Plan Review Details - Permit 13080496
| Plan Review Stops For Permit 13080496 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2014-03-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-03-06 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-03-05 |
Time |
11:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-01-28 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-01-28 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-01-28 |
Time |
14:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-08-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-08-16 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-08-13 |
Time |
11:07 |
Sent To |
|
|
| Notes |
| 2013-08-14 11:07:53 | SENT TO JULIO'S DESK FOR REVIEW. JG. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2014-03-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-03-06 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-03-06 |
Time |
11:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2014-01-28 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-01-28 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-01-28 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2014-01-28 14:51:01 | MECHANICAL REVIEW SECOND CHECKLIST. | | | CODE: 2010 FBC. | | | | | | | | | 1- FLOOR PLAN LAYOUT SHOWN ON PLANS SUBMITTED DON'T | | | MATCH FLOOR PLAN LAYOUT APPROVED FOR MASTER #13041122. | | | SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | | | 2- PROVIDE COMPLETE AND CLEAR SPECIFICATIONS FOR THE | | | ATTACHMENT OF THE CONDENSING UNIT TO THE CONCRETE SLAB. | | | SPECIFY THE STRAP SIZE AND HOW ARE THE THREE #14 SCREWS | | | INSTALLED AS SPECIFIED ON CURRENT DETAIL. REQUIRED BY | | | SEC. M1307.2.1 OF 2010 FBC-RESIDENTIAL. (REPEAT | | | COMMENT. NOT ADDRESSED). ENGINEER IS ONLY STATING | | | "SECURE CONDENSING UNIT TO CONCRETE PAD IN ACCORDANCE | | | WITH FMC 9RESIDENTIAL) SECTION 1307.3.1". THIS RESPONSE | | | DOESN'T ADDRESS HOW THE UNIT IS ATTACHED TO THE | | | CONCRETE SLAB. THE ENGINEER OF RECORD IS THE ONE WHO | | | DESIGNS HOW IS THE UNIT ATTACHED TO THE CONCRETE SLAB | | | TO RESIST THE WIND LOADS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2013-08-19 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-08-19 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-08-19 |
Time |
14:31 |
Sent To |
|
|
| Notes |
| 2013-08-16 10:37:55 | RESIDENTIAL (R3) RENOVATION, MECHANICAL REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- RETURN AIR CAN'T BE TAKEN FROM THE KITCHEN. SEC. | | | M1602.2 OF 2010 FBC-RESIDENTIAL. | | | | | | 2- PROVIDE 2 COPIES OF PLANS WITH ENGINEER'S ORIGINAL | | | SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA | | | STATUTE. | | | | | | 3- PROVIDE COMPLETE AND CLEAR SPECIFICATIONS FOR THE | | | ATTACHMENT OF THE CONDENSING UNIT TO THE CONCRETE SLAB. | | | SPECIFY THE STRAP SIZE AND HOW ARE THE THREE #14 SCREWS | | | INSTALLED AS SPECIFIED ON CURRENT DETAIL. SEC. | | | M1307.2.1 OF 2010 FBC-RESIDENTIAL. | | | | | | 4- NEED A/C CONTRACTOR TO APPLY FOR THE MECHANICAL | | | PERMIT. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
|