Plan Review Details - Permit 13081127
Plan Review Stops For Permit 13081127
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-09-09 Cont ID  
Sent By dharvey Date 2013-09-09 Time 13:33 Rev Time 0.00
Received By dharvey Date 2013-09-09 Time 13:10 Sent To  
Notes
2013-09-09 13:26:01PROVIDE RISER DIAGRAM/ONE LINE DRAWING SHOWING
 ELECTRICAL EQUIPMENT
 INDICATE LOADS PER NEC 210 AND 220
 PROVIDE MOTOR CALCULATIONS PER NEC 430, INCLUDING
 DISCONNECTS PER 430.102
 PROVIDE OVERLOAD PROTECTION OR INDICATE IF MOTOR IS
 INTERNALLY OVERLOAD PROTECTED 430.32
 PROVIDE RATING OF MOTOR AND DRIVEN MACHINERY TO ENSURE
 COMPATIBILITY
 EDISON BASE FUSES ARE FOR REPLACEMENT ONLY - 240.51

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-09 Cont ID  
Sent By dharvey Date 2013-09-09 Time 13:36 Rev Time 0.00
Received By dharvey Date 2013-08-28 Time 15:57 Sent To  
Notes
2013-09-09 13:42:28PLACED IN DENIED UNDER "L" DH
2013-08-28 15:57:57ROUTED TO ELECTRIC UNDER $5000