Plan Review Details - Permit 13080746
Plan Review Stops For Permit 13080746
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-08-29 Cont ID  
Sent By dharvey Date 2013-08-29 Time 18:41 Rev Time 0.00
Received By dharvey Date 2013-08-29 Time 18:41 Sent To  
Notes
2013-08-29 18:42:228-29-13
 COMMENTS ADDRESSED
 VB

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-08-24 Cont ID  
Sent By dharvey Date 2013-08-24 Time 11:07 Rev Time 0.00
Received By dharvey Date 2013-08-24 Time 10:57 Sent To  
Notes
2013-08-24 11:07:02PROVIDE MOTOR CALCULATION FOR INSTALLATION BASED ON NEC
 ARTICLE 430.
 CONDUCTORS DO NOT APPEAR TO BE SIZED FOR INRUSH AND/OR
 VOLTAGE DROP 430.250, 430 PART II, FLORIDA ENERGY CODE
 505.7.3 (NO DISTANCES SHOWN)
 PROVIDE DETAILS OF MOTOR CONTROL INCLUDING OVERLOAD
 PROTECTION 430.32
 PROVIDE DETAILS OF EQUIPMENT SHOWING SUITABILITY FOR
 THE INSTALLATION AND SUPPORTS 110.3, 110.8, 110.9,
 110.12, 110.13
 PLANS SHOW "FUTURE" BUILDING AND AS SUCH, DETAILS OF
 THE RACKING OR SUPPORT SYSTEM ARE NEEDED

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-29 Cont ID  
Sent By dharvey Date 2013-08-29 Time 18:42 Rev Time 0.00
Received By dharvey Date 2013-08-29 Time 18:42 Sent To  
Notes
2013-08-28 09:38:32SENT TO ELECTRIC UNDER $5000 BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-24 Cont ID  
Sent By dharvey Date 2013-08-24 Time 11:12 Rev Time 0.00
Received By dharvey Date 2013-08-20 Time 14:13 Sent To  
Notes
2013-08-24 11:09:14IN DENIED UNDR "I"
 CONTRACTOR CALLED AND ADVISED NOTES ARE IN THE SYSTEM
2013-08-20 14:13:41TO ELEC < $5K
  