Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-09-14 Cont ID  
Sent By shill Date 2013-09-14 Time 15:10 Rev Time 0.00
Received By shill Date 2013-09-14 Time 15:10 Sent To  
Notes
2013-09-14 15:13:16****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. ENGINEERING REQUIRED AS THIS DOES NOT FALL UNDER ANY
 OF THE EXEMPTIONS OF FLORIDA STATUTE 471. ENGINEERING
 TO SPECIFY FLOOR LOADS TABLE FBC 1607.1. ALSO SPECIFY
 PROPOSED USE OF PROPOSED DECK. PROVIDE PLANS PREPARED
 BY AN ENGINEER (OR ARCHITECT).
  
 2ND REVIEW, PLANS PREPARED BY AN ARCHITECT PROVIDED,
 BUT SUPPORTING DOCUMENTS REFER TO RESIDENTIAL CODE.
 THIS IS BUSINESS OCCUPANCY. FLOOR LOADS NOT SPECIFIED.
  
 2. SHOW ACCESSIBLE ROUTE FROM BUILDING TO PROPOSED
 DECK, FBC 2010 ACCESSIBILITY 201.1, (SCOPE INLCUDES ALL
 AREAS OF A FACILITY UNLESS EXEMPTED - DEFINITION OF
 "FACILITY" IS "ALL OR ANY PORTION OF BUILDINGS,
 STRUCTURES, SITE IMPROVEMENTS, ELEMENTS, AND PEDESTRIAN
 ROUTES OR VEHICULAR WAYS LOCATED ON A SITE;"
  
 202.3 REFERS TO ALTERATIONS TO COMPLY WITH CHAPTER 2
  
 206.2.2 REQUIRES ACCESSIBLE ROUTE TO ACCESSIBLE
 ELEMENTS, SEE ALSO CHAPTER 4.
  
 2ND REVIEW, NOT ADDRESSED.
  
 3. SEE FBC ACCESSIBILITY 302.3 REGARDING ELONGATED
 OPENINGS. SHOW WOOD DECK FLOOR PATTERN ORIENTATION IN
 RELATION TO DIRECTION OF TRAVEL.
  
 2ND REVIEW, NOT ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-31 Cont ID  
Sent By shill Date 2013-08-31 Time 15:46 Rev Time 0.00
Received By shill Date 2013-08-31 Time 15:46 Sent To  
Notes
2013-08-31 16:05:38****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. ENGINEERING REQUIRED AS THIS DOES NOT FALL UNDER ANY
 OF THE EXEMPTIONS OF FLORIDA STATUTE 471. ENGINEERING
 TO SPECIFY FLOOR LOADS TABLE FBC 1607.1. ALSO SPECIFY
 PROPOSED USE OF PROPOSED DECK. PROVIDE PLANS PREPARED
 BY AN ENGINEER (OR ARCHITECT).
  
 2. SHOW ACCESSIBLE ROUTE FROM BUILDING TO PROPOSED
 DECK, FBC 2010 ACCESSIBILITY 201.1, (SCOPE INLCUDES ALL
 AREAS OF A FACILITY UNLESS EXEMPTED - DEFINITION OF
 "FACILITY" IS "ALL OR ANY PORTION OF BUILDINGS,
 STRUCTURES, SITE IMPROVEMENTS, ELEMENTS, AND PEDESTRIAN
 ROUTES OR VEHICULAR WAYS LOCATED ON A SITE;"
  
 202.3 REFERS TO ALTERATIONS TO COMPLY WITH CHAPTER 2
  
 206.2.2 REQUIRES ACCESSIBLE ROUTE TO ACCESSIBLE
 ELEMENTS, SEE ALSO CHAPTER 4.
  
 3. SEE FBC ACCESSIBILITY 302.3 REGARDING ELONGATED
 OPENINGS. SHOW WOOD DECK FLOOR PATTERN ORIENTATION IN
 RELATION TO DIRECTION OF TRAVEL.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-09-14 Cont ID  
Sent By shill Date 2013-09-14 Time 15:13 Rev Time 0.00
Received By shill Date 2013-09-13 Time 16:48 Sent To  
Notes
2013-09-13 16:49:13GAVE TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-31 Cont ID  
Sent By shill Date 2013-08-31 Time 16:09 Rev Time 0.00
Received By shill Date 2013-08-13 Time 14:03 Sent To  
Notes
2013-08-14 14:03:51SENT TO ZONING SHELF FOR REVIEW. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2013-08-29 Cont ID  
Sent By llouie Date 2013-08-29 Time 10:51 Rev Time 0.00
Received By llouie Date 2013-08-15 Time 09:39 Sent To B
Notes
2013-08-15 16:55:39ZONING PASSED WITH THE FOLLOWING PROVISO:
  
 1.) DECK SHALL BE SETBACK 2 FT. FROM THE REAR PROPERTY
 LINE. (ZLDR S.94-305(B)(7))
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.