| Plan Review Stops For Permit 13080639 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2013-10-30 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-10-30 |
Time |
19:19 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-10-30 |
Time |
19:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2013-10-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-10-26 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-10-26 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2013-10-26 16:57:04 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | [email protected] | | | | | | 1. SPECIFY FSTENER EMBEDMENT FBC 1609. | | | | | | AN ATTEMPT WAS MADE TO REACH THE ENGINEER IN ORDER TO | | | REDLINE THIS PLAN. HOWEVER, THE ENGINEER'S TITLE BLOCK | | | WHICH IS REQUIRED BY FS 471 IS NOT INCLUDED ON THE | | | PLAN. REVISE PLANS TO INCLUDE ALL INFORMATION REQUIRED. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2013-08-24 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-08-24 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-08-24 |
Time |
10:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2013-10-28 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2013-10-28 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2013-10-28 |
Time |
09:58 |
Sent To |
I |
|
| Notes |
| 2013-10-28 10:15:20 | SENT TO SH DESK | | 2013-10-28 09:59:25 | RECEIVED A CALL FROM THE QUALIFIER CLAIMING TO HAVE | | | INCLUDED ALL THE ITEMS PREVIOUSLY REQUESTED ON THE | | | SUBMITTAL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2013-10-22 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2013-10-22 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2013-10-22 |
Time |
11:57 |
Sent To |
I |
|
| Notes |
| 2013-10-22 11:58:23 | NONE OF THE ITEMS PREVIOUSLY REQUESTED HAVE BEEN | | | SUBMITTED. SENT TO SH DESK. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2013-08-24 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-08-24 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-08-24 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2013-08-24 10:25:51 | WHAT IS A "STRUCTIAL" ENGINEER? PLEASE IDENTIFY WIND | | | SPEED AND VERIFY WINDLOAD COMPLIANCE WITH FBC-B1609 | | | FROM A FLORIDA REGISTERED ENGINEER. | | | ELECTRICAL DETAILS NOT SHOWN | | | PROVIDE DISCONNECT PER NEC ARTICLE 600 | | | PROVIDE COMPLIANCE VERIFICATION WITH FBC-EC 505.2 | | | ELECTRICAL SUPPLY AND CONNECTIONS TO SIGN TO BE SHOWN | | | FOR CODE COMPLIANCE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-10-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-10-26 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-10-21 |
Time |
13:32 |
Sent To |
|
|
| Notes |
| 2013-10-24 11:54:25 | TO SH DESK | | | | | 2013-10-21 13:33:14 | INCOMING SENT TO <$5K ELECTRICAL. JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-08-24 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-08-24 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-08-19 |
Time |
11:57 |
Sent To |
|
|
| Notes |
| 2013-08-31 09:33:12 | 8/31 FILED DENIED BIN 'B' SH | | 2013-08-24 10:27:25 | FILED IN DENIED UNDER "L" | | 2013-08-19 11:57:41 | ROUTED TO ZONING |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2013-08-22 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2013-08-22 |
Time |
11:59 |
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2013-08-22 |
Time |
11:59 |
Sent To |
E |
|
| Notes |
|
|