| 2013-08-20 07:56:45 | BUILDING PLAN REVIEW |
| | PERMIT: 13080554 |
| | ADD: 1400 CENTREPARK BLVD, SUITE # 1000 |
| | CONT: CHANDLER CONSTRUCTION |
| | TEL: (561)791-6934 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUESDAY AUGUST 20/ 2013 |
| | |
| | ACTION: PROVISO REVISION REQUIRED |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) NEITHER SHEET A2 FLOOR/ CEILING PLAN, A4 LIFE SAFETY |
| | PLAN NOR E2.1 LIGHTING PLAN SHOW COMPLIANCE WITH: |
| | 1A) 2010 FBC-B 1006.3.7 |
| | WHERE EMERGENCY LIGHTING FACILITIES ARE REQUIRED BY |
| | SECTION 1006.2, THE EXIT SIGNS SHALL BE ILLUMINATED BY |
| | THE EMERGENCY LIGHTING FACILITIES. THE LEVEL OF |
| | ILLUMINATION OF THE EXIT SIGN SHALL BE AT THE LEVELS |
| | PROVIDED IN ACCORDANCE WITH SECTION 1006.3.5 FOR THE |
| | REQUIRED EMERGENCY LIGHTING TIME DURATION AS SPECIFIED |
| | IN SECTION 1006.2.3.1, BUT SHALL BE PERMITTED TO |
| | DECLINE TO 60 PERCENT OF THE ILLUMINATION LEVEL AT THE |
| | END OF THE EMERGENCY LIGHTING TIME DURATION. |
| | |
| | 1B) 2010 FBC-B 1006.3.8 |
| | WHERE THE DIRECTION OF TRAVEL TO REACH THE NEAREST EXIT |
| | IS NOT APPARENT, A DIRECTIONAL SIGN COMPLYING WITH |
| | SECTIONS 1006.3.5 OR 1006.3.6 READING ?EXIT,? OR A |
| | SIMILAR DESIGNATION WITH A DIRECTIONAL INDICATOR |
| | SHOWING THE DIRECTION OF TRAVEL SHALL BE PLACED IN |
| | EVERY LOCATION. DIRECTIONAL SIGNS SHALL BE LISTED. |
| | |
| | C) 2010 FBC-B 1006.3.4 EXIT STAIR DOOR OR TACTILE |
| | SIGNAGE. |
| | TACTILE SIGNAGE STATING ?EXIT? AND COMPLYING WITH |
| | ICC/ANSI A117.1, AMERICAN NATIONAL STANDARD FOR |
| | ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES, SHALL |
| | BE INSTALLED ADJACENT TO THE LATCH SIDE OF THE DOOR 60 |
| | INCHES (1524 MM) ABOVE THE FINISHED FLOOR TO THE CENTER |
| | LINE OF THE SIGN. |
| | |
| | D) 2010 FBC-B 1006.3.3 |
| | EVERY REQUIRED SIGN SHALL BE LOCATED AND OF SUCH SIZE, |
| | DISTINCTIVE COLOR AND DESIGN AS TO BE READILY VISIBLE |
| | AND SHALL PROVIDE CONTRAST WITH INTERIOR FINISH OR |
| | OTHER SIGNS. NO EQUIPMENT THAT IMPAIRS VISIBILITY OF AN |
| | EXIT SIGN SHALL BE PERMITTED, NOR SHALL THERE BE ANY |
| | BRIGHTLY ILLUMINATED SIGN OR OBJECT IN OR NEAR THE LINE |
| | OF VISION OF THE REQUIRED EXIT SIGN OF SUCH A CHARACTER |
| | AS TO DETRACT ATTENTION FROM THE EXIT SIGN. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |