Plan Review Details - Permit 13080496
Plan Review Stops For Permit 13080496
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-03-06 Cont ID  
Sent By jgomez Date 2014-03-06 Time 11:31 Rev Time 0.00
Received By jgomez Date 2014-03-05 Time 11:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-28 Cont ID  
Sent By jgomez Date 2014-01-28 Time 14:30 Rev Time 0.00
Received By jgomez Date 2014-01-28 Time 14:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-16 Cont ID  
Sent By jgomez Date 2013-08-16 Time 10:19 Rev Time 0.00
Received By jgomez Date 2013-08-13 Time 11:07 Sent To  
Notes
2013-08-14 11:07:53SENT TO JULIO'S DESK FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2014-03-06 Cont ID  
Sent By jgomez Date 2014-03-06 Time 11:32 Rev Time 0.00
Received By jgomez Date 2014-03-06 Time 11:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-01-28 Cont ID  
Sent By jgomez Date 2014-01-28 Time 14:30 Rev Time 0.00
Received By jgomez Date 2014-01-28 Time 14:30 Sent To  
Notes
2014-01-28 14:51:01MECHANICAL REVIEW SECOND CHECKLIST.
 CODE: 2010 FBC.
  
  
 1- FLOOR PLAN LAYOUT SHOWN ON PLANS SUBMITTED DON'T
 MATCH FLOOR PLAN LAYOUT APPROVED FOR MASTER #13041122.
 SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 2- PROVIDE COMPLETE AND CLEAR SPECIFICATIONS FOR THE
 ATTACHMENT OF THE CONDENSING UNIT TO THE CONCRETE SLAB.
 SPECIFY THE STRAP SIZE AND HOW ARE THE THREE #14 SCREWS
 INSTALLED AS SPECIFIED ON CURRENT DETAIL. REQUIRED BY
 SEC. M1307.2.1 OF 2010 FBC-RESIDENTIAL. (REPEAT
 COMMENT. NOT ADDRESSED). ENGINEER IS ONLY STATING
 "SECURE CONDENSING UNIT TO CONCRETE PAD IN ACCORDANCE
 WITH FMC 9RESIDENTIAL) SECTION 1307.3.1". THIS RESPONSE
 DOESN'T ADDRESS HOW THE UNIT IS ATTACHED TO THE
 CONCRETE SLAB. THE ENGINEER OF RECORD IS THE ONE WHO
 DESIGNS HOW IS THE UNIT ATTACHED TO THE CONCRETE SLAB
 TO RESIST THE WIND LOADS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-08-19 Cont ID  
Sent By jgomez Date 2013-08-19 Time 10:19 Rev Time 0.00
Received By jgomez Date 2013-08-19 Time 14:31 Sent To  
Notes
2013-08-16 10:37:55RESIDENTIAL (R3) RENOVATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- RETURN AIR CAN'T BE TAKEN FROM THE KITCHEN. SEC.
 M1602.2 OF 2010 FBC-RESIDENTIAL.
  
 2- PROVIDE 2 COPIES OF PLANS WITH ENGINEER'S ORIGINAL
 SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTE.
  
 3- PROVIDE COMPLETE AND CLEAR SPECIFICATIONS FOR THE
 ATTACHMENT OF THE CONDENSING UNIT TO THE CONCRETE SLAB.
 SPECIFY THE STRAP SIZE AND HOW ARE THE THREE #14 SCREWS
 INSTALLED AS SPECIFIED ON CURRENT DETAIL. SEC.
 M1307.2.1 OF 2010 FBC-RESIDENTIAL.
  
 4- NEED A/C CONTRACTOR TO APPLY FOR THE MECHANICAL
 PERMIT.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712