Plan Review Details - Permit 13080746
| Plan Review Stops For Permit 13080746 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2013-08-29 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-08-29 |
Time |
18:41 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-08-29 |
Time |
18:41 |
Sent To |
|
|
| Notes |
| 2013-08-29 18:42:22 | 8-29-13 | | | COMMENTS ADDRESSED | | | VB |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2013-08-24 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-08-24 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-08-24 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2013-08-24 11:07:02 | PROVIDE MOTOR CALCULATION FOR INSTALLATION BASED ON NEC | | | ARTICLE 430. | | | CONDUCTORS DO NOT APPEAR TO BE SIZED FOR INRUSH AND/OR | | | VOLTAGE DROP 430.250, 430 PART II, FLORIDA ENERGY CODE | | | 505.7.3 (NO DISTANCES SHOWN) | | | PROVIDE DETAILS OF MOTOR CONTROL INCLUDING OVERLOAD | | | PROTECTION 430.32 | | | PROVIDE DETAILS OF EQUIPMENT SHOWING SUITABILITY FOR | | | THE INSTALLATION AND SUPPORTS 110.3, 110.8, 110.9, | | | 110.12, 110.13 | | | PLANS SHOW "FUTURE" BUILDING AND AS SUCH, DETAILS OF | | | THE RACKING OR SUPPORT SYSTEM ARE NEEDED |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-08-29 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-08-29 |
Time |
18:42 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-08-29 |
Time |
18:42 |
Sent To |
|
|
| Notes |
| 2013-08-28 09:38:32 | SENT TO ELECTRIC UNDER $5000 BOX. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-08-24 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-08-24 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-08-20 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2013-08-24 11:09:14 | IN DENIED UNDR "I" | | | CONTRACTOR CALLED AND ADVISED NOTES ARE IN THE SYSTEM | | 2013-08-20 14:13:41 | TO ELEC < $5K | | | |
|
|
|