Plan Review Details - Permit 13081093
| Plan Review Stops For Permit 13081093 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2013-11-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-11-05 |
Time |
12:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-11-05 |
Time |
12:07 |
Sent To |
|
|
| Notes |
| 2013-11-05 12:09:15 | LACK OF CERTIFICATE OF AUTHORIZATION NOTED; WILL | | | RESOLVE ISSUE DIRECTLY WITH ENGINEER/FBPE | | | ALI ABOLHASSANI, PE 64212/STRUCTURAL CONCEPTS | | | ENGINEERING | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2013-10-31 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2013-10-31 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2013-10-31 |
Time |
15:22 |
Sent To |
I |
|
| Notes |
| 2013-10-31 15:24:41 | PERMIT #13081093 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | ****PROVISO******* | | | | | | A PLACARD NEEDS TO BE ATTACHED TO SPRINKLER RISER | | | INDICATING THE TYPE OF EXTINGUISHING SYSTEM (ESFR) AND | | | THE RELEVANT DATE THAT PERTAINS TO THIS DESIGNATION. | | | | | | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING | | | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A | | | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN | | | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE | | | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST | | | BE SUBMITTED BY EMAIL ([email protected]) | | | ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND | | | APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT | | | 500 NORTH DIXIE HIGHWAY. | | | | | | | | | SUE ELLEN CALDERON | | | FIRE INSPECTOR & INVESTIGATOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2013-09-03 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2013-09-03 |
Time |
17:56 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2013-09-03 |
Time |
17:56 |
Sent To |
|
|
| Notes |
| 2013-09-03 18:00:16 | PERMIT #13081093 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | 1) HIGH-PILE STORAGE EXCEEDS 2,500 SQUARE FEE AND | | | THEREFORE REQUIRES BUILDING BE PROTECTED BY AN | | | APPROVED, AUTOMATIC SPRINKLER SYSTEM. PROVIDE | | | INFORMATION REGARDING THE TYPE OF SPRINKLER PROVIDED OR | | | TO BE PROVIDED. SEPARATE PLANS AND PERMITS ARE REQUIRED | | | FOR THE INSTALLATION OR MODIFICATION OF THE FIRE | | | SPRINKLER SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | | | | | | SUE ELLEN CALDERON | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-11-05 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-11-05 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-10-11 |
Time |
13:43 |
Sent To |
|
|
| Notes |
| 2013-11-01 12:57:42 | 11/1 TO MISC 2 BOX | | | | | 2013-10-23 13:43:21 | SENT TO FIRE.JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-08-28 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2013-08-28 14:53:17 | INCOMING SENT TO FIRE BOX. JW |
|
|
|