| 2013-08-31 12:48:51 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. FBC 2010 EXISTING BUILDING 907.1, FLOOR LOAD TO | | | COMPLY WITH FBC 2010 1607. TABLE 1607.1 REQUIRES 100 | | | PSF UNIFORM FOR RETAIL, FIRST FLOOR (OR 1000 | | | CONCENTRATED); THE DCA MODULAR DESIGNED FOR BUSINESS | | | OCCUPANCY HAS A LIMITATION OF 50PSF ON THE PLAN. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2013-08-28 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-08-28 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-08-28 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2013-08-28 10:40:21 | TEMP CONSTRUCTION TRAILER EXEMPT FROM FBC | | | NOT LOCATED IN FLOOD ZONE | | | CONTRACTOR TO PROVIDE COPY OF CONTRACT PRIOR TO | | | ISSUANCE (VALUE TOO LOW) | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2013-09-12 |
|
|
Cont ID |
|
| Sent By |
D HARVEY |
Date |
2013-09-12 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-09-12 |
Time |
08:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2013-08-30 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-08-30 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-08-30 |
Time |
14:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2013-09-11 |
|
|
Cont ID |
|
| Sent By |
LPHILMOR |
Date |
2013-09-11 |
Time |
17:01 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2013-09-11 |
Time |
17:01 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2013-08-30 |
|
|
Cont ID |
|
| Sent By |
lphilmor |
Date |
2013-08-30 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
lphilmor |
Date |
2013-08-30 |
Time |
13:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2013-08-28 |
|
|
Cont ID |
|
| Sent By |
lphilmor |
Date |
2013-08-28 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
lphilmor |
Date |
2013-08-28 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2013-08-28 15:40:34 | 7001 PARKER AVE | | | PERMIT # 13081031 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | 1. NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK | | | INFORMATION. | | | 2. UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION | | | OF THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE | | | 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA | | | AMENDMENTS | | | 3.TEMPORARY BUILDING SHALL BE SEPARATED FROM ADJACENT | | | STRUCTURE IN ACCORDANCE WITH NFPA 241, TABLE 4.2.1. | | | CURRENT PLAN SHOWS EXPOSED SIDE TO BE 56 FEET AND A | | | MINIMUM DISTANCE OF 50 FEET IS REQUIRED. | | | 4. PROVIDE LOCATION OF PORTABLE FIRE EXTINGUISHERS. | | | | | | | | | LAUREN PHILMORE | | | FIRE INSPECTOR II / INVESTIGATOR I | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4783 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2013-09-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-09-12 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-09-09 |
Time |
11:33 |
Sent To |
|
|
| Notes |
| 2013-09-12 08:14:38 | TO S HILL | | 2013-09-11 17:38:54 | 9/11 TO DOUG HARVEY'S DESK | | | | | 2013-09-09 11:34:05 | C04 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-08-30 |
|
|
Cont ID |
|
| Sent By |
lphilmor |
Date |
2013-08-31 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-08-30 |
Time |
13:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-08-28 |
|
|
Cont ID |
|
| Sent By |
lphilmor |
Date |
2013-08-28 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
lphilmor |
Date |
2013-08-28 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2013-08-28 12:51:21 | TO WJ DESK | | | | | | | | 2013-08-28 10:58:34 | SENT TO ZONING BOX. |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2013-09-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-09-12 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-09-12 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2013-09-12 16:44:43 | SPOKE WITH WILLIE SWOPE - NO IMPACT FEE ASSESSMENT | | | REQUIRED | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2013-08-31 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-08-31 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-08-31 |
Time |
12:50 |
Sent To |
|
|
| Notes |
| 2013-08-31 12:51:30 | CALLED 233-5025 TO CONFIRM THAT IMPACT FEE ASSESSMENT | | | IS NOT REQUIRED | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2013-09-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-09-09 |
Time |
12:02 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-09-09 |
Time |
12:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2013-08-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-08-30 |
Time |
18:12 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-08-30 |
Time |
18:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2013-09-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-09-09 |
Time |
12:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-09-09 |
Time |
12:03 |
Sent To |
|
|
| Notes |
| 2013-09-09 12:03:21 | PROVISO, PASSED WITH EXCEPTION | | | | | | THIS IS A CHANGE OF OCCUPANCY FROM BUSINESS TO | | | MERCANTILE, 2010 FBC EXISTING BUILDING. A DRINKING | | | FOUNTAIN IS REQUIRED PER 2010 FBC PLUMBING TABLE 403.1 | | | AND SECTION 410.1. A BOTTLED WATER DISPENSER IS NOT | | | ACCEPTABLE. A REVISED RISER DIAGRAM IS REQUIRED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2013-08-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-08-30 |
Time |
18:18 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-08-30 |
Time |
18:12 |
Sent To |
B |
|
| Notes |
| 2013-08-30 18:18:49 | PROVISO, PASSED WITH EXCEPTION | | | | | | THIS IS A CHANGE OF OCCUPANCY FROM BUSINESS TO | | | MERCANTILE, 2010 FBC EXISTING BUILDING. A DRINKING | | | FOUNTAIN IS REQUIRED PER 2010 FBC PLUMBING TABLE 403.1 | | | AND SECTION 410.1. A BOTTLED WATER DISPENSER IS NOT | | | ACCEPTABLE. A REVISED RISER DIAGRAM IS REQUIRED. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2013-09-10 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2013-09-10 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2013-09-10 |
Time |
16:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2013-08-28 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2013-08-28 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2013-08-28 |
Time |
14:13 |
Sent To |
|
|
| Notes |
|
|