| 2013-09-03 15:34:01 | ***CORRECTIONS*** |
| | |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE |
| | ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER |
| | FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED. |
| | THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET |
| | AT |
| | |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ |
| | INSTALLATION.PDF |
| | |
| | 2ND REVIEW, SUBMITTED BUT NOT ALL COLUMNS WERE |
| | COMPLETED. PLEASE COMPLETE THE FOLLOWING COLUMNS: WALL |
| | PRESSURE, SHUTTER GLASS SEPARATION, SPAN (THIS IS BLADE |
| | LENGTH OR ANCHOR TO ANCHOR, SHOULD BE ONE DIMENSION, |
| | NOT TWO), AND EDGE DISTANCE. |
| | |
| | ACCORDIONS ARE INSTALLED VERTICALLY (PANELS CAN BE |
| | INSTALLED HORIZONTALLY OR VERTICALLY, ANCHOR TO |
| | ANCHOR). |
| | |
| | SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE WITH |
| | ANCHOR CHART, SEE SHEET 7 (CONNECTION TYPES ARE NAMED 1 |
| | THROUGH 8). |
| | |
| | 2. PROVIDE THE COVER SHEET FOR THE FLORIDA STATE |
| | PRODUCT APPROVAL, FAC9N-3. THIS IS AVAILABLE AT |
| | WWW.FLORIDABUILDING.ORG. THIS WILL INCLUDE THE APPROVAL |
| | NUMBER AND THE STATUS, WHICH SHOULD BE "APPROVED." |
| | |
| | NOT ADDRESSED |
| | |
| | 3. TWO DIFFERENT EVALUATION REPORTS PROVIDED. THE |
| | INSTALLATION SCHEDULE OR A REVISED FLOOR PLAN SHOULD |
| | INDICATE WHICH OF THE PRODUCTS IS PROPOSED IN EACH |
| | LOCATION. |
| | |
| | NOT ADDRESSED. |
| | |
| | NEW COMMENT: |
| | |
| | 4. WHEN RESUBMITTING, PLEASE PUT THE NAME OF THE |
| | CONTRACTOR ON THE RESUBMITTAL FORM ON THE LINE |
| | "CONTRACTOR." IN THIS CASE, THE CONTRACTOR IS A |
| | COMPANY, SO SHOULD BE THE COMPANY NAME, NOT THE |
| | QUALIFIER. THIS WILL HELP KEEP YOUR PLANS FROM BEING |
| | MISFILED. |