Plan Review Details - Permit 13080650
Plan Review Stops For Permit 13080650
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-09-14 Cont ID  
Sent By jwitmer Date 2013-09-14 Time 11:57 Rev Time 0.00
Received By jwitmer Date 2013-09-14 Time 08;00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-02-04 Cont ID  
Sent By albarran Date 2014-02-04 Time 16:37 Rev Time 0.00
Received By albarran Date 2014-02-04 Time 16:37 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-01-06 Cont ID  
Sent By albarran Date 2014-01-06 Time 16:16 Rev Time 0.00
Received By albarran Date 2014-01-06 Time 16:16 Sent To I
Notes
2014-01-06 16:16:36VILLAS ON ANTIQUE ROW, BLDG. 5
 ELECTRICAL PLAN REVIEW NOTES FOR PERMITS: 13080647,
 13080648, 13080649, 13080650, 13080651, 13080653 AND
 13080654
  
 THE FOLLOWING NOTES ARE BASICALLY APPLICABLE TO ALL
 SEVEN (7) UNITS ALONG WITH THEIR SUBSEQUENT PERMIT
 NUMBERS AS DESCRIBED ABOVE:
 NOTE: THERE IS A CONFLICT IN THE UNIT DESIGNATIONS AS
 INDICATED ON THE ARCHITECTURAL DRAWINGS AND THE FIRE
 PROTECTION DRAWINGS.
 MOST OF THE ITEMS PREVIOUSLY ADDRESSED HAVE BEEN
 CORRECTED EXCEPT THE FOLLOWING:
  
 1. THE GROUNDING ELECTRODE CONDUCTOR SHALL BE SIZED AS
 PER NEC 250.66 FOR FOUR (4) 350 KCMILS AL
 2. NOTE 2 ADDRESSING THE SMOKE/CARBON MONOXIDE
 DETECTORS IS INCORRECT. THE DEVICES ARE TO BE
 INTER-CONNECTED WITHIN THE UNIT, BUT AT NO TIME TIED IN
 TO THE FIRE ALARM SYSTEM. NONE OF THE NOTES MENTION THE
 INSTALLATION TO BE AS PER MANUFACTURER?S INSTRUCTIONS.
 (NOTE: THE USE OF COMBINATION SMOKE/CO DETECTORS AND
 FOLLOWING PROPER PLACEMENT MAY REDUCE THE NUMBER OF
 DEVICES REQUIRED FOR COMPLIANCE)
 3. AFTER LOOKING THROUGH THE ENTIRE SET, I FOUND THE
 REFERENCES TO THE EASEMENT ON PAGE 2.1 OF THE UNITS,
 BUT PAGE E1.1 FOR THE SKY END UNIT HAS YET TO BE
 CORRECTED.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-09-17 Cont ID  
Sent By shill Date 2013-08-24 Time 08:13 Rev Time 0.00
Received By shill Date 2013-09-17 Time 08:13 Sent To  
Notes
2013-09-17 08:14:05SEE REVIEW BY DOUG HARVEY 13080654
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-07 Cont ID  
Sent By shill Date 2014-01-07 Time 09:10 Rev Time 0.00
Received By shill Date 2013-11-25 Time 12:57 Sent To  
Notes
2014-01-06 16:16:58SH
2013-11-25 12:57:39C-28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-02 Cont ID  
Sent By hmoser Date 2013-10-02 Time 08:26 Rev Time 0.00
Received By hmoser Date 2013-08-19 Time 14:59 Sent To  
Notes
2013-08-21 14:59:57INCOMING SENT TO C34. JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2014-02-12 Cont ID  
Sent By jwitmer Date 2014-02-12 Time 09:03 Rev Time 0.00
Received By jwitmer Date 2014-02-12 Time 09:02 Sent To  
Notes
2014-02-12 09:03:192/12/2014
 PLANS STAMPED FROM IMPACT FEES
 MU-2013-25245
 $17,080.70.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-09-14 Cont ID  
Sent By jwitmer Date 2013-09-14 Time 08:39 Rev Time 0.00
Received By jwitmer Date 2013-09-14 Time 08:39 Sent To  
Notes
2013-09-14 08:39:39BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-10-02 Cont ID  
Sent By hmoser Date 2013-10-02 Time 08:26 Rev Time 0.00
Received By hmoser Date 2013-10-02 Time 08:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-09-16 Cont ID  
Sent By lwagner Date 2013-09-16 Time 11:27 Rev Time 0.00
Received By lwagner Date 2013-09-09 Time 09:37 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2013-09-14 Cont ID  
Sent By jwitmer Date 2013-09-14 Time 08:57 Rev Time 0.00
Received By jwitmer Date 2013-09-14 Time 08:57 Sent To  
Notes
2013-09-14 08:57:35VILLAS ON ANTIQUE ROW
 ROOFING APPROVALS:
  
 SEE BLDG # 3 PRODUCT APPROVALS, PRODUCT APPROVALS FOR
 MASTER FOR BUILDINGS 3-7.
  
 ENTEGRA ROOF TILE
 ESTATE "S" TILE
 NOA 11-0510.02
 2-10D RING SHANK NAILS 37.4 MOMENT
  
 BORAL TILE SEAL
 NOA 12-1219.01
  
 O"HAGIN CLOAKED VENT TILE
 NOA 09-0316.04

Review Stop Z ZONING
Rev No 2 Status P Date 2014-01-07 Cont ID  
Sent By dmalone Date 2014-01-07 Time 09:10 Rev Time 0.00
Received By shill Date 2014-01-07 Time 09:10 Sent To  
Notes
2014-01-07 09:10:48OK PER D MALONE
 SEE REVIEW UNDER 13080647
 CO IS CONTINGENT UPON AND LINKED TO LDSPE PERMIT
 13080663 (PHASE V) APPROVED WITH CONDITIONAL APPROVAL
 REQUIRING PASSING FINAL LDSPE AND IRRIGATION
 INSPECTIONS.
  
  
2013-12-02 12:24:2912/2/13

Review Stop Z ZONING
Rev No 1 Status N Date 2014-02-12 Cont ID  
Sent By dmalone Date 2014-02-12 Time 09:02 Rev Time 0.00
Received By jwitmer Date 2014-02-12 Time 09:02 Sent To  
Notes
2013-08-28 14:43:128/28/13


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved