| Plan Review Stops For Permit 13080472 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2013-10-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-10-07 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-10-07 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2013-10-07 14:56:34 | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- REVISE THE ENERGY CALCULATIONS SUBMITTED: (A)THIS IS | | | NO NEW CONSTRUCTION. IT'S EXISTING. REVISE ITEM #1. | | | (B)REVISE CONDITIONED AREA. SEE PBC PROPERTY APPRAISER. | | | (C)OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM. | | | (D)COMPLETE ALL INFORMATION ON TOP OF FORM, INCLUDING | | | BUILDER'S NAME. (E)REVISE ROOF MATERIAL ON PAGE 2 OF 5. | | | THERE IS CONCRETE TILE ON THIS HOUSE NOT SHINGLES. | | | (F)REVISE DOOR TYPES ON PAGE 3 OF 5. NEED TO MATCH TYPE | | | OF PRODUCT APPROVALS SUBMITTED. | | | | | | 2- SHEET A-2.2: REVISE THE SPECIFICATIONS FOR THE | | | GARAGE DOOR THAT LEADS TO THE LAUNDRY. DOOR NEEDS TO | | | COMPLY WITH SEC. R302.5.1 OF 2010 FBC-RESIDENTIAL. | | | | | | 3- PROVIDE PRODUCT APPROVAL FOR ENTRY DOOR. INFORMATION | | | SUBMITTED DOESN'T HAVE A FLORIDA PRODUCT APPROVAL | | | NUMBER. | | | | | | 4- DESIGNER OF RECORD TO REVIEW AND APPROVE PRODUCT | | | APPROVAL BEFORE SUBMITTAL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2013-08-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-08-16 |
Time |
17:23 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-08-16 |
Time |
17:23 |
Sent To |
|
|
| Notes |
| 2013-08-16 17:35:55 | RESIDENTIAL (R3) REPAIRS/RENOVATION BUILDING REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9N-3 FOR: | | | A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON | | | PLANS. PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE AND | | | PAGE SHOWING THE SPECIFIED CONNECTOR. | | | | | | B) GARAGE DOOR. NOA 10-0216.03 SUBMITTED WAS SUPERSEDED | | | BY MIAMI-DADE. PROVIDE CURRENT NOA. | | | | | | C) INSWING ENTRY DOOR AS SHOWN ON PLANS. (AND CLARIFY | | | WHERE IS THE ALUMINUM/GLASS DOOR WITH NOA 12-0208.14 | | | SUBMITTED GOING TO BE INSTALLED?. IS THIS FOR THE | | | GARAGE SIDE DOOR? | | | | | | 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS. | | | | | | 3- SPECIFY TRUSS CONNECTOR AT BOTH ENDS. ONLY CONNECTOR | | | TO THE EXISTING CONCRETE BLOCK WALL WAS SPECIFIED ON | | | SHEET A-5-0. SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | | | 4- PROVIDE ENERGY CALCULATIONS. SEC. 101.4.3 OF 2010 | | | FBC-ENERGY CONSERVATION. | | | | | | 5- SHEET A-5-1; CLEARLY SPECIFY ROOF SHEATHING FOR ALL | | | ROOF ZONES, INCLUDING ROOF ZONE 3. SEC. R803.2.3.1 OF | | | 2010 FBC-RESIDENTIAL REQUIRES 8D RING SHANK NAILS AT 4" | | | O.C. IN ZONE 3. NAILING SCHEDULE DOESN'T SPECIFY THE | | | ROOF ZONE 3. AND, SEE FIGURE R803.2.3.1 FOR AL ROOF | | | ZONES MINIMUM DIMENSIONS. REVISE THE ROOF SHEATHING | | | DETAIL, ROOF COVERING DETAIL AND NAILING SCHEDULE AS | | | REQUIRED. | | | | | | 6- ARCHITECT'S TITLE BLOCK TO PROVIDE A SPACE FOR THE | | | PRINTED NAME AND LICENSE NUMBER OF THE PERSON SEALING | | | THE DOCUMENT AS REQUIRED BY CHAPTER 481 AND SEC. | | | 61G1-16.004 OF FLORIDA ADMINISTRATIVE CODE. | | | | | | 7- SHEET A-2.2: REVISE THE SPECIFICATIONS FOR THE | | | GARAGE DOOR THAT LEADS TO THE LAUNDRY. DOOR NEEDS TO | | | COMPLY WITH SEC. R302.5.1 OF 2010 FBC-RESIDENTIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2013-09-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-09-03 |
Time |
07:54 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-08-28 |
Time |
18:49 |
Sent To |
|
|
| Notes |
| 2013-09-03 07:54:56 | RED-LINED PLANS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-10-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-10-07 |
Time |
18:10 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-09-10 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2013-09-10 14:19:55 | INCOMING SENT TO R-11. JW |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-09-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-09-03 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-08-13 |
Time |
17:32 |
Sent To |
|
|
| Notes |
| 2013-08-13 17:33:16 | SENT TO R3 SHELF FOR REVIEW. JG. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2013-10-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-10-07 |
Time |
17:31 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-10-07 |
Time |
17:31 |
Sent To |
|
|
| Notes |
| 2013-10-07 17:58:07 | MECHANICAL REVIEW APPROVED WITH PROVISO: | | | | | | 1- REVISE THE TOTAL A/C AREA ON THE EQUIPMENT SIZING | | | CALCULATIONS. NEED TO MATCH THE AREA SHOWN ON THE | | | REVISED ENERGY CALCULATIONS. SEE BUILDING REVIEW | | | PROVISO. | | | ***NOTE; SPECIFY ON A/C PLANS ALL EQUIPMENT SHOWN ON | | | THE SIZING CALCULATIONS. | | | | | | 2- MASTER BEDROOM TRANSFER GRILL DOESN'T COMPLY WITH | | | SEC. M1602.4. REVISE SIZE AS REQUIRED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2013-08-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-08-16 |
Time |
18:57 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-08-16 |
Time |
18:57 |
Sent To |
|
|
| Notes |
| 2013-08-16 18:59:49 | RESIDENTIAL (R3) REPAIR/RENOVATION MECHANICAL REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROVIDE EQUIPMENT SIZING CALCULATIONS. EQUIPMENT TO | | | MATCH EQUIPMENT LISTED ON A/C PLANS. | | | ***NOTE; SPECIFY ON A/C PLANS ALL EQUIPMENT SHOWN ON | | | THE SIZING CALCULATIONS. | | | | | | 2- MASTER BATHROOM NEEDS ANOTHER EXHAUST FAN AS | | | REQUIRED BY SEC. M1507.1 OF 2010 FBC-RESIDENTIAL. | | | | | | 3- MASTER BEDROOM TRANSFER GRILL DOESN'T COMPLY WITH | | | SEC. M1602.4. REVISE SIZE AS REQUIRED. NEED 50SQUARE | | | INCHES FOR EACH 100CFM SUPPLIED. AND MASTER BEDROOM | | | NEED TO SIZE TRANSFER GRILL ACCORDING TO ALL THE AIR | | | THAT IS SUPPLIED INTO THE MASTER SUITE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2013-10-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-10-07 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-10-07 |
Time |
15:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2013-08-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-08-16 |
Time |
18:57 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-08-16 |
Time |
18:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2013-09-17 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2013-09-17 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2013-09-17 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2013-09-16 19:10:43 | 9/16/13 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2013-08-16 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2013-08-16 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2013-08-16 |
Time |
15:56 |
Sent To |
|
|
| Notes |
| 2013-08-16 15:59:58 | ZONING FAILED FOR THE FOLLOWING REASON: | | | | | | 1.) THE VALUE OF THE CONSTRUCTION ($121,784) EXCEEDS | | | 50% OF THE STRUCTURE'S VALUE ($155,386) ACCORDING TO | | | THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, | | | PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE | | | SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE | | | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE | | | SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A | | | LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE | | | INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES | | | NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING | | | APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND | | | IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL | | | TO BRING THE SITE INTO CONFORMITY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | LINDA LOUIE, AICP | | | PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1442 | | | EMAIL: [email protected] |
|
|