| 2013-09-11 11:47:12 | 2010 FBC |
| | |
| | 1) THE PERMIT APPLICATION INDICATES THE ADDITION IS TO |
| | BE STORAGE AND THE PLANS DO NOT SPECIFY THE ROOM USE. |
| | BASED ON THE PLANS THAT WERE SUBMITTED THE ADDITION |
| | APPEARS TO BE A BEDROOM OR COULD BE USED AS A BEDROOM |
| | BY AN OWNER IN THE FUTURE. PLEASE CLARIFY BY LABELING |
| | THE ROOM ON THE PLANS. |
| | |
| | 2) THE PLANS SPECIFY THAT THE SPACE WILL BE |
| | CONDITIONED. SUBMIT TWO COPIES OF ENERGY CALCULATIONS |
| | FOR THE BUILDING. FBC ENERGY CONSERVATION SECTIONS |
| | 101.4.3 , 101.4.5 |
| | |
| | 3) SHOW COMPLIANCE WITH FBCR 318 FOR TERMITE |
| | PROTECTION. |
| | |
| | 4) FBC R403.1.4 REQUIRES ALL EXTERIOR FOOTINGS TO BE |
| | PLACED AT LEAST 12 INCHES BELOW GRADE AND FBC R317.1 |
| | (5) REQUIRES PROTECTION OF WOOD AND WOOD PRODUCTS FROM |
| | DECAY FOR WALL FRAMING AND SHEATHING AT THE EXTERIOR OF |
| | A BUILDING HAVING A CLEARANCE OF LESS THAN 6" FROM THE |
| | GROUND. THE 16" DEEP FOOTING SPECIFIED ON THE PLANS |
| | WILL ONLY PROVIDE 4" FROM THE GROUND. SPECIFY HOW THIS |
| | REQUIREMENT WILL BE ADDRESSED. |
| | |
| | 5) SHOW COMPLIANCE WITH FBCR 318.6 WHICH REQUIRES |
| | GUTTERS AND DOWNSPOUTS AT THE REAR OF THE STRUCTURE |
| | WITH NO EAVE PROJECTION WHERE THE RAIN WATER FROM THE |
| | ROOF IS DISCHARGED. |
| | |
| | 6) SHOW COMPLIANCE WITH FBCR 806 FOR REQUIRED ATTIC |
| | VENTILATION. |
| | |
| | 7) PROVIDE A STRUCTURAL DETAIL SHOWING HOW THE 4 X 10 |
| | WOOD BEAM AT THE COVERED PORCH IS TO BE NOTCHED INTO |
| | THE CORNERS AT EACH END (INCLUDING THE EXISTING |
| | CORNER). SPECIFY THE NUMBER OF FRAMING MEMBERS REQUIRED |
| | FOR BEARING AND THE REQUIRED STRAPS AND CONNECTORS FOR |
| | UPLIFT AND LATERAL FORCES. FBC R301.1 |
| | |
| | 8) PLEASE CLARIFY IF THE (3) #5 BARS IN THE FOOTING ARE |
| | TO BE DOWELED INTO THE EXISTING FOOTING. FBC R301.1 |
| | |
| | 9) PROVIDE A STRUCTURAL DETAIL OF THE PARAPET |
| | CONSTRUCTION. SHOW ALL CONNECTORS REQUIRED TO ACHIEVE A |
| | CONTINUOUS LOAD PATH. FBC R301.1 |
| | |
| | 10) PRODUCT APPROVALS REQUIRED BY DCA RULE 9N-3 ARE |
| | REQUIRED TO BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD FOR THE PROJECT. CITY AMENDMENTS 10 |
| | |
| | 11) SUBMIT (2) COPIES OF PRODUCT APPROVALS FOR THE NEW |
| | EXTERIOR DOOR, THE ROOF TILE AND THE SIMPSON CONNECTORS |
| | AS REQUIRED BY DCA RULE 9N-3. |
| | |
| | 12) SPECIFY WHICH METHOD OF ATTACHMENT LISTED IN THE |
| | ROOF TILE PRODUCT APPROVAL WILL BE USED TO INSTALL IT. |
| | IF AN ADHESIVE IS USED, SUBMIT TWO COPIES OF THE |
| | PRODUCT APPROVAL. FBC R905.1 |
| | |
| | 13) SPECIFY THE APPROVED ASSEMBLY, INSULATION TYPE, |
| | FASTENING OPTION AND MAXIMUM DESIGN PRESSURE FROM THE |
| | MULE- HIDE ROOFING PRODUCT APPROVAL (NOA # 12-0815.09) |
| | THAT WILL BE USED. IF ENHANCED FASTENING OF THE BASE |
| | SHEET IS REQUIRED TO MEET THE UPLIFT PRESSURE |
| | REQUIREMENTS OF THE PERIMETER AND CORNER ROOF AREAS |
| | SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 |
| | CALCULATIONS IN ACCORDANCE WITH LIMITATION #7 ON PAGE |
| | 25 OF THE NOA. FBC R905.1 |
| | |
| | 14) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW THE |
| | REVIEW COMMENTS HAVE BEEN ADDRESSED. THIS WILL AID IN |
| | SPEEDING REVIEW TIMES. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |