| 2013-10-18 16:29:48 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS. |
| | CODE; 2010 FBC. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS. SEC. 103.2.1 OF 2010 |
| | FBC-ENERGY CONSERVATION. PLEASE MAKE SURE ALL THE |
| | INFORMATION IS PROVIDED ND COORDINATED WITH THE PLANS |
| | SUBMITTED. AND, PREPARER AND OWNER/AGENT TO CERTIFY AND |
| | DATE BOTTOM OF FORM. |
| | |
| | 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE |
| | DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT |
| | FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 3- FRENCH DOORS SHOWN ON PROPOSED SECOND FLOOR PLAN ON |
| | SHEET A-1 DON'T MATCH FRENCH DOORS SHOWN ON PROPOSED |
| | NORTH ELEVATION ON SHEET A-2. REVISE AS REQUIRED TO |
| | MATCH. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| | |
| | 4-PROVIDE COMPLETE FRAMING DETAILS FOR THE ATTACHMENT |
| | OF THE FRENCH DOORS TO THE STEEL COLUMN AS SHOWN ON |
| | SHEET A-1 ON THE PROPOSED GARAGE PLAN. SEC. 107.2.1.3 |
| | CITY AMENDMENTS TO FBC. |
| | |
| | 5- SHEET A-1: |
| | A) SPECIFY DIMENSION BY STAIRWAY ON TOP LANDING. SEC. |
| | R311.7.5. |
| | |
| | B) PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| | FOR GUARDRAIL ON INSIDE OPEN BALCONY ON SECOND FLOOR TO |
| | SHOW COMPLIANCE WITH TABLE R301.5 AND SEC. R312. |
| | |
| | C) PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| | FOR ALL THE EXTERIOR ENTRY CANOPIES SHOWN ON THE |
| | ELEVATIONS AND FOR THE OPTIONAL CANOPY AS SPECIFY ON |
| | THE PROPOSED SECOND FLOOR PLAN. SEC. 107.2.1.3 CITY |
| | AMENDMENTS. |
| | |
| | D) PROVIDE COMPLETE STAIR AND HANDRAILS DETAILS AND |
| | SPECIFICATIONS SHOWING COMPLIANCE WITH SEC. R311.7.4 |
| | AND SEC. R311.7.7. |
| | |
| | 6- SHEET A-4: |
| | A) SPECIFY UNDER-STAIR PROTECTION AS REQUIRED BY SEC. |
| | R302.7. |
| | |
| | B) REVISE/CLARIFY NOTE #1 SHOWN ON PROPOSED SOUTH |
| | ELEVATION CEILING ABOVE THE WASHER AND DRYER. |
| | |
| | C) SPECIFY INSULATION ON WALLS, FLOOR BETWEEN GARAGE |
| | AND SECOND FLOOR, AND ATTIC. ALSO, COORDINATE WITH THE |
| | ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | 7- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806. |
| | |
| | 8- SPECIFY ATTIC ACCESS LOCATION AND SIZE AS REQUIRED |
| | BY SEC. R807. |
| | |
| | 9- SPECIFY CARBON MONOXIDE ALARM AS REQUIRED BY SEC. |
| | R315.1 |
| | |
| | 10- ALL DRAWINGS TO HAVE THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | |
| | 11- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN |
| | PROFESSIONAL FEES. SEC. 109.3 CITY AMENDMENTS. |
| | VALUATION WAS UPDATED TO $68,828. THE PERMIT FEE |
| | BALANCE IS $1804.30. |
| | |
| | 12- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR |
| | A) METAL SHINGLE ROOF PRODUCT APPROVAL AS SPECIFIED ON |
| | PLANS.. |
| | |
| | B) ALTERNATE CARRIAGE DOORS AS SPECIFIED ON SHEET A-2 |
| | |
| | C) FRENCH DOORS WITH SIDELITES AS SHOWN ON PLANS FOR |
| | PROPOSED SECOND FLOOR. |
| | |
| | D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND ALL DETAILS. PROVIDE ONLY THE COVER PAGE AND PAGE |
| | SHOWING THE SPECIFIED CONNECTOR. |
| | |
| | E) GARAGE DOOR. NOA 12-0125.09 EXPIRED ON AUGUST 21, |
| | 2013. NEED CURRENT NOA. |
| | |
| | F) FRENCH DOORS NOA 10-0923.03 SUBMITTED WAS SUPERSEDED |
| | BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE AND |
| | DOWNLOAD CURRENT NOA. |
| | |
| | G) HURRICANE SHUTTERS FOR FRENCH DOORS THAT HAVE NO |
| | IMPACT GLASS (SEE NOA SUBMITTED). |
| | |
| | H) "INSWING" ENTRY DOOR FOR GUEST SUITE AS SHOWN ON |
| | PLANS. |
| | |
| | 13- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 14- PROVIDE COMPLETE HURRICANE SHUTTERS INSTALLATION |
| | SCHEDULE FOR DOORS THAT HAVE NO IMPACT GLASS. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | 15- COORDINATE SECTION 1/S-6 AND FINISH ELEVATIONS |
| | SHOWN ON SHEET A-4. NEED TO HAVE 6" MIN. DISTANCE FROM |
| | EXTERIOR WALL COVERING TO FINISH GRADE. SEE SEC. R704. |
| | SECTION 1/S-6 SHOWS 4" AT SOUTH SIDE. ***NOTE: FOOTING |
| | SIZE MAY NEED TO BE ADJUSTED. |
| | |
| | 16- REVISE SECTION 8/S-7 TO MATCH FOUNDATION PLAN. |
| | MISSING THE THICKENED EDGE. SEC. 107.2.1 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 17- REVISE SECTION 3/S-6. NEED TO SPECIFY 8D RING SHANK |
| | NAILS FOR SHEATHING FASTENING IN ALL ROOF ZONES AS |
| | REQUIRED BY SEC. R803.2.3.1. |
| | |
| | 18- REVISE CORNER DISTANCE "A" ON THE WIND LOAD |
| | SCHEDULE ON SHEET S-4. NEED 4'-0" MIN. AS REQUIRED BY |
| | FOOTNOTE "A" ON FIGURE R301.2(7). |
| | |
| | 19- DESIGN LOAD SCHEDULE ON SHEET S-4: CLEARLY SPECIFY |
| | AL LIVE AND DEAD LOADS, INCLUDING THE ATTIC LIVE LOAD |
| | AS REQUIRED BY TABLE R301.5. |
| | |
| | 20- PROVIDE COMPLETE FRAMING DETAILS FOR THE |
| | CONSTRUCTION OF EXTERIOR BALCONY HANDRAILS TO SHOW |
| | COMPLIANCE WITH TABLE R301.5 AND SEC. R312. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |