Plan Review Details - Permit 13080748
Plan Review Stops For Permit 13080748
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-11-15 Cont ID  
Sent By JWITMER Date 2013-11-15 Time 16:45 Rev Time 0.00
Received By jwitmer Date 2013-11-15 Time 16:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-09-30 Cont ID  
Sent By jwitmer Date 2013-09-30 Time 14:10 Rev Time 0.00
Received By jwitmer Date 2013-09-30 Time 14:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-09-09 Cont ID  
Sent By jwitmer Date 2013-09-09 Time 10:12 Rev Time 0.00
Received By jwitmer Date 2013-09-09 Time 09:17 Sent To  
Notes
2013-09-09 10:12:20BUILDING PLAN REVIEW
 PERMIT: 13080748
 ADD: 721 VILLAGE BLVD # 207
 CONT: PAGE CONTRACTING
 TEL: (954)868-4561
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SEPT. 09/2013
 ACTION: DENIED
  
 1) COVERSHEET/ A0.01:
  
 1A) THE COVER SHEETOF THE PLANS LIST THE ADDESS OF 207
 VILLAGE BLVD., IN REVIEWEING THE PERMIT APPLICATION
 WITH THE ADDRESS OF 721 VILLAGE BLVD SUITE # 207 AND
 THE CORRESPONDING PROPERTY CONTROL NUMBER
 THAT MATCHES THE 721 VILLAGE BLVD ADDRESS IT APPEARS
 THE PLANS HAVE THE WRONG ADDRESS, PLEASE UPDATE THE
 PLANS, DISCREPANCY CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 2010 EDITION, SECTION 107.2.1.3.
  
 1B) BUILDING DATA CHART, THIS BUILDING IS CLASSIFIED AS
 A III-B BUILDING, THE PLANS DO NOT PROVIDE IF THIS
 BUILDING IS FIRE SPRINKLERED OR NOT? CITY OF WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION, 2010 EDITION, SECTION 107.3.5.1.
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDING, COMMERCIAL
 BUILDING. SHEET A2.01 HAS A NOTE ABOUT FIRE SPRINKLERS,
 BUT IT IS NOT PART OF THE BUILDING DATA CHART FOUND ON
 SHEET A0.01.
  
 1C) BUILDING DATA CHART INDICATES THIS TENANT SPACE TO
 BE A BUSINESS OCCUPANCY, WITH AN OCCUPANT LOAD OF 12.
 THE EXCEPTION THAT YOU WERE LOOKING AT EXCEPTION # 1
 ALSO TIES WITH EXCEPTIOJN # 3, IF THE ROOM OR AREA IN
 QUESION IS UNDER 750 SQ FT /15 OCCUPANTS, THE OCCUPANT
 LOAD IS LESS THAN 50. THIS SPACE IS 1,120 SQ FT/ 15= 75
 OCCUPANTS, NOT ALL OF THE SPACE IS TO BE USED FOR AN
 ASSEMBLY OCCUPANCY, IT APPEARS TO BE A MIXED USE
 OCCUPANCY WITH MERCANTILE AND POSSILE BUSINESS
 OCCUPANCY WITH THE CHECK IN AND WEIGH-IN AREAS, PLEASE
 PROVIDE THE SQUARE FOOTAGE FOR THESE USE AREAS TO
 ACTUALLY DETERMINE WHAT OCCUPANCIES ARE TO BE DECLARED.
 IS THIS SPACE GOING TO BE A MIXED USE SEPERATED OR NONE
 SEPERATED OCCUPANCY FBC-B 508.3 & 508.4. PLEASE ALSO
 REVIEW 508.2 & 508.2.1.
  
 2) SHEET A2.01, THE PLANS INDICATE THEERE TO BE A SIGN
 IN OR ENROLLMENT REGISTRY AND ALSO A MERCHANDISE AREA
 AS WELL AS A WEIGH IN AREA PLEASE PROVIDE CODE
 COMPLIANCE FOR THE FOLLOWING:
 2A) SIGN IN OR ENROLLMENT REGISTRY: 2010 FL ACCESS.
 CODE 904.3.3 & 902.3.
  
 2B) MERCANTILE AREA 2010 FL ACCESS CODE 904.4. SALES
 ANS SERVICE COUNTERS.
  
 2C) WEIGH IN AREA: 2010 FL ACCESS CODE 202.3.1. &
 305.7.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-10-25 Cont ID  
Sent By skennedy Date 2013-10-25 Time 14:45 Rev Time 0.00
Received By skennedy Date 2013-10-25 Time 14:45 Sent To  
Notes
2013-10-25 14:46:25NO REVIEW AT THIS TIME AS PLAN WILL REQUIRE REDESIGN
 DUE TO PLUMBING PLAN REVIEW COMMENTS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-09-16 Cont ID  
Sent By dharvey Date 2013-09-16 Time 16:47 Rev Time 0.00
Received By dharvey Date 2013-09-16 Time 16:47 Sent To  
Notes
2013-09-16 16:47:469-16-13
  
 APPROVED AS NOTED
  
 VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status N Date 2013-11-20 Cont ID  
Sent By WJOLIN Date 2013-11-20 Time 15:05 Rev Time 0.00
Received By skennedy Date 2013-11-20 Time 15:05 Sent To  
Notes
2013-11-20 15:05:38RESTAMP ONLY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-10-08 Cont ID  
Sent By scaldero Date 2013-10-08 Time 13:37 Rev Time 0.00
Received By scaldero Date 2013-10-08 Time 13:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-08-28 Cont ID  
Sent By wjolin Date 2013-08-28 Time 11:40 Rev Time 0.00
Received By wjolin Date 2013-08-28 Time 11:20 Sent To  
Notes
2013-08-28 11:40:46721 VILLAGE BOULEVARD - #207
 PERMIT #13080748
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE ADDRESS PROVIDED ON THE PLANS (207 VILLAGE BLVD)
 DOES NOT MATCH THE ADDRESS PROVIDED ON THE PERMIT
 APPLICATION (721 VILLAGE BOULEVARD - #207).
  
 THE PLANS INDICATE THIS TO BE A BUSINESS OCCUPANCY;
 HOWEVER, AN ASSEMBLY OCCUPANCY IS MORE APPROPRIATE FOR
 THIS LARGE MEETING ROOM. AN ASSEMBLY OCCUPANCY IS
 DEFINED AS "AN OCCUPANCY USED FOR A GATHERING OF 50 OR
 MORE PERSONS FOR DELIBERATION, WORSHIP, ENTERTAINMENT,
 EATING, DRINKING, AMUSEMENT, AWAITING TRANSPORTATION,
 OR SIMILAR USES." USING AN OCCUPANT LOAD FACTOR OF 15
 SQ.FT. PER PERSON, THE TOTAL NUMBER OF PERSONS IN THIS
 SPACE WILL EXCEED 50 (900 SQ.FT. / 15 = 60 PERSONS).
  
 FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD OF 50 OR
 MORE PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON DOORS
 TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES
 ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC
 HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE MAIN
 ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED DOOR
 LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING
 THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS
 OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN
 HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE
 SUBSTITUTED FOR A KEYED LOCK.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-11-20 Cont ID  
Sent By skennedy Date 2013-11-20 Time 15:09 Rev Time 0.00
Received By skennedy Date 2013-11-05 Time 16:47 Sent To  
Notes
2013-11-06 16:49:25B35

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-25 Cont ID  
Sent By skennedy Date 2013-10-25 Time 14:47 Rev Time 0.00
Received By skennedy Date 2013-09-27 Time 14:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2013-09-19 Time   Rev Time 0.00
Received By shill Date 2013-08-20 Time 15:49 Sent To  
Notes
2013-08-22 15:50:09B41

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-11-20 Cont ID  
Sent By HMOSER Date 2013-11-20 Time 15:02 Rev Time 0.00
Received By skennedy Date 2013-11-20 Time 15:02 Sent To  
Notes
2013-11-20 15:02:26RESTAMP

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-10-23 Cont ID  
Sent By mricard Date 2013-10-23 Time 15:59 Rev Time 0.00
Received By mricard Date 2013-10-23 Time 15:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-09-19 Cont ID  
Sent By rregueir Date 2013-09-19 Time 16:59 Rev Time 0.00
Received By rregueir Date 2013-09-19 Time 16:59 Sent To  
Notes
2013-09-19 17:09:33REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2010
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE CONDENSING UNIT ATTACHMENT DETAIL FOR WIND
 RESISTANCE PER FBC-M 301.12.
  
 2. PROVIDE CFMS FOR EACH GRILL/REGISTER ON PLANS PER
 FBC-M 603.1.
  
 3. PROVIDE SMOKE DETECTOR WITH FAN SHUT DOWN PER FBC-M
 606.2.1.
  
 4. AHU DETAIL SAYS TO "SEE PLUMBING FOR CONTINUATION"
 OF AUXILIARY DRAIN LINE. NO INFORMATION ON AUXILIARY
 DRAIN WAS FOUND ON PLUMBING DRAWINGS. PROVIDE AUXILIARY
 OR SECONDARY DRAIN PROTECTION PER FBC-M 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2013-11-20 Cont ID  
Sent By LWAGNER Date 2013-11-20 Time 15:02 Rev Time 0.00
Received By skennedy Date 2013-11-20 Time 15:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2013-10-17 Cont ID  
Sent By lwagner Date 2013-10-17 Time 13:44 Rev Time 0.00
Received By lwagner Date   Time   Sent To  
Notes
2013-10-17 13:31:26FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #2
 DENIED:
  
 COMMENTS FROM REVIEW #1 WERE NOT ADDESSED:
 ONE RESTROOM WOULD BE OK FOR UP TO 25 PERSONS. FBC
 PLUMBING 403.1 (1 PER 25 FOR THE FIRST 50 AND 1 PER 50
 FOR THE REMAINDER EXCEEDING 50). SHEET A2.01 LISTS
 OCCUPANT LOAD AS 43. THE EXCEPTION SHOWN ON SHEET A0.01
 WOULD BE FOR AN OCCUPANT LOAD BASED ON SQUARE FEET (1
 PER 100 SQUARE FOOT). 43 OCCUPANTS WOULD REQUIRE 2
 FACILITIES PER TABLE 403.1 BUSINESS.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-09-09 Cont ID  
Sent By lwagner Date 2013-09-09 Time 15:37 Rev Time 0.00
Received By lwagner Date 2013-09-09 Time 14:00 Sent To  
Notes
2013-09-09 15:37:40FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. PLEASE SEE BUILDING AND FIRE COMMENTS ABOUT
 OCCUPANCY TYPE. IF THIS AN ASSEMBLY OCCUPANCY, THEN
 SEPARATE RESTROOMS FOR EACH SEX WILL BE REQUIRED AND A
 SERVICE SINK. TABLE FBC PLUMBING 403.1.
 IF THE OCCUPANCY TYPE IS BUSINESS, THEN ONE RESTROOM
 WOULD BR OK FOR UP TO 25 PERSONS. FBC PLUMBING 403.1 (1
 PER 25 FOR THE FIRST 50 AND 1
 PER 50 FOR THE REMAINDER EXCEEDING 50).
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  