Plan Review Details - Permit 13080622
Plan Review Stops For Permit 13080622
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-10-03 Cont ID  
Sent By rmcdouga Date 2013-10-03 Time 11:30 Rev Time 0.00
Received By rmcdouga Date 2013-10-03 Time 10:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2013-10-03 Cont ID  
Sent By dkittred Date 2013-10-03 Time 10:05 Rev Time 0.00
Received By rmcdouga Date 2013-10-03 Time 10:05 Sent To  
Notes
2013-10-03 10:07:36ZONING ENTERED NOTES IN WRONG REVIEW STOP BY MISTAKE.
 RM
2013-08-22 16:21:43PLANNING & ZONING:
 8/22/2013
  
 ALL INTERIOR WORK, LESS THAN 50% STRUCTURE VALUE.
  
 DANIELLE J. KITTREDGE
 SENIOR PLANNER

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-10-03 Cont ID  
Sent By rmcdouga Date 2013-10-03 Time 15:50 Rev Time 0.00
Received By rmcdouga Date 2013-10-03 Time 12:34 Sent To  
Notes
2013-10-03 15:50:54REDLINED CORRECTIONS ON PLAN

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-09-16 Cont ID  
Sent By dharvey Date 2013-09-16 Time 16:07 Rev Time 0.00
Received By dharvey Date 2013-09-16 Time 16:07 Sent To  
Notes
2013-09-16 16:09:59FIRST REVIEW - 9-16-13
  
 1. PROVIDE INTERSYSTEM BONDING BAR AT SERVICE PER NEC
 250.94
 2.PLEASE NOTE ALL NEW RECEPTS TO BE TAMPER RESISTANT
 TYPE PER NEC 406.11
 3. PLEASE NOTE THAT AFCI BREAKERS ARE REQUIRED TO
 PROTECT ALL NEW OUTLETS PER NEC 210.12B
 PLEASE SHOW CIRCUITS ON FLOOR PLAN FOR CLARITY
  
 VB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-15 Cont ID  
Sent By rmcdouga Date 2013-10-15 Time 13:58 Rev Time 0.00
Received By rmcdouga Date 2013-10-10 Time 18:53 Sent To  
Notes
2013-10-10 18:54:01SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-03 Cont ID  
Sent By rmcdouga Date 2013-10-03 Time 18:17 Rev Time 0.00
Received By rmcdouga Date 2013-08-16 Time 16:29 Sent To  
Notes
2013-08-16 16:36:14INCOMING SENT TO R08 BOX. JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-10-15 Cont ID  
Sent By rmcdouga Date 2013-10-15 Time 13:58 Rev Time 0.00
Received By rmcdouga Date 2013-10-15 Time 13:17 Sent To  
Notes
2013-10-15 14:00:47SUBMIT CORRECTED ENERGY CALCULATION FORM 405-10.
 HEATING BTUS TOO HIGH AND NOT A HEAT PUMP SYSTEM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-10-03 Cont ID  
Sent By rmcdouga Date 2013-10-03 Time 18:16 Rev Time 0.00
Received By rmcdouga Date 2013-10-03 Time 15:51 Sent To  
Notes
2013-10-03 16:24:222010 FBC
  
 DENIED BY MECHANICAL
  
 1) THE EQUIPMENT SIZING CALCULATIONS RECOMMEND A 3 TON
 SYSTEM (32,620 BTU) AND THE ENERGY CALCULATIONS SPECIFY
 A 3.5 TON SYSTEM (42,000 BTU). THESE TWO DOCUMENTS
 SHOULD MATCH. PLEASE CLARIFY. 2010 FBC ENERGY
 CONSERVATION SECTION 101.4.7.1.2 NOTE: IT APPEARS THAT
 THE ORIGINAL ENERGY CALCULATIONS WERE WORST CASE AND
 THE NEW ONES ARE SITE SPECIFIC AS REQUIRED BY THE 2010
 ENERGY CODE.
  
 2) SUBMIT TWO COPIES OF AN EQUIPMENT SCHEDULE
 SPECIFYING THE MODEL NUMBERS AND OVERCURRENT PROTECTION
 REQUIREMENTS. YOU CAN USE THE CITY OF WEST PALM BEACHES
 A/C CHANGE OUT FORM FOR THIS. THE EQUIPMENT MUST MATCH
 THE SIZING CALCULATIONS. 2010 FBC ENERGY CONSERVATION
 SECTION 101.4.3 & TABLE 101.4.1
  
 3) BECAUSE THE DUCT WORK IS BEING REPLACED WITH NEW,
 THE INSTALLATION SHALL COMPLY WITH FBCR M1602.4 FOR
 BALANCED RETURN AIR. 2010 FBC ENERGY CONSERVATION
 SECTION 101.4.3 & TABLE 101.4.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-10-03 Cont ID  
Sent By rmcdouga Date 2013-10-03 Time 11:37 Rev Time 0.00
Received By rmcdouga Date 2013-10-03 Time 10:07 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2013-08-22 Time   Rev Time 0.00
Received By dkittred Date 2013-08-22 Time 14:00 Sent To  
Notes
2013-08-22 16:24:32PLANNING & ZONING:
 8/22/2013
  
 ALL INTERIOR WORK, LESS THAN 50% STRUCTURE VALUE.
  
 DANIELLE J. KITTREDGE
 SENIOR PLANNER