Plan Review Details - Permit 13080577
Plan Review Stops For Permit 13080577
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-29 Cont ID  
Sent By shill Date 2013-08-29 Time 14:10 Rev Time 0.00
Received By jwitmer Date 2013-08-29 Time 11:01 Sent To  
Notes
2013-08-29 13:07:30BUILDING PLAN REVIEW
 PERMIT: 13080577
 ADD: 901 NORTHPOINT PARKWAY # 400-404
 CONT: NICK RAICHBUILDING CORP
 TEL: (561)659-9347
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: AUGUST 29/ 2013
 ACTION: DENIED
  
 1) SHEET A1 INDICATES A ONE HOUR TENANT SEPERATION
 WALL, PLEASE SEE 2010 FBC-B TABLE 508.4 NON SPRINKLERED
 BUILDING A 2 HOUR OCCUPANCY WALL IS REQUIRED. UPDATE
 PLANS TO PROVIDE TWO HOUR FIRE SEPERATION TO OTHER
 OCCUPANCIES. THE PERMIT APPLICATION INDICATES SUITES
 400-404, WHICH SUITE IS THE WORK BEING COMPLETED IN,
 ONLY ONE OF THE OCCUPANCY WALLS MAY NEED TO BECOME A 2
 HOUR OCCUPANCY SEPERATION WALL.
  
 2) LS 1 THE EXISTING OFFICE APPEARS TO HAVE BEEN PART
 OF THE OTHER TENANT SPACE, THESE WALLS WILL ALSO BE
 REQUIRED TO BE FIRE RATED TO THE DECK ABOVE.
  
 3) PLEASE PROVIDE A DETAIL SHOWING COMPLIANCE WITH 2010
 FBC-B 714.1 WALL TO ROOF JOINT, PROVIDE UL OR GYPSUM
 ASSOC ASSEMBLY OR OTHER NATIONALLY RECONIZED TESTING
 AGENCY.
  
 4) LS SHEET PLEASE PROVIDE THE SQ FT FOR CLASSROOM # 1
 & 2, IT APPEARS THESE CLASSROOMS ARE OVER THE 250 SQ FT
 AND WILL NEED TO COMPLY WITH
 2010 FBC-B 1029.4.1.
  
 5) THE 2 RESTROOMS ARENOT ACCESSIBLE RESTROOMS, PLEASE
 SEE 2010 FL ACCESSIBLITY CODE AND DISPROPORTIONATE
 COST, $960.00 DOLLARS WILL NEED TO BE PROVIDED IN
 UPDATING THE EXISTING RESTROOMS TO BE MORE ACCESSIBLE,
 ONCE THE $960.00 DOLLARS IS SPENT THE CLIENT DOES NOT
 NEED TO DO ANY MORE UNDER THIS PERMIT FOR
 ACCESSIBILITY, THE DISPROPORTIONATE LIMIT WAS REACHED.
 ITEMIZE HOW THESE FUNDS WILL BE SPENT IN ACCESSBLE
 UPGRADES.
  
 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2013-08-19 Cont ID  
Sent By dharvey Date 2013-08-19 Time 16:02 Rev Time 0.00
Received By dharvey Date 2013-08-19 Time 15:13 Sent To  
Notes
2013-08-19 16:02:20NO ELECTRICAL PLAN HAS BEEN PROVIDED FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-08-22 Cont ID  
Sent By wjolin Date 2013-08-22 Time 10:04 Rev Time 0.00
Received By wjolin Date 2013-08-21 Time 18:39 Sent To  
Notes
2013-08-21 18:44:17901 NORTHPOINT PARKWAY - #400
 PERMIT #13080577
 MASTER #13060868
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 AN OPEN MASTER PERMIT (#13060868) ALREADY EXISTS FOR
 THIS LOCATION. IS THIS PERMIT TO BE VOIDED?
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE, NOT THE 2007 EDITION.
  
 PER SECTION 8.3.2.4, EACH FIRE BARRIER SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE
 AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 PER SECTION 8.3.5.1, PENETRATIONS THROUGH A FIRE-RATED
 WALL ASSEMBLY SHALL BE PROTECTED BY A FIRESTOP SYSTEM
 OR DEVICE.
  
 PROVIDE ADDITIONAL EMERGENCY LIGHTING; ONLY ONE FIXTURE
 IS CURRENTLY SHOWN. EMERGENCY ILLUMINATION SHALL BE
 PROVIDED FOR A MINIMUM OF 1.5 HOURS IN THE EVENT OF
 FAILURE OF NORMAL LIGHTING. EMERGENCY LIGHTING
 FACILITIES SHALL BE ARRANGED TO PROVIDE INITIAL
 ILLUMINATION THAT IS NOT LESS THAN AN AVERAGE OF 1
 FT-CANDLE AND, AT ANY POINT, NOT LESS THAN 0.1
 FT-CANDLE, MEASURED ALONG THE PATH OF EGRESS AT FLOOR
 LEVEL.
  
 THE EXISTING FIRE BARRIER BETWEEN THE EDUCATIONAL
 OCCUPANCY AND THE BUSINESS OCCUPANCY (ADJACENT TENANT)
 NEEDS TO BE A 2-HOUR FIRE BARRIER. DURING A FIRE
 INSPECTION, MR. VINCE KENDRICK INDICATED THIS WAS A
 2-HOUR FIRE BARRIER. THE PLAN INDICATES THIS WALL TO
 ONLY BE A 1-HOUR FIRE BARRIER. PLEASE VERIFY THE FIRE
 RATING OF THE EXISTING WALL.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-07 Cont ID  
Sent By hmoser Date 2013-09-07 Time 07:07 Rev Time 0.00
Received By hmoser Date 2013-08-15 Time 10:29 Sent To  
Notes
2013-08-19 10:31:12B05
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-08-29 Cont ID  
Sent By jwitmer Date 2013-08-29 Time 11:01 Rev Time 0.00
Received By jwitmer Date 2013-08-29 Time 11:01 Sent To  
Notes
2013-08-29 11:01:49BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-09-07 Cont ID  
Sent By hmoser Date 2013-09-07 Time 07:07 Rev Time 0.00
Received By hmoser Date 2013-09-07 Time 06:57 Sent To  
Notes
2013-09-07 07:07:02PLANS DENIED
 THERE ARE NO MECHANICAL PLANS. DON'T KNOW IF THERE IS A
 FIRE DAMPER OR IF ONE IS NEEDED.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-08-30 Cont ID  
Sent By lwagner Date 2013-08-30 Time 14:47 Rev Time 0.00
Received By lwagner Date 2013-08-30 Time 14:39 Sent To  
Notes
2013-08-30 14:48:03NO PLUMBING SHOWN AT THIS TIME.

Review Stop Z ZONING
Rev No 1 Status N Date 2013-08-21 Cont ID  
Sent By ajones Date 2013-08-21 Time 15:24 Rev Time 0.00
Received By ajones Date 2013-08-21 Time 15:24 Sent To  
Notes
***NONE***