Plan Review Details - Permit 13080302
Plan Review Stops For Permit 13080302
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-11-02 Cont ID  
Sent By rmcdouga Date 2013-11-02 Time 12:24 Rev Time 0.00
Received By rmcdouga Date 2013-11-02 Time 12:24 Sent To  
Notes
2013-11-02 12:25:512010 FBC
  
 BUILDING PROVISO
  
 SUBMIT TWO SETS OF PRODUCT APPROVALS WITH RAS 117
 CALCULATIONS FOR THE APPROVED ASSEMBLY AND FASTENING
 OPTION THAT WILL BE INSTALLED ON THE FLAT ROOFS. SEE
 NOTES UNDER THE (R) PLAN REVIEW STOP.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-10-21 Cont ID  
Sent By dharvey Date 2013-10-21 Time 17:16 Rev Time 0.00
Received By rmcdouga Date 2013-09-30 Time 10:50 Sent To  
Notes
2013-10-21 16:12:222010 FBC
  
 DENIED BY BUILDING
  
 1) THE PROJECTED ROOF AREA IN THE CALCULATIONS FOR THE
 ROOF SCUPPERS ON SHEET A-3 ARE REQUIRED TO INCLUDE ONE
 HALF OF VERTICAL WALL AREAS THAT DIVERT ( FBC P 1106.4)
 RAINWATER TO THE ROOF AND THE AREA OF THE ROOFS ABOVE
 THAT WILL DRAIN ON TO THE LOWER ROOF. FBCR 903.4, FBC P
 1101.7 AND 1106.4 PLEASE REVISE CALCULATIONS.
  
 2) SPECIFY THE EMBED DEPTH OF THE SLEEVE ANCHORS ON THE
 CANOPY DETAIL, 4 ON SHEET A-10. FBC R301.2.1
  
 3) ALSO, ON DETAIL 4 ON A-10, PLEASE REVIEW THE
 ATTACHMENT OF THE RAFTERS TO THE BEAM WITH TWO (2) 10D
 TOE-NAILS FOR REQUIRED UPLIFT RESISTANCE. FBC R301.2.1
  
 4) SUBMIT TWO SETS OF SPECIFICATIONS AND THE LISTING
 INFORMATION FOR THE ISOKERN FIREPLACES AND THEIR METAL
 FLUE CHIMNEYS. FBC R1001, R1004 AND R1005.
  
 5) SHOW COMPLIANCE WITH FBC R1006 FOR REQUIRED EXTERIOR
 AIR SUPPLY.
  
 6) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 CLAY BARREL TILE ROOF (NOA NO. 11-0329.02) EXPIRED ON
 3/13/13. SUBMIT TWO COPIES OF CURRENT PRODUCT
 APPROVALS. DCA RULE 9N-3
  
 7) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED
 TO INSTALL THE ROOF TILE BY MARKING ONE OF THE ONES
 LISTED IN THE PRODUCT APPROVAL. FBC R905.3.7 IF AN
 ADHESIVE IS SELECTED, SUBMIT TWO COPIES OF THE PRODUCT
 APPROVAL FOR IT. DCA RULE 9N-3
  
 8) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 FLAT ROOFS AND DECK AREAS AS REQUIRED BY DCA RULE 9N-3.
 SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117
 CALCULATIONS FOR ENHANCED FASTENING AT THE PERIMETER
 AND CORNER AREAS (LIMITATION #7) IF THE MAXIMUM DESIGN
 PRESSURE IS NOT ADEQUATE FOR THE FASTENING OPTION THAT
 IS SELECTED. FBC R301.2.1
  
 9) THE REQUIRED DESIGN PRESSURES FOR THE OVERHEAD
 GARAGE DOOR IS SPECIFIED ON THE PLAN AS + 48 , - 62
 PSF. THE AMARR GARAGE DOOR PRODUCT APPROVAL THAT WAS
 SUBMITTED (NOA NO. 12-0228.12) HAS A NEGATIVE DESIGN
 PRESSURE OF - 60.3 PSF WHICH IS LOWER THAN THE REQUIRED
 NEGATIVE PRESSURE LISTED ON THE PLANS. PLEASE SUBMIT
 PRODUCT APPROVALS WITH ADEQUATE PRESSURES. FBC R301.2.1
  
 10) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 PGT FIXED WINDOW (NOA NO. 11-1110.15) HAS BEEN
 SUPERSEDED. SUBMIT TWO COPIES OF CURRENT PRODUCT
 APPROVALS. DCA RULE 9N-3
  
 11) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 EXTERIOR FRENCH DOORS (FL# 16217.1) ARE FOR CGI SERIES
 SENTINEL 160 DOORS. THE DOOR NOTES ON SHEET A-12
 SPECIFY PGT FD750 SERIES DOORS. PLEASE CLARIFY. CITY
 AMENDMENTS 107.2.1
  
 12) SUBMIT TWO COPIES OF THE PRODUCT EVALUATION FOR THE
 ICYNENE SPRAY FOAM INSULATION. FBC R316
  
 IN ORDER TO EXPEDITE THE PLAN REVIEW, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE PLAN REVIEW
 COMMENTS HAVE BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
2013-09-16 12:23:31ENTERED BYMISTAKE. SHOULD HAVE BEEN ELECTRICAL STOP DH

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-09-16 Cont ID  
Sent By dharvey Date 2013-09-09 Time 12:22 Rev Time 0.00
Received By dharvey Date 2013-09-09 Time 12:22 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2013-10-16 Cont ID  
Sent By rmcdouga Date 2013-10-16 Time 08:57 Rev Time 0.00
Received By rmcdouga Date 2013-10-16 Time 08:57 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2013-08-08 Cont ID  
Sent By fmittner Date 2013-08-08 Time 09:53 Rev Time 0.00
Received By fmittner Date 2013-08-08 Time 09:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-11-02 Cont ID  
Sent By rmcdouga Date 2013-11-02 Time 12:25 Rev Time 0.00
Received By rmcdouga Date 2013-11-02 Time 12:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-21 Cont ID  
Sent By rmcdouga Date 2013-10-21 Time 17:16 Rev Time 0.00
Received By rmcdouga Date 2013-08-08 Time 11:02 Sent To  
Notes
2013-08-09 11:03:38R26
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2013-11-04 Cont ID  
Sent By skennedy Date 2013-11-04 Time 12:06 Rev Time 0.00
Received By skennedy Date 2013-11-04 Time 12:06 Sent To  
Notes
2013-11-04 12:07:48CUSTOMER RETURNED COUNTY IMPACT FEE RECEIPT.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-10-16 Cont ID  
Sent By rmcdouga Date 2013-10-16 Time 07:13 Rev Time 0.00
Received By rmcdouga Date 2013-10-16 Time 07:13 Sent To  
Notes
2013-10-16 07:15:52PLANS ARE REQUIRED TO BE REVIEWED BY PALM BEACH COUNTY
 FOR IMPACT FEES.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-10-16 Cont ID  
Sent By rmcdouga Date 2013-10-16 Time 11:06 Rev Time 0.00
Received By rmcdouga Date 2013-10-16 Time 09:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-10-16 Cont ID  
Sent By rmcdouga Date 2013-10-16 Time 08:57 Rev Time 0.00
Received By rmcdouga Date 2013-10-16 Time 07:13 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2013-11-02 Cont ID  
Sent By rmcdouga Date 2013-11-02 Time 08:21 Rev Time 0.00
Received By rmcdouga Date 2013-11-02 Time 08:21 Sent To  
Notes
2013-11-02 08:57:30SEE BUILDING PROVISO
  
 1) PRODUCT APPROVAL COVER SHEET FL 1654-R12 HAS THE
 EVALUATION REPORT FOR FL 1654-R11 ATTACHED TO IT RATHER
 THAN THE R-12 (REVISION 12) ONE. THE W-6 SYSTEM NUMBER
 IS MARKED ON THE R11 REPORT. THIS IS SYSTEM TYPE A-2:
 MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION
 AND BONDED ROOF COVER. THE ANCHOR SHEET ATTACHMENT IS 6
 " OC IN THE 4" LAP AND 6" OC IN FOUR EQUALLY SPACED
 STAGGERED CENTER ROWS FOR A MAXIMUM DESIGN PRESSURE OF
 -60 PSF. THE SIGNED AND SEALED RAS 117 CALCULATIONS
 THAT WERE SUBMITTED SPECIES 2 CENTER ROWS WITH A
 FASTENER SPACING OF 9 " OC . THE LAP AND DESIGN
 PRESSURES MATCH, BUT THE CENTER ROWS ARE DIFFERENT.
 THERE IS NO WAY FOR ME TO DETERMINE WHICH ONE IS
 INCORRECT, BECAUSE THE RAS 117 CALCULATIONS DO NOT
 SPECIFY THE PRODUCT APPROVAL NUMBER OR THE SYSTEM. THE
 CALCULATIONS ALSO DO NOT SPECIFY THE WIND SPEED, THE
 EXPOSURE CATEGORY OR THE MEAN ROOF HEIGHT USED TO
 DETERMINE THE REQUIRED COMPONENT AND CLADDING
 PRESSURES. PLEASE CORRECT.
  
 THE FOLLOWING ROOFING PRODUCTS ARE ACCEPTABLE: NOA NO.
 12-0529.12 FOR THE CLAY BARREL TILE AND NOA NO.
 12-0228.18 FOR THE AH-160 ROOF TILE ADHESIVE

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2013-10-21 Cont ID  
Sent By rmcdouga Date 2013-10-21 Time 17:17 Rev Time 0.00
Received By rmcdouga Date   Time   Sent To  
Notes
2013-10-21 17:18:36NEED CURRENT ROOFING PRODUCT APPROVALS FOR THE CLAY
 TILE ON THE SLOPED ROOF AND THE ROOFING MATERIAL FOR
 THE FLAT ROOFS.

Review Stop Z ZONING
Rev No 1 Status P Date 2013-08-08 Cont ID  
Sent By fmittner Date 2013-08-08 Time 09:53 Rev Time 0.00
Received By fmittner Date 2013-08-08 Time 09:53 Sent To  
Notes
***NONE***