Plan Review Details - Permit 13080942
Plan Review Stops For Permit 13080942
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-05-20 Cont ID  
Sent By skennedy Date 2014-05-20 Time 07:24 Rev Time 0.00
Received By skennedy Date 2014-05-20 Time 07:07 Sent To Z
Notes
2014-05-20 07:25:15PROVISIONALLY APPROVED SUBJECT TO THE FOLLOWING:
  
 PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY
 COPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR
 INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL
 CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110
 & FBC 117.
 FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-05-20 Cont ID  
Sent By skennedy Date 2013-10-22 Time 13:57 Rev Time 0.00
Received By skennedy Date 2013-10-22 Time 11:44 Sent To  
Notes
2013-10-22 13:16:22PLEASE ADDRESS THE ITEMS NOTED BELOW:
 1) FBC 107.3.5.3 - PROVIDE SURVEY/SITE PLAN.
 2) FBC 107.3.4 - PROVIDE EVIDENCE OF REVIEW AND
 APPROVAL IN WRITING OF THE SELECTED PRODUCT APPROVALS
 BY THE DESIGNER OF RECORD, SPECIFICALLY FOR
 WINDOWS/SLIDING GLASS DOOR.
  
 PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY
 COPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR
 INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL
 CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110
 & FBC 117.
 FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-10-16 Cont ID  
Sent By dharvey Date 2013-10-16 Time 13:42 Rev Time 0.00
Received By dharvey Date 2013-10-16 Time 12:48 Sent To  
Notes
2013-10-16 13:31:37THIS FILE HAS BEEN APPROVED WITH THE HEREIN DESCRIBED
 EXCEPTIONS WHICH SHALL BE BE REQUIRED FOR SUCCESSFUL
 INSPECTIONS.
  
 FROM THE PERMIT APPLICATION, I GATHER THAT THIS
 STRUCTURE WAS BUILT WITHOUT THE BENEFIT OF A PERMIT AND
 OR INSPECTIONS SOME TIME AGO. REGARDLESS OF THE TIME IT
 WAS BUILT, IT IS CURRENTLY BEING PERMITTED; THEREFORE
 IT SHALL COMPLY WITH CURRENT CODE REQUIREMENTS AS
 FOLLOWS:
 1. THE ADDITION OF THIS ROOM MANDATES COMPLIANCE WITH
 THE FBCR 314.
 2. THE ELECTRICAL CIRCUITS WITHING THE AREA IN QUESTION
 (WITHIN THE SCOPE OF THIS PERMIT) SHALL COMPLY WITH NEC
 210.12 (B) AFCI
 3. THE ELECTRICAL DEVICES WITH IN AREA IN QUESTION,
 SHALL COMPLY WITH NEC 406.11 WHICH REQUIRES
 TAMPER-RESISTANT OUTLETS.
 4. THE LIGHT ON THE EXTERIOR OF THE ENTRY DOOR SHALL
 NOT BE BEHIND THE DOOR SWING.
 5. THE SUBMITTED DRAWING DOES NOT INDICATE COMPLIANCE
 WITH NEC 210.52 WITH REGARDS TO PROPER OUTLET PLACING.
 FURTHERMORE, THE DEDICATED OUTLET FOR THE WALL A/C UNIT
 IS SHOWN TO BE 30 AMP AND THUS SHALL NOT BE CONSIDERED
 AS PART OF THE REQUIRED OULTELS ALONG THE WALL LINE,
  
 THOUGH SOME OR ALL OF THE ABOVE MENTIONED REQUIREMENTS
 MAY ALREADY BE IN PLACE, THEY ARE NOT REFLECTED ON THE
 SUBMITTED DRAWING AND THUS MENTIONED HEREIN.
  
 SENT BACK TO BIN FOR FURTHER REVIEWS BY: MA
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-07-29 Cont ID  
Sent By jgomez Date 2014-07-29 Time 09:03 Rev Time 0.00
Received By jgomez Date 2014-07-25 Time 17:23 Sent To  
Notes
2014-07-25 17:24:03RE-SUBMITTAL (SURVEYS) SENT TO ZONING SHELF FOR LINDA'S
 REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-06-09 Cont ID  
Sent By skennedy Date 2014-06-09 Time 16:44 Rev Time 0.00
Received By skennedy Date 2014-05-19 Time 18:40 Sent To  
Notes
2014-05-19 18:44:55SENT TO S KENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-22 Cont ID  
Sent By skennedy Date 2013-10-22 Time 14:08 Rev Time 0.00
Received By skennedy Date 2013-08-23 Time 08:48 Sent To  
Notes
2013-10-22 14:11:41LEFT VM WITH CONTACT. PLACED SUBMITTAL IN DENIED PLANS
 SMALL "C."
2013-08-27 08:48:45SENT TO R28 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2014-08-18 Cont ID  
Sent By jgomez Date 2014-08-18 Time 16:12 Rev Time 0.00
Received By jgomez Date 2014-08-18 Time 16:12 Sent To  
Notes
2014-08-18 16:13:06IMPACT FEES PAID. $180.65. MU-2014-018316. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-10-22 Cont ID  
Sent By skennedy Date 2013-10-22 Time 09:48 Rev Time 0.00
Received By skennedy Date 2013-10-22 Time 09:47 Sent To  
Notes
2013-10-22 09:48:27IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED.
 THE PLANS ARE TO BE STAMPED AND RECEIPT PROVIDED.
 CONTACT 561 233 5100.

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-10-22 Cont ID  
Sent By skennedy Date 2013-10-22 Time 14:07 Rev Time 0.00
Received By skennedy Date 2013-10-22 Time 09:49 Sent To  
Notes
2013-10-22 14:06:54PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY
 COPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR
 INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL
 CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110
 & FBC 117.
 FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
 FBC 117 - THE BUILDING OFFICIAL (INSPECTOR) MAY REQUIRE
 TESTS OR TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED
 TESTS ARE TO BE MADE AT THE EXPENSE OF THE OWNER, OR
 AGENT, BY AN APPROVED TESTING LABORATORY OR OTHER
 APPROVED AGENCY.

Review Stop Z ZONING
Rev No 3 Status P Date 2014-07-29 Cont ID  
Sent By llouie Date 2014-07-29 Time 08:29 Rev Time 0.00
Received By llouie Date 2014-07-29 Time 08:28 Sent To  
Notes
2014-07-29 08:30:25** ZONING PROVISO **
  
 1.) NO KITCHEN FACILITY PERMITTED.

Review Stop Z ZONING
Rev No 2 Status F Date 2014-05-20 Cont ID  
Sent By llouie Date 2014-05-20 Time 14:46 Rev Time 0.00
Received By llouie Date 2014-05-20 Time 14:46 Sent To  
Notes
2014-05-20 14:50:46** FAILED **
  
 COMMENTS FROM 8/30/13 HAVE NOT BEEN ADDRESSED:
  
 1.) PROVIDE AN UPDATED SURVEY OF THE PROPERTY. THE
 SURVEY IS NEEDED TO DETERMINE THE SETBACKS OF THE
 STRUCTURE, INCLUDING ALL PROJECTIONS (I.E. WALL MOUNTED
 A/C UNIT) FROM THE PROPERTY LINES.
  
 PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE
 ARE QUESTIONS.
  
  
  
2014-05-20 09:11:505/20/14 ZONING RECEIVED SENT TO L. SG

Review Stop Z ZONING
Rev No 1 Status F Date 2013-08-30 Cont ID  
Sent By llouie Date 2013-08-30 Time 16:38 Rev Time 0.00
Received By llouie Date 2013-08-29 Time 16:38 Sent To  
Notes
2013-08-30 08:09:26FAILED.
  
 PROVIDE A SURVEY OF THE PROPERTY.
  
 PLEASE CONTACT LINDA LOUIE, PLANNER AT (561) 822-1442
 IF YOU HAVE ANY QUESTIONS.