Plan Review Details - Permit 13080547
Plan Review Stops For Permit 13080547
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-09-27 Cont ID  
Sent By jwitmer Date 2013-09-27 Time 11:04 Rev Time 0.00
Received By jwitmer Date 2013-09-27 Time 09:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-29 Cont ID  
Sent By jwitmer Date 2013-08-29 Time 10:37 Rev Time 0.00
Received By jwitmer Date 2013-08-29 Time 10:37 Sent To  
Notes
2013-09-27 10:05:25BUILDING PLAN REVIEW
 PERMIT: 13080547
 ADD: 509 S OLIVE AVE SUITE # ????
 CONT: MVP
 TEL: (561)214-0226
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE:SEPT 27/ 2013
 ACTION: PROVISO
 1) SHEET # 1, PLEASE SEE RESTROOM REVIEW DOORS IN
 SERIES 2010 FL ACCESS CODE 404.2.6. THE DISTANCE
 BETWEEN TWO HINGED OR PIVOTED DOORS IN SERIES AND GATES
 IN SERIES SHALL BE 48 INCHES (1220 MM) MINIMUM PLUS THE
 WIDTH OF DOORS OR GATES SWINGING INTO THE SPACE.
  
 2010 FL ACCESSIBILITY CODE 603.2.3 DOOR SWING.
 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE
 PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE.
 EXCEPTIONS:
 2. WHERE THE TOILET ROOM OR BATHING ROOM IS FOR
 INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING WITH
 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE
 DOOR SWING, DOORS SHALL BE PERMITTED TO SWING INTO THE
 CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY
 FIXTURE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
2013-08-29 10:56:54BUILDING PLAN REVIEW
 PERMIT: 13080547
 ADD: 509 S OLIVE AVE SUITE # ????
 CONT: MVP
 TEL: (561)214-0226
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: AUGUST 29/ 2013
 ACTION: DENIED
  
 1) THIS PLANS CANNOT BE ISSUED UNTIL PERMIT # 13070893
 IS ISSUED.
  
 2) THE PLANS ARE NOT CLEAR AS IF THE RESTROOM/ BATHROOM
 IS TO BE USED AS A SINGLE USER SINCE THE SHOWER DOES
 NOT HAVE ITS OWN PRIVACY IF THE HALLWAY DOOR IS NOT
 LOCKED.
  
 3) THE SHOWER IS NOT SHOWN AS A ACCESSIBLE SHOWER 2010
 FL ACCESS CODE 2010 FBC-B 213.2.1./ 608.2.1 OR 608.2.3.
 PROVIDE DETAIL WITH SEAT, GRAB BARS & CONTROLS.
  
 4) PLEASE REVIEW DOORS IN SERIES 2010 FL ACCESS CODE
 404.2.6.
  
  
  
  
 3)
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-10-17 Cont ID  
Sent By dharvey Date 2013-10-17 Time 15:34 Rev Time 0.00
Received By dharvey Date 2013-10-17 Time 14:59 Sent To I
Notes
2013-10-17 15:39:47THESE PLANS WERE APPROVED WITH THE FOLLOWING
 EXCEPTIONS/PROVISIONS WHICH WILL BE LOOKED FOR AT THE
 TIME OF THE NECESSARY INSPECTIONS.
 1. AS PER NEC 210.62, AN OUTLET IS REQUIRED FOR SHOW
 WINDOW LIGHTING AS INDICATED ON THE APPROVED PLANS.
 2. AS PER NEC 600.5, EVERY COMMERCIAL ESTABLISHMENT
 SHALL HAVE A DEDICATED OUTLET FOR SIGNAGE WITHIN CLOSE
 PROXIMITY OF PEOPLE ENTRY DOORS. SEE APPROVED DRAWINGS
 AS MARKER ACCORDINGLY.
  
 FILE SENT TO SH DESK BY: MA

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-09-16 Cont ID  
Sent By dharvey Date 2013-09-16 Time 15:10 Rev Time 0.00
Received By dharvey Date 2013-09-16 Time 15:10 Sent To  
Notes
2013-09-16 15:12:13FIRST REVIEW - 9-16-13
  
 SINCE IT DOES NOT SHOW A FOOTPRINT OF THE WHOLE
 BUILDING ON THE PLANS, IT IS ASSUMED THAT THIS SPACE IS
 PART OF A LARGER BUILDING GREATER THAN 5000 SQ FT,
 THERFORE LIGHTING CONTROLS ARE REQUIRED.
  
 VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2013-08-24 Cont ID  
Sent By wjolin Date 2013-08-24 Time 13:04 Rev Time 0.00
Received By wjolin Date 2013-08-24 Time 12:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-18 Cont ID  
Sent By shill Date 2013-10-18 Time 11:42 Rev Time 0.00
Received By shill Date 2013-09-17 Time 08:49 Sent To  
Notes
2013-09-18 08:49:20SENT TO B3 SHELF FOR REVIEW. JG.,

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-16 Cont ID  
Sent By shill Date 2013-09-16 Time 17:37 Rev Time 0.00
Received By shill Date 2013-08-15 Time 17:33 Sent To  
Notes
2013-08-16 17:34:03B03

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-09-27 Cont ID  
Sent By jwitmer Date 2013-09-27 Time 11:05 Rev Time 0.00
Received By jwitmer Date 2013-09-27 Time 11:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-09-20 Cont ID  
Sent By lwagner Date 2013-09-20 Time 09:12 Rev Time 0.00
Received By lwagner Date 2013-09-19 Time 14:27 Sent To  
Notes
2013-09-20 09:12:26***PROVISO***
 1. THE RESTROOM WILL BE REQUIRED TO BE A MINIMUM OF
 7'-1" WIDE TO ACHIEVE THE REQUIRED 60" CLEAR SPACE FOR
 THE WATER CLOSET. FBC ACCESSIBILITY CODE 2010 604.3.1
 FBC ACCESSIBILITY CODE 2010 604.3.2 THE LAVATORY WILL
 NOT BE PERMITTED IN THE 60" SPACE.
  
 2. FBC ACCESSIBILITY CODE 606.3 HEIGHT: LAVATORIES AND
 SINKS SHALL BE INSTALLED WITH THE FRONT OF THE HIGHER
 OF THE RIM OR COUNTER SURFACE 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-08-30 Cont ID  
Sent By lwagner Date 2013-08-30 Time 14:30 Rev Time 0.00
Received By lwagner Date 2013-08-30 Time 09:28 Sent To  
Notes
2013-08-30 14:29:35FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
  
 1. SHEET 1 SHOWS THE RESTROOM AS 6'- 10" INSIDE. THE
 MINIMUM SIZE FOR THIS CONFIGURATION WOULD BE 7'- 1".
 FBC ACCESSIBILITY CODE 2010 604.3.1 SIZE. CLEARANCE
 AROUND A WATER CLOSET SHALL BE 60 INCHES (1525 MM)
 MINIMUM MEASURED PERPENDICULAR FROM THE SIDE WALL AND
 56 INCHES (1420 MM) MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL.
 FBC ACCESSIBILITY CODE 2010 604.3.2 THE LAVATORY WILL
 NOT BE PERMITTED IN THE 60" SPACE.
 PLEASE ALSO SEE FIGURE 604.8.1.6.
  
 2. SHEET 1 THE SHOWER WILL BE REQUIRED TO BE
 ACCESSIBLE.
 FBC ACCESSIBILITY CODE 2010 608.1 - 608.8
  
 3. SHEET 1 THE SMALL SINK WILL BE REQUIRED TO HAVE THE
 COUNTER TOP NO HIGHER THAN 34" MAX.
 FBC ACCESSIBILITY CODE 2010 606.3
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  