| 2013-08-23 08:41:55 | |
| | 8/28/2013 PLANS SUBMITTED FOR TIE DOWNS. JW |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 13080844 |
| | ADD: 3501 N MILITARY TRAIL/ MODULAR BUILDINGS- |
| | RESTROOMS |
| | CONT: HEDRICK BROTHERS / JIM KLEEN |
| | TEL: (561)310-5150 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRIDAY AUGUST 23/ 2010 |
| | ACTION: DENIED |
| | |
| | 1) PREFABRICATED STAIR AND LANDING ANCHORING SHEET S-1 |
| | BY ANDREW MORGAN P.E. INDICATES LOADS TO BE RESISTED |
| | FOR THE PREFABRICATED LANDINGS & STAIRS AND HAS A NOTE |
| | : |
| | STRAPS BY TIE DOWN ENGINEERING ATLANTA, GEORGIA |
| | GROUND ANCHORS IN SANDY SOILSBY THE TIE DOWN |
| | ENGINEERING ATLANTA, GEORGIA |
| | |
| | THE ENGINEER OF RECORD ANDREW MORGAN P. E. DOES NOT |
| | HAVE A SHOP DRAWING STAMP SHOWING HE HAS REVIEWED THE |
| | DOCUMENTS. |
| | THE ANCHOR CHART INDICATES (CIRCLED) AN ANCHOR 36" X |
| | 3/4" ROD/ 1'-6" X 1'-4" HELIX BUT THE CHART DOES NOT |
| | INDICATE HOW MUCH IN KIPS THE LOADS TO BE RESISTED. |
| | SHEET S1 INDICATES TO TYPES OF ANCHORS REQUIRED A 5.5K |
| | AND A 6.3 K. |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | 1609. 6.4.1 PART OF THE MWFRS MAIN WIND-FORCE RESISTING |
| | SYSTEM. |
| | |
| | 2) 8/27/2013 COMPLIED. TO BE PERMITED AS A BUILDING |
| | "TEMPORARY " LESS THAN 180 DAYS, SEE LETTER FROM THE |
| | PRESIDENT, OXBRIDGE ACADEMY. |
| | |
| | NOTE: CODE COMMENT. |
| | REVIEWED AS: |
| | FBC-B & 503.1.2 (2) BUILDINGS SAME LOT. TWO OR MORE |
| | BUILDINGS ON THE SAME LOT SHALL BE REGULATED AS |
| | SEPARATE BUILDINGS OR SHALL BE CONSIDERED AS PORTIONS |
| | OF ONE BUILDING ( NO FIRE RESISTANCE SEPERATION |
| | REQUIRED/ NOR OPENING PROTECTIVES) IF THE BUILDING |
| | HEIGHT OF EACH BUILDING AND THE AGGREGATE BUILDING AREA |
| | OF THE BUILDINGS ARE WITHIN THE LIMITATIONS OF TABLE |
| | 503 AS MODIFIED BY SECTIONS 504 AND 506. THE PROVISIONS |
| | OF THIS CODE APPLICABLE TO THE AGGREGATE BUILDING SHALL |
| | BE APPLICABLE TO EACH BUILDING. |
| | BUILDING AREA 15.66'X 44'= 689 SQ FT X 2= 1378 SQ FT |
| | ALLOWABLE AREA TYPE VB/ BUSINESS OCCUPANCY ON THE SAME |
| | LOT IN COMPLIANCE WITH 2010 FBC-B ALLOWABLE AREA 9,000 |
| | SQ FT |
| | ALLOWABLE AREA TYPE VB/ UTILITY OCCUANCY ON THE SAME |
| | LOT IN COMPLIANCE WITH WITH 2010 FBC-B ALLOWABLE AREA |
| | 5,500 SQ FT |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |