Plan Review Details - Permit 13080849
Plan Review Stops For Permit 13080849
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-12-05 Cont ID  
Sent By jgomez Date 2013-12-04 Time 17:29 Rev Time 0.00
Received By jgomez Date 2013-12-04 Time 17:11 Sent To  
Notes
2013-12-04 17:46:13BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE PRODUCT APPROVALS FOR: *A) HARDIBOARD FOR
 VERTICAL APPLICATION AS SHOWN ON PLANS. ALSO, NOA
 08-0514.11 SUBMITTED EXPIRED ON 10/02/13.
 **B) ENTRY DOORS AS SPECIFIED ON PLANS. (NONE
 SUBMITTED).
 ***C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS AND DETAILS. ONLY FLORIDA PRODUCT APPROVAL FOR
 SIMPSON CONNECTOR H10A WAS SUBMITTED.
 NEED PRODUCT APPROVALS FOR THE OTHER CONNECTORS
 SPECIFIED ON PLANS AND ALL DETAILS. ***NOTE: DETAIL "B"
 ON SHEET S3 SPECIFY "USP" CONNECTORS, NOT SIMPSON.
 ****D) HURRICANE SHUTTERS AND COMPLETE INSTALLATION
 SCHEDULE IF DOORS WITH GLASS DON'T HAVE IMPACT GLASS.
 (DOOR PRODUCT APPROVAL WAS NOT SUBMITTED AT THIS TIME.
 UNABLE TO VERIFY).
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVALS.
  
 3- TYPICAL WALL SECTION ON SHEET SHEET A4.1. VERTICAL
 SIDING: NEED TO SHOW THE 6" CLEARANCE FROM FINISH GRADE
 AS REQUIRED BY SEC. R704. REVISE EXTERIOR ELEVATIONS AS
 WELL TO SHOW 6" CLEARANCE FROM THE GROUND.
  
 4- ENGINEER TO PROVIDE ALL HIS INFORMATION ON THE TITLE
 BLOCK AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES.
 ORIGINAL SUBMITTAL HAD THE INFORMATION AT THE BOTTOM OF
 THE PAGE. THIS TIME ALL THE STRUCTURAL DRAWINGS ARE
 MISSING THE ENGINEER'S INFORMATION.
  
 5- SHEET S3: PLYWOOD SHEATHING NAILING SCHEDULE:
 PROVIDE ENGINEERING CALCULATIONS SHOWING THAT THE
 SPECIFIED 10D NAILS ARE EQUIVALENT OR BETTER THAN THE
 MIN. 8D "RING SHANK" NAILS REQUIRED BY SEC. R803.2.3.1
 OF 2010 FBC-RESIDENTIAL AND SEC. 107.2.1.3 OF CITY
 AMENDMENTS TO FBC.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-10-21 Cont ID  
Sent By jgomez Date 2013-10-21 Time 14:22 Rev Time 0.00
Received By jgomez Date 2013-10-21 Time 14:04 Sent To  
Notes
2013-10-21 14:25:10NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
  
 2- SHEET A2.1:
 A) NEED TO PROVIDE BATHROOM WITH MAXIMUM POSSIBLE
 PRIVACY (MASTER BATHROOM IN THIS CASE) WITH A DOOR THAT
 HAS 29" MIN. CLEAR OPENING AS REQUIRED BY SEC R320 OF
 2010 FBC-RESIDENTIAL. REVISE SIZE OF DOOR.
  
 B) REVISE THE EGRESS WINDOWS NOTE. EGRESS WINDOWS
 REQUIRE A MINIMUM "CLEAR OPENING AREA" NOT MINIMUM
 "GLASSS AREA". ALSO, REVISE THE MIN. HEIGHT AND TOTAL
 MINIMUM AREA. SEE SEC. R310 AND REVISE NOTE AS
 REQUIRED.
  
 C) SPECIFY ATTIC ACCESS LOCATION AND SIZE TO SHOW
 COMPLIANCE WITH SEC. R807.
  
 3- SPECIFY CARBON MONOXIDE ALARMS IN PLANS AS REQUIRED
 BY SEC. R315.
  
 4- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806.
 COORDINATE WITH THE ENERGY CALCULATIONS.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) HARDIBOARD AS SPECIFIED ON PLANS.
  
 B) ROOF SHINGLES AS SPECIFIED ON PLANS.
  
 C) SINGLE HUNG WINDOWS AS SPECIFIED ON PLANS.
  
 D) ENTRY DOORS AS SPECIFIED ON PLANS.
  
 E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. ***NOTE: PROVIDE ONLY THE PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR.
  
 F) HURRICANE SHUTTERS IF WINDOWS AND DOORS WITH GLASS
 DON'T HAVE IMPACT GLASS.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS.
  
 7- TYPICAL WALL SECTION ON SHEET SHEET A4.1:
 A) R-19 INSULATION DOESN'T FIT ON 2X4 WOOD WALL. REVISE
 AS REQUIRED. COORDINATE WITH ENERGY CALCULATIONS ALSO.
 SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) SPECIFY 7/8" STUCCO THICKNESS AS REQUIRED BY TABLE
 R702.1(1).
  
 C) NEED TO SHOW THE 6" CLEARANCE FROM FINISH GRADE AS
 REQUIRED BY SEC. R704. REVISE EXTERIOR ELEVATIONS AS
 WELL TO MATCH.
  
 8- SHEET S1: SOME WINDOWS AND DOORS ARE LOCATED ON WALL
 ZONE #5 (SEE SHEET S3). DESIGN PRESSURES PROVIDED ARE
 FOR WALL ZONE #4. REVISE THE DESIGN PRESSURES AS
 REQUIRED BY SEC. R301. 2.1.4.3.
  
 9- SHEET S2: REVISE SECTION AT STEPS #2 TO MATCH PLANS.
 NEED TO SHOW THE LANDING. SEC. 107.2.1 CITY AMENDMENTS.
 AND PROVIDE DIMENSIONS. FLOOR PLAN DON'T SHOW RISER
 HEIGHT. SEE SEC. R311.7.4.
  
 10- SHEET S3:
 A) CLEARLY SPECIFY AND IDENTIFY ALL DEAD AND LIVE LOADS
 SEPARATELY, INCLUDING THE ATTIC LIVE LOAD REQUIRED BY
 TABLE R301.5. AND CLARIFY DESIGN LOAD SCHEDULE "(ALL
 LOADS SHOWN ARE IN (BLANK) PER SQ. FT.).
  
 B) REVISE PLYWOOD SHEATHING NAILING SCHEDULE. IT
 DOESN'T MATCH ROOF SHEATHING NAILING NOTE SHOWN ON SAME
 SHEET. ***NOTE; SEC. R803.2.3.1 REQUIRES MIN. 8D RING
 SHANK NAILS IN ALL ZONES AND ROOF ZONE 3 REQUIRES NAILS
 TO BE 4" O.C..
  
 11- PROVIDE 2 COPIES OF THE SOIL TEST REPORT SUBMITTED
 WITH ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED
 BY CHAPTER 471 FLORIDA STATUTE.
  
 12- IF WINDOWS AND DOORS WITH GLASS HAVE NO IMPACT
 GLAZING, THEN NEED TO PROVIDE A COMPLETE HURRICANE
 SHUTTERS INSTALLATION SCHEDULE ALONG WITH THE PRODUCT
 APPROVAL SUBMITTED. SEC. 107.2.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS....
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-12-05 Cont ID  
Sent By skennedy Date 2013-12-05 Time 16:44 Rev Time 0.00
Received By skennedy Date 2013-12-05 Time 16:44 Sent To  
Notes
2013-12-04 17:28:58NEW SHEETS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-10-16 Cont ID  
Sent By dharvey Date 2013-10-16 Time 12:27 Rev Time 0.00
Received By dharvey Date 2013-10-16 Time 11:34 Sent To  
Notes
2013-10-16 12:16:41THE FOLLOWING ITEMS, THOUGH NOT ADDRESSED ON THE
 SUBMITTED PLANS SHALL BE ADDRESSED AND ADHERED TO FOR
 SUCCESSFUL INSPECTIONS:
 1. CARBON MONOXIDE DETECTION AS PER FBCR 315 SHALL BE
 REQUIRED.
 2. ELECTRICAL NOTES INDICATE AFCI PROTECTION FOR
 BEDROOMS, NEC 2008 210.12 REQUIRES FURTHER APPLICATION
 OF AFCI.
 3. AS PER NEC 406.11 TAMPER-RESISTANT DEVICES WILL BE
 REQUIRED THROUGHOUT RESIDENCE.
  
 THIS FILE WAS APPROVED PENDING THE HEREIN DESCRIBED
 EXCEPTIONS,
  
 SENT BACK TO BIN WAITING FURTHER REVIEWS BY: MA

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2013-12-06 Cont ID  
Sent By skennedy Date 2013-12-06 Time 09:40 Rev Time 0.00
Received By skennedy Date 2013-12-06 Time 09:40 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2013-10-22 Cont ID  
Sent By lwagner Date 2013-10-22 Time 10:12 Rev Time 0.00
Received By lwagner Date 2013-10-22 Time 09:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-01-07 Cont ID  
Sent By jgomez Date 2014-01-07 Time 15:43 Rev Time 0.00
Received By jgomez Date 2013-12-19 Time 17:58 Sent To  
Notes
2013-12-19 17:59:03INCOMING SENT TO J GOMEZ DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-05 Cont ID  
Sent By jgomez Date 2013-12-05 Time 16:53 Rev Time 0.00
Received By jgomez Date 2013-11-20 Time 16:25 Sent To  
Notes
2013-11-21 16:26:05SENT TO ZONING SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-22 Cont ID  
Sent By lwagner Date 2013-10-22 Time 10:12 Rev Time 0.00
Received By lwagner Date 2013-08-22 Time 15:39 Sent To  
Notes
2013-08-22 15:40:45SENT TO R-27 BOX. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2014-01-07 Cont ID  
Sent By jgomez Date 2014-01-07 Time 15:42 Rev Time 0.00
Received By jgomez Date 2014-01-07 Time 15:15 Sent To  
Notes
2014-01-07 15:43:23NO FEES DUE. PLANS STAMPED ON DECEMBER 19, 2013.
 MU-2013-26423. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2013-12-05 Cont ID  
Sent By jgomez Date 2013-12-05 Time 08:52 Rev Time 0.00
Received By jgomez Date 2013-12-05 Time 08:52 Sent To  
Notes
2013-12-05 08:52:33BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-10-21 Cont ID  
Sent By jgomez Date 2013-10-21 Time 14:25 Rev Time 0.00
Received By jgomez Date 2013-10-21 Time 14:25 Sent To  
Notes
2013-10-21 14:27:17BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-12-05 Cont ID  
Sent By jgomez Date 2013-12-05 Time 09:30 Rev Time 0.00
Received By jgomez Date 2013-12-05 Time 09:30 Sent To  
Notes
2013-12-05 10:06:01MECHANICAL REVIEW APPROVED WITH PROVISO:
  
 1-PROVIDE THE COMPLETE EQUIPMENT SIZING CALCULATIONS
 NOT JUST THE SUMMARY. AND, INCLUDE THE EQUIPMENT AS
 REQUIRED BY SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- A/C PLAN ON SHEET A5.1 TO SHOW EQUIPMENT LISTED IN
 THE EQUIPMENT SIZING CALCULATIONS. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-10-21 Cont ID  
Sent By jgomez Date 2013-10-21 Time 18:24 Rev Time 0.00
Received By jgomez Date 2013-10-21 Time 18:24 Sent To  
Notes
2013-10-21 18:48:01NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- CONDENSING UNIT PAD DETAIL STATES THAT SEE
 STRUCTURAL DRAWINGS FOR SPECIFICATIONS. STRUCTURAL
 DRAWINGS DON'T PROVIDE ANY SPECIFICATIONS. PROVIDE SUCH
 SPECIFICATIONS. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 2- MECHANICAL PLAN ON SHEET A5.1 SHOWS THE RETURN AIR
 FROM THE BEDROOMS BUT IT DOESN'T SHOW RETURN AIR FOR
 THE REST OF THE HOUSE. SHOW HOW PROVIDING THE RETURN
 AIR FOR THE REST OF THE HOUSE. SEC. M1602 OF 2010
 FBC-RESIDENTIAL.
  
 3- PROVIDE THE COMPLETE EQUIPMENT SIZING CALCULATIONS
 NOT JUST THE SUMMARY. AND, INCLUDE THE EQUIPMENT AS
 REQUIRED BY SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION.
  
 ***NOTE: COORDINATE WITH THE ENERGY CALCULATIONS
 SUBMITTED.
  
 4- A/C PLAN ON SHEET A5.1 TO SHOW EQUIPMENT LISTED IN
 THE EQUIPMENT SIZING CALCULATIONS. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-10-22 Cont ID  
Sent By lwagner Date 2013-10-22 Time 10:12 Rev Time 0.00
Received By lwagner Date 2013-10-22 Time 09:41 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2013-12-05 Cont ID  
Sent By jgomez Date 2013-12-05 Time 08:53 Rev Time 0.00
Received By jgomez Date 2013-12-05 Time 08:53 Sent To  
Notes
2013-12-05 08:54:32SHINGLES FLORIDA PRODUCT APPROVAL FL10124-R11
 SUBMITTED. JG.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2013-10-21 Cont ID  
Sent By jgomez Date 2013-10-21 Time 18:21 Rev Time 0.00
Received By jgomez Date 2013-10-21 Time 18:21 Sent To  
Notes
2013-10-21 18:22:07NO ROOF PRODUCT APPROVALS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 3 Status P Date 2013-12-17 Cont ID  
Sent By dkittred Date 2013-12-17 Time 17:31 Rev Time 0.00
Received By dkittred Date 2013-12-17 Time 17:30 Sent To  
Notes
2013-12-17 17:31:38SEPARATE LANDSCAPE PERMIT SUBMITTED - 13120520 AND
 APPROVED BY PLANNING & ZONING 12/17/13 WHICH SATISFIES
 THE OUTSTANDING P & Z COMMENTS FROM 11/22/13. - DK

Review Stop Z ZONING
Rev No 2 Status F Date 2013-11-22 Cont ID  
Sent By dkittred Date 2013-11-22 Time 17:35 Rev Time 0.00
Received By dkittred Date 2013-11-22 Time 13:16 Sent To  
Notes
2013-12-17 17:29:29SEPARATE LANDSCAPE PERMIT SUBMITTED - 13120520 AND
 APPROVED BY PLANNING & ZONING 12/17/13 WHICH SATISFIES
 THE OUTSTANDING P & Z COMMENTS FROM 11/22/13. - DK
2013-11-22 17:43:4211/22/13 SENT TO JG.
2013-11-22 17:34:39PLANNING & ZONING COMMENTS:
  
 11/22/13
 ALL COMMENTS SATISFIED, HOWEVER, SEPARATE PERMIT
 APPLICATION WILL NEED TO BE SUBMITTED IN ORDER FOR
 PLANNING TO ISSUE FINAL APPROVAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2013-11-22 07:45:3211/22/13 - ZONING RECEIVED. SENT TO DK FOR REVIEW. LL

Review Stop Z ZONING
Rev No 1 Status F Date 2013-08-29 Cont ID  
Sent By dkittred Date 2013-08-29 Time 11:19 Rev Time 0.00
Received By dkittred Date 2013-08-29 Time 08:58 Sent To  
Notes
2013-08-29 11:19:49PLANNING & ZONING COMMENTS ***FAILED***
  
 8/29/2013
  
 1. SURVEY OF THE PROPERTY WILL BE REQUIRED.
  
 2. THE SITE PLAN COMPLIES WITH SETBACKS, BUT THE
 MINIMUM SETBACK FOR THE SIDE (MIN. 5' WITH TOTAL OF
 15') AND REAR (10% THE DEPTH OF THE LOT) ARE NOT
 DEPICTED CORRECTLY. PLEASE REVISE.
  
 3.LANDSCAPE PLAN WILL REQUIRE A SEPARATE PERMIT.
 COMMENTS FOR THE LANDSCAPE PLAN:
 A. THE MINIMUM PLANTING REQUIREMENTS ARE CALCUATED
 BASED ON OPEN SPACE (OPEN SPACE IS THE TOTAL AREA OF
 THE PROPERTY MINUS FOOTPRINT OF STRUCTURE(S)). MY
 CALCUATIONS SHOW THAT 4 TREES AND 9 SHRUBS ARE
 REQUIRED.
 B. THE TREES AS PROPOSED ARE FINE, HOWEVER, IF
 SOMETHING IS CHANGED ON THE PLANS PLEASE KEEP IN MIND
 THAT PALM TREES PROPOSED CAN ONLY COUNT TOWARD 35% OF
 THE REQUIRED TREES. ADDITIONALLY, PALM TREES ARE
 REQUIRED TO BE PLANTED IN GROUPS OF THREE.
 C. THE LEATHER FERNS ARE NOT CONSIDERED SHRUBS AND CAN
 NOT BE COUNTED TOWARD THE MINIMUM SHRUB REQUIREMENT.
 PLEASE PROVIDE ADDITIONAL SHRUBS OR REVISE THE SPECIES.
 [SHRUBS MEAN A SELF-SUPPORTING, WOODY, EVERGREEN PLANTS
 SMALLER THAN A TREE AND USUALLY BRANCHING FROM OR NEAR
 THE GROUND, INCLUDING, BUT NOT LIMITED TO, SUCH PLANTS
 AS HIBISCUS ROSA-SINENSIS, LIGUSTRUM LUCIDUM,
 PODOCARPUS MACROPHYLLA, AND MURRAYA PANICULATA.]
  
 4. IF ANY EXISTING TREES ON THE SITE WILL BE REMOVED OR
 RELOCATED WITH THE PROPOSED CONSTRUCTION, A TREE
 ALTERATION PERMIT WILL BE REQUIRED THROUGH THE PLANNING
 & ZONING DIVISION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2013-08-28 14:53:258/28/13