF THE AREA EXCEEDS 1/3RD |
| | OF THE ROOF AREA, REGARDLESS OF HEIGHT THEN THE |
| | PENTHOUSE MUST BE CONSIDERED A STORY. REGARDLESS OF |
| | HEIGHT OR AREA, ROOF STRUCTURES USED FOR ANYTHING |
| | EXCEPT SHELTERING MECHANICAL EQUIPMRNT OR VERTICAL |
| | SHAFT OPENINGS MUST BE CONSIDERD AS AN ADDITIONAL |
| | STORY. |
| | |
| | 2D) 2ND REQUEST, SEMI-COMPLIED. THE DESIGNER OF RECORD |
| | HAS ELECTED TO USE THE COMPLIANCE METHOD LISTED IN |
| | 1105.2. BUT HAS NOT INDICATED WHICH OF THE OPTIONS: |
| | 2010 FL EXST BLDG CODE CHAPTER 11 HISTORIC 1105.2 |
| | COMPLIANCE OPTION. |
| | LIFE SAFETY AND PROPERTY CONSERVATION SHALL BE PROVIDED |
| | IN ACCORDANCE WITH ONE OF THE FOLLOWING OPTIONS: |
| | OPTIONS: |
| | 1. PRESCRIPTIVE-BASED PROVISIONS OF THIS CODE. |
| | |
| | 2. COMPLIANCE ALTERNATIVE-BASED PROVISIONS OF THIS |
| | CODE. |
| | |
| | 3. PERFORMANCE-BASED PROVISIONS OF NFPA 914, CODE FOR |
| | FIRE PROTECTION OF HISTORIC STRUCTURES, CHAPTER 6, |
| | ALONG WITH A STRUCTURAL EVALUATION AS SPECIFIED IN |
| | SECTION 1301.4.1 OF THIS CODE. |
| | |
| | ORIGINAL COMMENT: FOR HISTORIC BUILDINGS THERE ARE |
| | VARIOUS METHODS OF ACHIEVING CODE COMPLIANCE, 2010 |
| | EXISITNG BUILDING CODE CHAPTER 11, PLEASE PICK ONE: |
| | 1105.1 STRICT COMPLIANCE. |
| | 1105.2 COMPLIANCE OPTION |
| | 1105.3 CONDITIONS SPECIFIC TO COMPLIANCE OPTIONS 2 & 3. |
| | ALSO SEE 1104.1 EQUIVALENCY. |
| | |
| | 2E) COMPLIED. THE BUILDING IS BEING DECLARED AS A LEVEL |
| | 3 ALTERATION. THE 2010 FL EXISTING BUILDING CODE804.1. |
| | AUTOMATIC SPRINKLER SYSTEMS SHALL BE PROVIDED IN ALL |
| | WORK AREAS IN ACCORDANCE WITH THE FLORIDA BUILDING |
| | CODE, BUILDING. FBC-B [F] 903.2.11.3 BUILDINGS THREE |
| | STORIES OR MORE IN HEIGHT. ANY BUILDING WHICH IS OF |
| | THREE STORIES OR MORE IN HEIGHT SHALL BE EQUIPPED WITH |
| | AN APPROVED AUTOMATIC SPRINKLER SYSTEM INSTALLED IN |
| | ACCORDANCE WITH SECTION 903.1. |
| | |
| | 3) SHEET A.01 INDEX: |
| | |
| | 3A) COMPLIED. MISSING LIFE-SAFETY SHEETS. WEST PALM |
| | BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| | 1, ADMINISTRTION, 2010 EDITION 107.3.5.1.1 |
| | COMMERCIAL BUILDINGS 7. |
| | |
| | 3B) COMPLIED. TYPO INDEX INDICATES A A2.11 MISSING BUT |
| | LABLEED A2.12. |
| | |
| | ------------NEW COMMENTS-------------- |
| | |
| | 3C) MISSING OR NOT IDENTIED AS SHEETS ARE IDENTIFIED |
| | CIVIL PLANS |
| | |
| | 3D) MISSING P3.3, P4.1 & P4.2 |
| | |
| | 3E) MISSING FP3.1 & FP 3.2. |
| | |
| | 4) A1.0 SITE PLAN: |
| | 4A) COMPLIED. POOL AND POOL DECK WILL REQUIRE A |
| | SEPERATE PERMIT. , NOTE ALDO COMPLIANCE WITH EFFECTIVE |
| | BARRIER A 48 " HIGH FENCE SEPERATING THE POOL AREA |
| | FROM TTHE REMAINDER OF THE BUILDING. FBC-B 424.1.3.1.9. |
| | |
| | 4B) COMPLIED. UNKNOWN AREA, ARROWS PONTING AT BUT NO |
| | NOMENCLATURE, SEE SHEET A2.0 BETWWEN GRID LINES AB & AC |
| | AND ABOVE A1? 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 4C)2ND REQUEST. THERE ARE NO ELEVATIONS PROVIDED FOR |
| | THE GARAGE FLOOR ON SHEET A1.0 THE SITE PLAN. CHANGE IN |
| | GRADE IS GIVEN FOR LOBBY BUT NOT FOR THE GARAGE TO THE |
| | PARKING LOBBY ENTRANCE NOR FROM THE PARKING GARAGE |
| | ENTRY TO THE SOUTH PARKING LOT. SHEET PD1 DOES SHOW |
| | ELEVATIONS FOR CHANGE IN GRADE, THESE WILL BE USED FOR |
| | THIS REVIEW,SHEET A1.0 SHOWS THIS AS NEW WORK AND WOULD |
| | NEED TO COMPLY WITH 2010 EXISTING BUILDING CODE LEVEL |
| | II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | 107.2.1.3 ADDITIONAL INFORMATION REQUIRED, PLEASE SEE |
| | FBC-B 1003.5. |
| | ---------NEW COMMENTS---------- |
| | 4C) ASSUMPTION SINCE THE A1.0 SHEET DOES NOT PROVIDE |
| | WHAT THE FINISH FLOOR IS FROM NGVD, THE PARKING LOBBY |
| | TO BE ASSUMED TO BE AT 13.00' NGVD. THIS REVIEW IS |
| | BASED ON THIS ASSUMPTION. THERE ALSO APPEARS TO BE |
| | DISCREPANCIES BETWEEN PD-1 AND ASSUMED ELEVATION ON |
| | A-1.0. PD-1 INDICATES THE INTERIOR 1ST FLOOR AT |
| | ELEVATION 13.00' WHEREAS A-1.0 HAS A 1'-0" DROP IN |
| | ELEVATION THE EAST MAIN ENTRY WOULD BE AT ELEVAION |
| | 12'-0" WHERE AS PD-1 ARE AT 12.70 AND SLOPE DOWN TO |
| | 12.32 AND THEN DOWN TO 11.98, PLEASE PROVIDE |
| | INFORMATION ON THIS WHOLE DESIGN. COORDINATE DRAWING |
| | ELEVATIONS. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED FOR THIS AREA. |
| | |
| | 4C)(1A) THE MEANS OF EGRESS TRAVEL FROM THE LOBBY TO |
| | THE RAMP THAT LEADS INTO THE GARAGE THE AREA WHERE THE |
| | CHANGE IN DIRECTION OCCURS, |
| | PART OF THIS AREA STILL HAS SLOPE (RAMP 1 1/2 INCHES) |
| | AND THE OTHER HALF IS CONSIDERED A LANDING ONLY 4'-0" |
| | WIDE. |
| | 2010 FBC-B 1010.2 SLOPE. |
| | RAMPS USED AS PART OF A MEANS OF EGRESS SHALL HAVE A |
| | RUNNING SLOPE NOT STEEPER THAN ONE UNIT VERTICAL IN 12 |
| | UNITS HORIZONTAL (8.333-PERCENT SLOPE). THE SLOPE OF |
| | OTHER PEDESTRIAN RAMPS SHALL NOT BE STEEPER THAN ONE |
| | UNIT VERTICAL IN EIGHT UNITS HORIZONTAL (12.5-PERCENT |
| | SLOPE). |
| | |
| | 4C)(1B) 2010 FBC-B 1010.6.4 1010.6.4 CHANGE IN |
| | DIRECTION. WHERE CHANGES IN DIRECTION OF TRAVEL OCCUR |
| | AT LANDINGS PROVIDED BETWEEN RAMP RUNS, THE LANDING |
| | SHALL BE 60 INCHES BY 60 INCHES (1524 MM BY 1524 MM) |
| | MINIMUM. |
| | |
| | 4C)(1C) WITHIN THE PARKING GARAGE FROM THE ACCESSIBLE |
| | PARKING SPACE TO THE RAMP THERE IS NO DEMARKATION THAT |
| | IS PART OF AN ACCESSIBLE ROUTE AND NO PARKING SHOULD |
| | OCCUR THERE 2010 FBC-B 1005.1. |
| | |
| | 4D) THERE ARE SIMILAR CIRCUMSTANCES FOR THE RAMP THAT |
| | LEADS FROM THE STAIRS LABELED # 112 TO THE SOUTH |
| | PARKING LOT. |
| | |
| | 4E) THE NORTH SIDE OF THE LOT THERE IS A UTILITY VAULT |
| | WITH NEW 8'-0" GATES THAT SWING OVER THE PROPERTY LINE. |
| | 2010 FBC-B 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8 |
| | FEET IN HEIGHT. ENCROACHMENTS INTO THE PUBLIC |
| | RIGHT-OF-WAY ABOVE GRADE AND BELOW 8 FEET (2438 MM) IN |
| | HEIGHT SHALL BE PROHIBITED EXCEPT AS PROVIDED FOR IN |
| | SECTIONS 3202.2.1 THROUGH 3202.2.3. DOORS AND WINDOWS |
| | SHALL NOT OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY. |
| | |
| | 5) SHEET A2.0A: COMMON SATEMENT TO ALL FLOORS!!! |
| | |
| | 5A)SEMI-COMPLIED. WALL IDENTIFICATION TAGS MISSING, |
| | IDENTIFYING WALL CONSTRUCTION TYPES, FIRE BARRIERS, |
| | SHAFT ENCLOSURES AND TENANT SEPERATION WALLS. |
| | COMPLIED. 2 HOUR SHAFT WALLS FOR ENCLOSED STAIRS AND |
| | SHAFTS. FBC-B 708.2. NO SHAFTS ARE LABELED AS SUCH. |
| | NON-COMPLIANCE 2 HOUR SHAFT WALL CONSTRUCTION FOR TRASH |
| | CHUTE CONSTRUCTION FBC-B 708.13.1 PROVIDE A SECTION |
| | THROUGH THE ROOM, TRASH CHUTE AND 2 HOUR WALL, |
| | SEE FBC-B 903.2.11.2. RUBBISH CHUTES |
| | COMPLIED. 2 HR ELEVATOR MACHINE ROOM FBC-B 3006.4. |
| | COMPLIED. 1 HR TENANT SEPERATION WALLS FBC-B 709.1. |
| | NON-COMPLIANCE 1 HR TERMINATION ROOM FOR TRASH CHUTE |
| | FBC-B 708.13.4. & OPENING PROTECTIVES IN ACCORDANCE |
| | WITH FBC-B TABLE 715.4 NOTE MECHANICAL SHOW |
| | EAST TERMINATION ROOM WITH FULL LOUVERED DOOR |
| | 1 HR REFUGE CHUTE ACCESS ROOMS FBC-B 708.13.3. & |
| | OPENING PROTECTIVES IN ACCORDANCE WITH FBC-B TABLE |
| | 715.4 |
| | |
| | COMPLIED. TABLE FBC-B TABLE 508.4 SPRINKLERED BUSINESS |
| | OCC OR ASSEMBLY VERSES R2 OCCUPANCY, 2 HOUR. |
| | FIRE PUMP ROOM (IF PROVIDED, NOT A HIGH-RISE) 2 HRS. |
| | FBC-B 913.2.1 |
| | GENERATOR ROOM 2 HR WALLS (IFPROVIDED, NOT A HIGH-RISE) |
| | NFPA 20:5.1.2.1.1. |
| | |
| | 5B) DOORS ARE IDENTIFIED, THE DOOR SCHEDULE FOUND ON |
| | SHEET A7.0 DOORS MISSING FIRE RATINGS, DOORS LISTED IN |
| | WALLS TYPES ABOVE WILL NEED OPENING PROTECTION IN |
| | ACCORDANCE WITH FBC-B TABLE 715.4. |
| | MOST ARE COMMON TO ALL FLOORS: |
| | 5B)(1)DOOR 1-003 N.E. STAIR DOOR WITHIN 10'-0" WILL |
| | NEED TO COMPLY WITH 2010 FBC-B 1022.6 THIS WILL ALSO |
| | NEED TO DEAL WITH WINDOW OPENINGS ON ALL FLOORS WITHIN |
| | THE STAIRWELL. |
| | |
| | 5B)(2) 1005 EXTERIOR DOOR TO TRASH ROOM & 1009 EXTERIOR |
| | DOOR WEST TRASH ROOM TO COMPLY WITH 1 HR REFUGE CHUTE |
| | ACCESS ROOMS FBC-B 708.13.3. & OPENING PROTECTIVES IN |
| | ACCORDANCE WITH FBC-B TABLE 715.4 |
| | |
| | 5B)(3) DOOR # 1007 WEST STAIRWELL 2 HR RATED ENCLOSURE, |
| | 1 1/2 HR OPENING PROTECTIVE TABLE 715.4. |
| | |
| | 5B)(4) DOOR # 1008 MAIN ELECTRIC ROOM IF DOOR IS OVER |
| | 600 VOLT NFPA 13.8.14.10 |
| | |
| | 5B)(5) DOOR # 1-022 UNIT G ENTRY DOOR TABLE 715.4 |
| | OPENING PROTECTIVES TENANT SEPERATION WALL. |
| | |
| | 5B)6) S.E. STAIR, EXTERIOR STAIRWAY. 1026.6 EXTERIOR |
| | STAIR PROTECTION 1 HR. COMMON TO ALL FLOORS. |
| | |
| | 5B)(7) S.E. EXTERIOR STRAIR, CLARIFICATION IS REQUIRED. |
| | IT APPEARS THERE IS A WINDOW TO BE FILLED IN ON ALL |
| | FLOOR BUT NO NOMENCLATURE IS PROVIDED, AGAIN IF THIS IS |
| | TO BE A OPENING THEN COMPLIANCE WITH 2010 FBC-B 1026.6 |
| | WILL BE REQUIRED. |
| | |
| | 5C) 2ND REQUEST. PLEASE PROVIDE HANDRAILS AT THE |
| | WALL-LINE NONE ARE PROVIDED. LOBBY HANDRAIL PROVIDE THE |
| | DISTANCE BETWEEN WALLS AND HANDRAILS, FBC-B 1012.9 |
| | INTERMEDIATE HANDRAILS, RAMPS AND STAIRS AT WALL LINE |
| | DO NOT INDICATE THE USE OF HANDRAILS FBC-B 1009.12 & |
| | 1010.8. |
| | |
| | 5D) COMPLIED. LOBBY STAIR, PLEASE REVIEW FBC-B 1003.5 |
| | EXCEPTION # 2 AND STIAR TREAD OF 13 INCHES. |
| | |
| | 5E) COMPLIED. WALLS BETWEEN COMMON AREAS, CORRIDORS AND |
| | TENANT WALLS WILL ALSO NEED DOCUMENTATION THEY MEET |
| | SECTION FBC-B 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION |
| | ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| | CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| | EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR |
| | OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. |
| | THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT |
| | ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| | FITTING TO THE FRAME AND SILL. |
| | |
| | 5F) 2ND REQUEST. PLEASE CONFIRM THE ELEVATOR LOCATED IN |
| | GRID LINES B4 & BD IS NEW CONSTRUCTION, THE STRUCTURAL |
| | SHEETS SHOW WORK IN THIS AREA ON ALL FLOORS, IF SO |
| | PLEASE ALSO REVIEW 3002.4 ELEVATOR AMBULANCE STRETCHER |
| | REQUIREMENTS. SHEET A5.1 DETAIL #6 INDICATES THE CABIN |
| | TO BE A 6'-8" X 4'-3" PLEASE PROVIDE THE MANUFACTURERS |
| | SPEC THAT IT MEETS THE REQUIREMENTS FOR AMBULANCE |
| | STRETCHER REQUIREMENTS, IT APPEARS TO NOT BE ABLE TO |
| | GET THE STRETHER IN WITHOUT HITTING THE BACK WALLS AND |
| | RUNNING OUT OF ROOMK. |
| | |
| | 6) SHEET A2.1A, COMMON NOTE FOR ALL FLOORS: |
| | |
| | 6A) 2ND REQUEST, PROVIDE DOCUMENTATION THAT THE SOUND |
| | REQUIREMENTS ARE MET. PLEASE PROVIDE COMPLIANCE WITH: |
| | FBC-B 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING |
| | ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING |
| | UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE |
| | SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF |
| | NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 492. |
| | |
| | 6B) 2ND REQUEST. FBC-B 603.1 ALLOWABLE MATERIALS. |
| | COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS |
| | OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING |
| | APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1 |
| | THROUGH 603.1.3: |
| | EXCEPTIONS: |
| | 1. FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF |
| | NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING |
| | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 100. |
| | 2. FLOOR INSULATION INSTALLED BETWEEN A FINISHED FLOOR |
| | AND SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE |
| | ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| | 200. |
| | |
| | 6C) COMPLIED. THE 2 STORY UNITS DO NOT PROVIDE DETAILS |
| | OF THE NEW INTERIOR STAIRS AS TO LIVE LOADS, TABLE |
| | 1607.1 OR COMPLIANCE WITH 1009.6 STAIRWAY CONSTRUCTION. |
| | ALL STAIRWAYS SHALL BE BUILT OF MATERIALS CONSISTENT |
| | WITH THE TYPES PERMITTED FOR THE TYPE OF CONSTRUCTION |
| | OF THE BUILDING, EXCEPT THAT WOOD HANDRAILS SHALL BE |
| | PERMITTED FOR ALL TYPES OF CONSTRUCTION. |
| | |
| | 6D) L. DETAIL A2-4.1 CUT THROUGH SECTION NO DETAILS FOR |
| | GAURDRAIL ON BALCONY. TO COMPLY WITH FBC-B SECTION |
| | 1013., 1607.7.1, 1607.7.1.1 & 1607.7.1.2. |
| | |
| | 7) 2ND REQUEST. SHEET A2.5 ROOF DECK: |
| | 7A) 1/19/2014 THE 2010 FBC-B DOES NOT HAVE A CODE |
| | COMMENTARY BUT THE 2007 FBC-B DOES, AND ON THIS CODE |
| | ISSUE THE COMMENTARY STATES: IF THE AREA EXCEEDS 1/3RD |
| | OF THE ROOF AREA, REGARDLESS OF HEIGHT THEN THE |
| | PENTHOUSE MUST BE CONSIDERED A STORY. REGARDLESS OF |
| | HEIGHT OR AREA, ROOF STRUCTURES USED FOR ANYTHING |
| | EXCEPT SHELTERING MECHANICAL EQUIPMRNT OR VERTICAL |
| | SHAFT OPENINGS MUST BE CONSIDERD AS AN ADDITIONAL |
| | STORY. |
| | |
| | ORIGINAL COMMENT, THE ROOF DECK IS BEING USED FOR MORE |
| | THAN A ROOF DECK, THE USEAGE OF THIS AREA MAKES THE |
| | ROOF DECK A 6TH FLOOR, SEE FBC-B 1509.2.3 USE |
| | LIMITATIONS. PENTHOUSES OR BULKHEADS USED FOR PURPOSES |
| | OTHER THAN PERMITTED BY THIS SECTION SHALL CONFORM TO |
| | THE REQUIREMENTS OF THIS CODE FOR AN ADDITIONAL STORY. |
| | THE RESTRICTIONS OF THIS SECTION SHALL NOT PROHIBIT THE |
| | PLACING OF WOOD FLAGPOLES OR SIMILAR STRUCTURES ON THE |
| | ROOF OF ANY BUILDING. |
| | |
| | 7B) 2ND REQUEST, FBC-B 1509.2.4 TYPE OF CONSTRUCTION. |
| | PENTHOUSES SHALL BE CONSTRUCTED WITH WALLS, FLOORS AND |
| | ROOF AS REQUIRED FOR THE BUILDING. |
| | |
| | 7C) 2ND REQUEST. THERE ARE TWO ISSUES AT HAND WITH THE |
| | ROOF DECK OCCUPANCY: |
| | 7C)(1) THIS PLAN INDICATES ONLY ONE MEANS OF EGRESS, |
| | PLEASE REVIEW FBC-B TABLE 1021.2 STORIES WITH ONE EXIT. |
| | THE ROOF DECK IS THE 6TH STORY, TABLE 1021.2 ONLY |
| | ALLOWS ONE EXIT LIMITED TO R2 OCCUPANCY, 3 STORIES, 4 |
| | DWELLING UNITS AND 50 FEET OR LESS TRAVEL DISTANCE. |
| | |
| | 7C)(2) PROVIDE THE SQUARE FOOTAGE OF USABLE ROOF DECK, |
| | AND PROVIDE A OCCUPANT LOAD BASED ON TABLE 1004.1.1. |
| | |
| | 8) SHEET A-5.0: |
| | 8A) 2ND REQUEST. EYEBROW SUNSHADE BY DORALCO OR |
| | APPROVED EQUAL. WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | EDITION 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | SUCH INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL |
| | CODES. PROVIDE MANUFACTURERS SPECIFICATION. SHALL NOT |
| | BE CITED AS A WHOLE OR IN PART, NOR SHALL THE TERM |
| | "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR |
| | SPECIFIC INFORMATION... |
| | |
| | 8B)COMPLIED. UNDER SEPERATE PERMIT. DETAIL # 2 POOL |
| | RETAINING WALL INDICATES A POOLPAVER DECK BUT THE |
| | SUB-BASE IS NOT PROVIDED, 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED, TO BE UNDER SEPERATE PERMIT. |
| | |
| | 8C) COMPLIED. DETAIL # 3 FIRE STOPPING MATERIALS AS |
| | REQUIRED FOR FIRE RATING, WEST PALM BEACH AMENDMENTS TO |
| | THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, |
| | 2010 EDITION 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC, AND THE |
| | TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN |
| | PART, NOR SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE |
| | USED AS A SUBSTITUTE FOR SPECIFIC INFORMATION... |
| | |
| | 8D) COMPLIED.DETAIL #4, INDICATES WINDOWS BY E. S. |
| | WINDOWS OR EQUAL, WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 |
| | EDITION 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | SUCH INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL |
| | CODES SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR |
| | SHALL THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A |
| | SUBSTITUTE FOR SPECIFIC INFORMATION... |
| | |
| | 9) 2ND REQUEST. PLEASE PROVIDE A WIND ANYLSIS FOR THE |
| | 45 DEGREE SECTORS FOR THE NORTH EAST AND SOUTH EAST: |
| | 2010 FBC-B 1609.4.1 WIND DIRECTIONS AND SECTORS. |
| | FOR EACH SELECTED WIND DIRECTION AT WHICH THE WIND |
| | LOADS ARE TO BE EVALUATED, THE EXPOSURE OF THE BUILDING |
| | OR STRUCTURE SHALL BE DETERMINED FOR THE TWO UPWIND |
| | SECTORS EXTENDING 45 DEGREES (0.79 RAD) EITHER SIDE OF |
| | THE SELECTED WIND DIRECTION. THE EXPOSURES IN THESE TWO |
| | SECTORS SHALL BE DETERMINED IN ACCORDANCE WITH SECTIONS |
| | 1609.4.2 AND 1609.4.3 AND THE EXPOSURE RESULTING IN THE |
| | HIGHEST WIND LOADS SHALL BE USED TO REPRESENT WINDS |
| | FROM THAT DIRECTION. |
| | |
| | 2010 FBC-B 1609.4.2 SURFACE ROUGHNESS CATEGORIES. |
| | A GROUND SURFACE ROUGHNESS WITHIN EACH 45-DEGREE (0.79 |
| | RAD) SECTOR SHALL BE DETERMINED FOR A DISTANCE UPWIND |
| | OF THE SITE AS DEFINED IN SECTION 1609.4.3 FROM THE |
| | CATEGORIES DEFINED BELOW, FOR THE PURPOSE OF ASSIGNING |
| | AN EXPOSURE CATEGORY AS DEFINED IN SECTION 1609.4.3. |
| | |
| | ORIGINAL COMMENT: SHEET S-1.0 WIND DESIGN IS INDICATED |
| | TO BE A EXPOSURE C, PLEASE SEE FBC-B 1609.4 EXPOSURE |
| | CATEGORY.EXPOSURE D. EXPOSURE D SHALL APPLY WHERE THE |
| | GROUND SURFACE ROUGHNESS, AS DEFINED BY SURFACE |
| | ROUGHNESS D, PREVAILS IN THE UPWIND DIRECTION FOR A |
| | DISTANCE OF AT LEAST 5,000 FEET (1524 M) OR 20 TIMES |
| | THE HEIGHT OF THE BUILDING, WHICHEVER IS GREATER. |
| | EXPOSURE D SHALL EXTEND INLAND FROM THE SHORELINE FOR A |
| | DISTANCE OF 600 FEET (183 M) OR 20 TIMES THE HEIGHT OF |
| | THE BUILDING, WHICHEVER IS GREATER FROM AN EXPOSURE D |
| | CONDITION AS DEFINED IN THE PREVIOUS SENTENCE. |
| | |
| | 10)2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 11) 2ND REQUEST. A DESCRIPTION IS NOT THE PRODUCT |
| | APPROVAL AND THE REQUIRED TECHNICAL SHEETS. IF MORE |
| | THAN ONE PRODUCT IS IDENTIFIED IN THE PRODUCT APPROVAL |
| | CIRCLE THE PRODUCT TO BE INSTALLED SIZE LIMITATIONS AND |
| | PRESSURES THAT THE UNIT WAS TESTED FOR. |
| | |
| | 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| | COMPONENTS & CLADDING |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | . |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |