Plan Review Details - Permit 13081049
Plan Review Stops For Permit 13081049
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-10-21 Cont ID  
Sent By jwitmer Date 2013-10-21 Time 17:17 Rev Time 0.00
Received By jwitmer Date 2013-10-21 Time 17:17 Sent To  
Notes
2013-10-21 17:19:43PROVISO:
 TENANT SEPERATION WALL IS ALSSO A OCCUPANCY SEPERATION
 WALL.
 WILL REQUIRE 2 HR FIRE SEPERATION IF BUILDING IS NOT
 FIRE SPRINKLERED.
 WILL REQUIRE 1 HR FIRE SEPERATION IF BUILDING IS FIRE
 SPRINKLERED.
 2010 FBC-B TABLE 508.4.
  
 NEW FTOREFRONT DOOR REQUIRES STORM SHUTTERS UNDER
 SEPERATE PERMIT.
 2010 FBC-B 1609.1.2/ 1609.4.4.1
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-09-17 Cont ID  
Sent By jwitmer Date 2013-09-17 Time 15:22 Rev Time 0.00
Received By jwitmer Date 2013-09-17 Time 15:22 Sent To  
Notes
2013-09-17 15:52:41BUILDING PLAN REVIEW
 PERMIT: 13081049
 ADD: 871 VILLAGE BLVD SUITE # 602A
 CONT: PERFORMANCE GLASS
 TEL: (954)968-5222
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SEPT 17/ 2013
 ACTION: DENIED
  
 1) THE TITLEBLOCK OF THE PLANS INDICATE THE ADDRESS TO
 BE 721 VILLAGE, THIS IS A SITE ADRESS NOT THE BUILDING
 OR SUITE NUMBER PLEASE IDENTIFY THE LOCATION WHERE THE
 WORK IS TO BE COMPLETED UNDER THIS PERMIT. CITY OF WEST
 PALM BEAH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 ADMINISTRATION, CHAPTER 1, 2010 EDITION. 107.2.1
  
 2) SHEET A2.01 INDICATES NEW SWING STOREFRONT DOORS.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 4) SHEET A2.01 INDICATES PRESSURES FOR THE NEW
 STOREFRONT DOORS BUT IS MISSING THE WIND DESIGN
 CRITERIA THESE PRESSURES WERE DERIVED FROM:
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 5) PLANS INDICATE A ONE HOUR TENANT SEPEERATION WALL,
 THIS WALL IS ALSO CONSIDERED A OCCUPANCY SEPERATION
 WALL, THE A2 OCCUPANCY REQUIRES A 2 HOUR WALL. THIS
 WALL SHOULD BE LABELED AS A 2 HR OCCUPANCY SEPERATION
 WALL. UNDER PERMIT 05110790 THIS WALL RATING WENT INTO
 EFFECT. PLEASE NOTE ON PLAN AS WEL AS VERIFY IN THE
 FIELD. FBC-B TABLE 508.4.
  
 6)FBC-B 713.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY
 OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE
 AND SMOKE BARRIER ? PROTECT ALL OPENINGS.?
  
 7) 1008.1.10 PANIC AND FIRE EXIT HARDWARE. DOORS
 SERVING A GROUP H OCCUPANCY AND DOORS SERVING ROOMS OR
 SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN A GROUP A
 OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A LATCH OR
 LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE.
  
 8) SHEET E2 IS MISSING THE EXIT LIGHT AT THE REAR OF
 THE TENANT SPACE, NOR IS THERE A DIRECTIONAL EXIT SIGN
 TO THE REAR EXIT FBC-B 1006.3.1.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-11-04 Cont ID  
Sent By dharvey Date 2013-11-04 Time p Rev Time 0.00
Received By albarran Date 2013-11-04 Time 17:41 Sent To I
Notes
2013-11-04 18:28:47SENT TO SH DESK
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-10-11 Cont ID  
Sent By dharvey Date 2013-10-11 Time 10:12 Rev Time 0.00
Received By dharvey Date 2013-10-11 Time 08:58 Sent To  
Notes
2013-10-11 10:12:44SHEET E3
 1) EXSTING SERVICE IS RATED FOR 200 AMPS. HOWEVER, THE
 DEMANS LOAD SHOW 203 AMPS. NEED TO TAKE INTO ACCOUNT
 CONTINUOUS LOADS,
 2) PROVIDE THE SERVICE CONDUCTOR INSULATION TYPE, SIZE,
 LENGTH AND MATERIAL. FBC 107.3.5.
 3) PROVIDE THE SIZE OF THE SERVICE CONDUCTOR CONDUIT
 TYPE AND SIZE. FBC 107.3.5.
 4) NEED TO COMPLY WITH FBC ENERGY CONSERVATION CODE
 SECTION 505.7.3.
 5) PROVIDE SIZE OF CONDUIT AND CONDUCTORS SIZE FOR EACH
 NEW BRANCH CIRCUITS.
 SHEET E2
 1) ADDITIONAL EXIT LIGHT IS REQUIRED AT REAR DOOR.
 PROVIDE BRANCH CIRCUIT.
 2) EMERGENCY LIGHTING IS REQUIRED. NEED TO COMPLY WITH
 FBC 1006.2 FOR LIGHTING DENSIITY.
  
 REVIEWED BY WDS.
 DENIED IN (I)

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-10-23 Cont ID  
Sent By wjolin Date 2013-10-23 Time 15:39 Rev Time 0.00
Received By scaldero Date 2013-10-23 Time 15:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-09-11 Cont ID  
Sent By wjolin Date 2013-09-11 Time 17:52 Rev Time 0.00
Received By wjolin Date 2013-09-11 Time 17:21 Sent To  
Notes
2013-09-11 17:52:37871 VILLAGE BOULEVARD - #602A
 PERMIT #13081049
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: THE ADDRESS PROVIDED ON THE PLANS (721 VILLAGE
 BOULEVARD) DOES NOT MATCH THE ADDRESS PROVIDED ON THE
 PERMIT APPLICATION (871 VILLAGE BOULEVARD). ALSO, NO
 SUITE NUMBER PROVIDED ON THE PLANS.
  
 GENERAL: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED
 SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED
 IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE
 ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 GENERAL: CONFIRM EXISTING DOORS ARE EQUIPPED WITH PANIC
 HARDWARE.
  
 GENERAL: PROVIDE A SEATING LAYOUT.
  
 SHEET E2: NO EMERGENCY LIGHTING PROVIDED. EMERGENCY
 ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM OF 1.5
 HOURS IN THE EVENT OF FAILURE OF NORMAL LIGHTING.
 EMERGENCY LIGHTING FACILITIES SHALL BE ARRANGED TO
 PROVIDE INITIAL ILLUMINATION THAT IS NOT LESS THAN AN
 AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT, NOT LESS THAN
 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF EGRESS AT
 FLOOR LEVEL.
  
 SHEET E2: NO EXIT SIGNS PROVIDED FOR REAR EGRESS OR
 EXIT.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2013-09-11 Cont ID  
Sent By lwagner Date 2013-09-11 Time 09:04 Rev Time 0.00
Received By lwagner Date 2013-09-11 Time 08:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-11-06 Cont ID  
Sent By hmoser Date 2013-11-06 Time 10:58 Rev Time 0.00
Received By hmoser Date 2013-10-18 Time 05:48 Sent To  
Notes
2013-10-19 05:54:22C12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-15 Cont ID  
Sent By shill Date 2013-10-15 Time 16:13 Rev Time 0.00
Received By shill Date 2013-08-27 Time 12:25 Sent To  
Notes
2013-08-28 16:56:44C07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2013-10-21 Cont ID  
Sent By jwitmer Date 2013-10-21 Time 17:17 Rev Time 0.00
Received By jwitmer Date 2013-10-21 Time 17:17 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-09-17 Cont ID  
Sent By jwitmer Date 2013-09-17 Time 17:16 Rev Time 0.00
Received By jwitmer Date 2013-09-17 Time 17:16 Sent To  
Notes
2013-10-21 17:17:21BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-11-06 Cont ID  
Sent By hmoser Date 2013-11-06 Time 10:40 Rev Time 0.00
Received By hmoser Date 2013-11-06 Time 10:34 Sent To  
Notes
2013-11-06 10:39:45PASS PROVISO
 REFER TO SECTION 501.2.2 EXHAUST OPENING PROTECTION.
 PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS
 SHOWING
 AMCA STANDARD 550.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2013-11-04 Cont ID  
Sent By jwitmer Date 2013-11-04 Time 13:37 Rev Time 0.00
Received By mricard Date 2013-10-25 Time 14:26 Sent To  
Notes
2013-10-25 14:27:49ORIGINAL PLAN REVIEW COMMENTS WERE NOT ADDRESSED

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-10-02 Cont ID  
Sent By jwitmer Date 2013-10-02 Time 08:42 Rev Time 0.00
Received By jwitmer Date 2013-10-02 Time 08:42 Sent To  
Notes
2013-10-02 08:56:58MECHANICAL PLAN REVIEW
 PERMIT: 13081049
 ADD:871 VILLAGE BLVD # 602A
 CONT: PERFORMANCE CLASS
 TEL: (954)968-5222
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 10/02/2013
 ACTION: DENIED
  
 1) SHEET M1 INDICATES THE INSTALATION OF (2) NEW PIECES
 OF EQUIPMENT, NO SPECIFICATIONS AND INSTALATION
 INSTRUCTIONS WERE SUBMITTED FOR:
 1A) BAGEL OVEN, DIRECT VENT? 2010 FBC-M 301.3 / 506.4.2
 MANUFACTURES INSTRUCTIONS.
  
 1B) BEGAL KETTLE HOOD 2010 FBC-M 301.3 / 506.4.2
 MANUFACTURES INSTRUCTIONS.
  
  
 2) BAGEL OVEN NOTE # 8 INDICATES A DUAL EXHAUST WHILE
 DEPICTED A 8 INCH FRESH AIR AND A SINGLE 10 INCH B VENT
 FLUE, 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED,
 APPEARS THERE IS A DISCREPANCY.
  
 3) FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-09-11 Cont ID  
Sent By lwagner Date 2013-09-11 Time 08:57 Rev Time 0.00
Received By lwagner Date 2013-09-10 Time 15:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2013-09-05 Cont ID  
Sent By ajones Date 2013-09-05 Time 09:17 Rev Time 0.00
Received By ajones Date 2013-09-05 Time 09:17 Sent To  
Notes
***NONE***