Plan Review Details - Permit 13080516
Plan Review Stops For Permit 13080516
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-09-24 Cont ID  
Sent By WITMER Date 2013-09-24 Time 17:59 Rev Time 0.00
Received By jwitmer Date 2013-09-24 Time 17:02 Sent To  
Notes
2013-09-24 17:47:46BUILDING PROVISO:
 SHEET A2.01 & A3.01
 DOOR # 4
 EXIT PASSAGEWAY
 2010 FBC-B 402.4.5.1.
 1 HOUR FIRE RATED DOOR ASSEMBLY
 402.4.5.1 EXIT PASSAGEWAYS.
 WHERE EXIT PASSAGEWAYS PROVIDE A SECONDARY MEANS OF
 EGRESS FROM A TENANT SPACE,
 DOORWAYS TO THE EXIT PASSAGEWAY SHALL BE PROTECTED BY
 1-HOUR FIRE DOOR ASSEMBLIES THAT
 ARE SELF- OR AUTOMATIC-CLOSING BY SMOKE DETECTION IN
 ACCORDANCE WITH SECTION 715.4.8.3
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-21 Cont ID  
Sent By jwitmer Date 2013-08-21 Time 14:01 Rev Time 0.00
Received By jwitmer Date 2013-08-21 Time 12:59 Sent To  
Notes
2013-08-21 14:01:37BUILDING PLAN REVIEW
 PERMIT: 13080516
 ADD: 721 VILLAGE BLVD SUITE 701 B-F
 CONT: PAGE CONTRACTING
 TEL: (561)868-4561
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: 8/21/2013
 ACTION: DENIED
  
 1) SHEET A2.1 INDICATES A NEW EIXT PASSAGE WAY (EXIT
 CORRIDOR), THE PLANS INDICATE A DOOR TAG TYPE 4, THE
 DOOR SCHEDULE FOUND ON A3.01 DOES NOT INDICATE
 COMPLIANCE WITH:
  
  
 1A) 2010 1023.5 OPENINGS AND PENETRATIONS. EXIT
 PASSAGEWAY OPENING PROTECTIVES SHALL BE IN ACCORDANCE
 WITH THE REQUIREMENTS OF SECTION 715.
  
 1B) OPEN MALLS 402.4.5.1 EXIT PASSAGEWAYS. WHERE EXIT
 PASSAGEWAYS PROVIDE A SECONDARY MEANS OF EGRESS FROM A
 TENANT SPACE, DOORWAYS TO THE EXIT PASSAGEWAY SHALL BE
 PROTECTED BY 1-HOUR FIRE DOOR ASSEMBLIES THAT ARE SELF-
 OR AUTOMATIC-CLOSING BY SMOKE DETECTION IN ACCORDANCE
 WITH SECTION 715.4.8.3.
  
 1C) 2010 FBC-B TABLE 715.4. EXIT PASSAGEWAY WALLS 1 HR
 OPENING PROTECTIVES 1 HOUR. WHERE THERE IS DIFFERENCE
 BETWEEN TWO CODES THE MOST RESTRICTIVE IS USED.
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS,
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-09-16 Cont ID  
Sent By dharvey Date 2013-09-16 Time 14:31 Rev Time 0.00
Received By dharvey Date 2013-09-16 Time 14:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-10-02 Cont ID  
Sent By wjolin Date 2013-10-02 Time 15:17 Rev Time 0.00
Received By wjolin Date 2013-10-02 Time 15:12 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-09-28 Cont ID  
Sent By JOLIN Date 2013-09-28 Time 09:01 Rev Time 0.00
Received By wjolin Date 2013-09-28 Time 08:51 Sent To  
Notes
2013-09-28 08:56:11721 VILLAGE BOULEVARD
 PERMIT #13080516
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT:
 FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION
 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES
 SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE
 DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE
 SPRINKLERS. AFTER THE BUILDING PERMIT HAS BEEN ISSUED,
 THE SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-08-20 Cont ID  
Sent By wjolin Date 2013-08-20 Time 18:11 Rev Time 0.00
Received By wjolin Date 2013-08-20 Time 17:38 Sent To  
Notes
2013-08-20 18:11:31721 VILLAGE BOULEVARD
 PERMIT #13080516
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A3.01: THE FOUR DOOR OPENINGS (DOOR TAG #4) INTO
 THE FIRE RATED EXIT CORRIDOR SHALL HAVE A FIRE
 RESISTANCE RATING OF AT LEAST 45 MINUTES. DOORS SHALL
 BE SELF-CLOSING AND POSITIVE LATCHING.
  
 SHEET M1: PROVIDE DUCT SMOKE DETECTION FOR NEW 6.5 TON
 AIR HANDLER.
  
 SHEET E1: INSUFFICIENT EMERGENCY LIGHTING PROVIDED IN
 EXIT CORRIDOR.
  
 FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION
 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES
 SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE
 DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE
 SPRINKLERS. AFTER THE BUILDING PERMIT HAS BEEN ISSUED,
 THE SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-10-02 Cont ID  
Sent By rmcdouga Date 2013-10-02 Time 16:44 Rev Time 0.00
Received By rmcdouga Date 2013-10-01 Time 13:55 Sent To  
Notes
2013-10-02 14:03:56SENT TO W JOLIN
  
  
 PROCESSED OUT PLANS / 10/2/13 RM

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-09-30 Cont ID  
Sent By hmoser Date 2013-09-30 Time 11:25 Rev Time 0.00
Received By hmoser Date 2013-09-18 Time 18:10 Sent To  
Notes
2013-09-19 18:10:34C06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-17 Cont ID  
Sent By shill Date 2013-09-17 Time 07:11 Rev Time 0.00
Received By shill Date 2013-08-14 Time 18:44 Sent To  
Notes
2013-08-14 18:44:37C05
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-09-30 Cont ID  
Sent By MOSER Date 2013-09-30 Time 11:25 Rev Time 0.00
Received By hmoser Date 2013-09-30 Time 11:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-09-09 Cont ID  
Sent By hmoser Date 2013-09-09 Time 11:45 Rev Time 0.00
Received By hmoser Date 2013-09-09 Time 10:42 Sent To  
Notes
2013-09-09 11:45:07PLANS DENIED
 1) PROVIDE DUCT WORK ON 6.5 TON RTU ON PLANS.
 PER SECTION 107 FBC 2010.
 2) REFER TO SECTION 606.2.1 SUPPLY SYSTEMS
 ( DUCT DETECTOTS ) 606.3 INSTALLATION AND
 606.4.1 SUPERVISION. 2010 FBC (M)
 3) REFER TO SECTION 304.12 AREA SERVIED
 ( NUMBER RTU ) 2010 FBC (M)
 4) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROLS
 (FOR OUTSIDE AIR AND EXHAUST) 2010 FLORIDA ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-09-20 Cont ID  
Sent By WAGNER Date 2013-09-20 Time 14:01 Rev Time 0.00
Received By lwagner Date 2013-09-20 Time 13:28 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-08-16 Cont ID  
Sent By lwagner Date 2013-08-16 Time 12:46 Rev Time 0.00
Received By lwagner Date 2013-08-16 Time 11:03 Sent To  
Notes
2013-08-16 12:46:28FBC 2010 EXISTING BUILDING CODE
 FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. SUITE 107C WILL HAVE AN OCCUPANT LOAD OF OVER 15
 OCCUPANTS. BUSINESS/ MERCANTILE OCCUPANCIES WITH OVER
 15 OCCUPANTS REQUIRE A HIGH/LO DRINKING FOUNTAIN.
 PLUMBING TABLE 403.1 (E) (F)
 FBC ACCESSIBILITY CODE 2010 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  