Plan Review Details - Permit 13080472
Plan Review Stops For Permit 13080472
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-10-07 Cont ID  
Sent By jgomez Date 2013-10-07 Time 13:44 Rev Time 0.00
Received By jgomez Date 2013-10-07 Time 13:44 Sent To  
Notes
2013-10-07 14:56:34BUILDING REVIEW APPROVED WITH PROVISO:
 1- REVISE THE ENERGY CALCULATIONS SUBMITTED: (A)THIS IS
 NO NEW CONSTRUCTION. IT'S EXISTING. REVISE ITEM #1.
 (B)REVISE CONDITIONED AREA. SEE PBC PROPERTY APPRAISER.
 (C)OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM.
 (D)COMPLETE ALL INFORMATION ON TOP OF FORM, INCLUDING
 BUILDER'S NAME. (E)REVISE ROOF MATERIAL ON PAGE 2 OF 5.
 THERE IS CONCRETE TILE ON THIS HOUSE NOT SHINGLES.
 (F)REVISE DOOR TYPES ON PAGE 3 OF 5. NEED TO MATCH TYPE
 OF PRODUCT APPROVALS SUBMITTED.
  
 2- SHEET A-2.2: REVISE THE SPECIFICATIONS FOR THE
 GARAGE DOOR THAT LEADS TO THE LAUNDRY. DOOR NEEDS TO
 COMPLY WITH SEC. R302.5.1 OF 2010 FBC-RESIDENTIAL.
  
 3- PROVIDE PRODUCT APPROVAL FOR ENTRY DOOR. INFORMATION
 SUBMITTED DOESN'T HAVE A FLORIDA PRODUCT APPROVAL
 NUMBER.
  
 4- DESIGNER OF RECORD TO REVIEW AND APPROVE PRODUCT
 APPROVAL BEFORE SUBMITTAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-16 Cont ID  
Sent By jgomez Date 2013-08-16 Time 17:23 Rev Time 0.00
Received By jgomez Date 2013-08-16 Time 17:23 Sent To  
Notes
2013-08-16 17:35:55RESIDENTIAL (R3) REPAIRS/RENOVATION BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE AND
 PAGE SHOWING THE SPECIFIED CONNECTOR.
  
 B) GARAGE DOOR. NOA 10-0216.03 SUBMITTED WAS SUPERSEDED
 BY MIAMI-DADE. PROVIDE CURRENT NOA.
  
 C) INSWING ENTRY DOOR AS SHOWN ON PLANS. (AND CLARIFY
 WHERE IS THE ALUMINUM/GLASS DOOR WITH NOA 12-0208.14
 SUBMITTED GOING TO BE INSTALLED?. IS THIS FOR THE
 GARAGE SIDE DOOR?
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS.
  
 3- SPECIFY TRUSS CONNECTOR AT BOTH ENDS. ONLY CONNECTOR
 TO THE EXISTING CONCRETE BLOCK WALL WAS SPECIFIED ON
 SHEET A-5-0. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 4- PROVIDE ENERGY CALCULATIONS. SEC. 101.4.3 OF 2010
 FBC-ENERGY CONSERVATION.
  
 5- SHEET A-5-1; CLEARLY SPECIFY ROOF SHEATHING FOR ALL
 ROOF ZONES, INCLUDING ROOF ZONE 3. SEC. R803.2.3.1 OF
 2010 FBC-RESIDENTIAL REQUIRES 8D RING SHANK NAILS AT 4"
 O.C. IN ZONE 3. NAILING SCHEDULE DOESN'T SPECIFY THE
 ROOF ZONE 3. AND, SEE FIGURE R803.2.3.1 FOR AL ROOF
 ZONES MINIMUM DIMENSIONS. REVISE THE ROOF SHEATHING
 DETAIL, ROOF COVERING DETAIL AND NAILING SCHEDULE AS
 REQUIRED.
  
 6- ARCHITECT'S TITLE BLOCK TO PROVIDE A SPACE FOR THE
 PRINTED NAME AND LICENSE NUMBER OF THE PERSON SEALING
 THE DOCUMENT AS REQUIRED BY CHAPTER 481 AND SEC.
 61G1-16.004 OF FLORIDA ADMINISTRATIVE CODE.
  
 7- SHEET A-2.2: REVISE THE SPECIFICATIONS FOR THE
 GARAGE DOOR THAT LEADS TO THE LAUNDRY. DOOR NEEDS TO
 COMPLY WITH SEC. R302.5.1 OF 2010 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-09-03 Cont ID  
Sent By rmcdouga Date 2013-09-03 Time 07:54 Rev Time 0.00
Received By rmcdouga Date 2013-08-28 Time 18:49 Sent To  
Notes
2013-09-03 07:54:56RED-LINED PLANS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-07 Cont ID  
Sent By jgomez Date 2013-10-07 Time 18:10 Rev Time 0.00
Received By jgomez Date 2013-09-10 Time 14:15 Sent To  
Notes
2013-09-10 14:19:55INCOMING SENT TO R-11. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-09-03 Cont ID  
Sent By rmcdouga Date 2013-09-03 Time 07:55 Rev Time 0.00
Received By rmcdouga Date 2013-08-13 Time 17:32 Sent To  
Notes
2013-08-13 17:33:16SENT TO R3 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-10-07 Cont ID  
Sent By jgomez Date 2013-10-07 Time 17:31 Rev Time 0.00
Received By jgomez Date 2013-10-07 Time 17:31 Sent To  
Notes
2013-10-07 17:58:07MECHANICAL REVIEW APPROVED WITH PROVISO:
  
 1- REVISE THE TOTAL A/C AREA ON THE EQUIPMENT SIZING
 CALCULATIONS. NEED TO MATCH THE AREA SHOWN ON THE
 REVISED ENERGY CALCULATIONS. SEE BUILDING REVIEW
 PROVISO.
 ***NOTE; SPECIFY ON A/C PLANS ALL EQUIPMENT SHOWN ON
 THE SIZING CALCULATIONS.
  
 2- MASTER BEDROOM TRANSFER GRILL DOESN'T COMPLY WITH
 SEC. M1602.4. REVISE SIZE AS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-08-16 Cont ID  
Sent By jgomez Date 2013-08-16 Time 18:57 Rev Time 0.00
Received By jgomez Date 2013-08-16 Time 18:57 Sent To  
Notes
2013-08-16 18:59:49RESIDENTIAL (R3) REPAIR/RENOVATION MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS. EQUIPMENT TO
 MATCH EQUIPMENT LISTED ON A/C PLANS.
 ***NOTE; SPECIFY ON A/C PLANS ALL EQUIPMENT SHOWN ON
 THE SIZING CALCULATIONS.
  
 2- MASTER BATHROOM NEEDS ANOTHER EXHAUST FAN AS
 REQUIRED BY SEC. M1507.1 OF 2010 FBC-RESIDENTIAL.
  
 3- MASTER BEDROOM TRANSFER GRILL DOESN'T COMPLY WITH
 SEC. M1602.4. REVISE SIZE AS REQUIRED. NEED 50SQUARE
 INCHES FOR EACH 100CFM SUPPLIED. AND MASTER BEDROOM
 NEED TO SIZE TRANSFER GRILL ACCORDING TO ALL THE AIR
 THAT IS SUPPLIED INTO THE MASTER SUITE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-10-07 Cont ID  
Sent By jgomez Date 2013-10-07 Time 15:37 Rev Time 0.00
Received By jgomez Date 2013-10-07 Time 15:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-08-16 Cont ID  
Sent By jgomez Date 2013-08-16 Time 18:57 Rev Time 0.00
Received By jgomez Date 2013-08-16 Time 18:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2013-09-17 Cont ID  
Sent By llouie Date 2013-09-17 Time 13:39 Rev Time 0.00
Received By llouie Date 2013-09-17 Time 13:39 Sent To  
Notes
2013-09-16 19:10:439/16/13

Review Stop Z ZONING
Rev No 1 Status F Date 2013-08-16 Cont ID  
Sent By llouie Date 2013-08-16 Time 15:56 Rev Time 0.00
Received By llouie Date 2013-08-16 Time 15:56 Sent To  
Notes
2013-08-16 15:59:58ZONING FAILED FOR THE FOLLOWING REASON:
  
 1.) THE VALUE OF THE CONSTRUCTION ($121,784) EXCEEDS
 50% OF THE STRUCTURE'S VALUE ($155,386) ACCORDING TO
 THE P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE,
 PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
 LINDA LOUIE, AICP
 PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1442
 EMAIL: [email protected]