| Plan Review Stops For Permit 13080677 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2013-08-23 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2013-08-23 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2013-08-23 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2013-08-23 11:20:04 | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE | | | OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. | | | | | | TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM | | | BUILDING STRUCTURES. | | | | | | POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | | LOCATIONS. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-08-23 |
|
|
Cont ID |
|
| Sent By |
wjolin |
Date |
2013-08-23 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
wjolin |
Date |
2013-08-19 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2013-08-19 15:01:25 | ROUTED TO TEMPORARY TENTS |
|
|
|