Plan Review Details - Permit 13080227
Plan Review Stops For Permit 13080227
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-10-25 Cont ID  
Sent By jwitmer Date 2013-10-25 Time 17:13 Rev Time 0.00
Received By skennedy Date 2013-10-25 Time 17:12 Sent To  
Notes
2013-10-25 17:13:33BY JW 10/17/13
2013-10-23 16:15:11SORRY I DID NOT MEAN TO CLICK HERE

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-07 Cont ID  
Sent By jwitmer Date 2013-08-07 Time 07:24 Rev Time 0.00
Received By jwitmer Date 2013-08-07 Time 06:30 Sent To  
Notes
2013-08-07 07:24:39BUILDING PLAN REVIEW
 PERMIT: 13080227
 ADD: 3111 45TH ST. SUITE # 17
 CONT: GREG C BELL CONSTRUCTION
 TEL: (561)346-2217
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: AUGUST 07/ 2013
 ACTION: DENIED
  
 1) ALL DOORS SHOWN IN THIS PLAN ARE 2'-8" SWING DOORS.
 PLEASE UPDATE PLANS TO CODE COMPLIANCE FOR 201 FBC-B
 1008.1.1 SIZE OF DOORS.
 THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE
 SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL
 PROVIDE A CLEAR WIDTH OF 32 INCHES (813 MM). CLEAR
 OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES (1.57 RAD).
  
 2) DOORS IN CORRIDORS PLEASE COMPLY WITH 2010 FBC-B
 1008.1.9.11
 DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL
 LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF THE REQUIRED
 WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY, OR LANDING,
 NOR PROJECT MORE THAN 7 INCHES (178 MM) INTO THE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY OR
 LANDING, WHEN FULLY OPEN.
  
 3) DOOR FROM WAITING ROOM TO RECEPTION AREA, PLEASE SEE
 2010 FBC-ACCESSIBILTY CODE 404.2.4.1 SWINGING DOORS AND
 GATES.
 SWINGING DOORS AND GATES SHALL HAVE MANEUVERING
 CLEARANCES COMPLYING WITH TABLE 404.2.4.1. FROM FRONT,
 PULL SIDE 18" BEYOND THE LATCH SIDE OF THE DOOR.
  
 4) RECEPTION DESK, THERE IS NO DETAILS OF THE RECEPTION
 COUNTER, IT IS INDICATED IT IS 40" TALL, PLEASE SEE:
 2010 FL ACCESSIBILITY CODE 904.3.3 CHECK WRITING
 SURFACES. WHERE PROVIDED, CHECK WRITING SURFACES SHALL
 COMPLY WITH 902.3.
 902.3 HEIGHT. THE TOPS OF WORK SURFACES SHALL BE 28
 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 5) 2010 FL ACCESSIBILITY CODE. 202.4.1 DISPROPORTIONATE
 COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 PLEASE PROVIDE WHERE AN ADDITIONAL 20% OR $1160.00 WILL
 BE SPENT IN ACCESSIBLE UPGRADES. PLEASE NOTE THE
 EXISTING RESTROOM DOOR DOES NOT MEET THE REQUIREMENT OF
 18" ON THE LATCH SIDE OF THE DOOR (ACC. CODE 404.2.4.1)
 AND PLANS DO NOT INDICATE ANY ACCESSIBLE ELEMENTS
 WITHIN THE RESTROOM AT ALL, SUCH AS GRAB BARS COMPLYING
 WITH 2010 FL ACC CODE 604.5.
  
 6) NEITHER THE ARCHITECTURAL SHEET NOR ELECTRICAL SHEET
 INDICATE ANY EMERGENCY LIGHT SOURCE IN THE CORRIDOR
 THAT WILL PROVIDE ILLUMINATION FOR EXITING. 2010 FBC-B
 1006.1.1.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-10-25 Cont ID  
Sent By d harvey Date 2013-10-25 Time 17:13 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-08-27 Cont ID  
Sent By dharvey Date 2013-08-27 Time 15:00 Rev Time 0.00
Received By dharvey Date 2013-08-27 Time 14:59 Sent To  
Notes
2013-08-27 15:04:538-27-13
  
 THERE IS NO REFERENCE TO NEC ARTICLE 517 ON THE
 DRAWINGS. ANY PATIENT CARE AREAS MUST HAVE SPECIFIC
 WIRING METHODS. THESE MUST BE SHOWN ON THE PLANS.
 VB

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-10-09 Cont ID  
Sent By w jolin Date 2013-10-09 Time 15:22 Rev Time 0.00
Received By scaldero Date 2013-10-09 Time 15:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-08-14 Cont ID  
Sent By wjolin Date 2013-08-14 Time 17:41 Rev Time 0.00
Received By wjolin Date 2013-08-14 Time 17:28 Sent To  
Notes
2013-08-14 17:38:273111 45TH STREET - SUITE #17
 PERMIT #13080227
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PER NFPA 101 SECTION 7.2.1.4.3 DOOR LEAF ENCROACHMENT -
 DURING ITS SWING, ANY DOOR LEAF IN A MEANS OF EGRESS
 SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED
 WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A
 LANDING UNOBSTRUCTED AND SHALL PROJECT NOT MORE THAN
 7-INCHES INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGEWAY, OR A LANDING, WHEN FULLY OPEN.
  
 PER NFPA 101 SECTION 7.2.1.2.3.2, DOOR OPENINGS IN THE
 MEANS OF EGRESS SHALL BE NOT LESS THAN 32-INCHES IN
 CLEAR WIDTH.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-25 Cont ID  
Sent By skennedy Date 2013-10-25 Time 17:14 Rev Time 0.00
Received By skennedy Date 2013-10-07 Time 18:04 Sent To  
Notes
2013-10-07 18:21:11B23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-27 Cont ID  
Sent By shill Date 2013-08-27 Time 17:15 Rev Time 0.00
Received By shill Date 2013-08-06 Time 15:49 Sent To  
Notes
2013-08-06 15:49:50INCOMING SENT TO B-40. JW

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-10-23 Cont ID  
Sent By hmoser Date 2013-10-23 Time 16:42 Rev Time 0.00
Received By mricard Date 2013-10-23 Time 16:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-08-07 Cont ID  
Sent By jwitmer Date 2013-08-07 Time 07:28 Rev Time 0.00
Received By jwitmer Date 2013-08-07 Time 07:28 Sent To  
Notes
2013-08-07 07:28:36NO MECHANICAL PLANS SUPPLIED.2010 FBC-M 601.4. FAILURE
 TO SHOW BALANCE RETURN AIR. RESTRICTED RETURN AIR
 OCCURS IN BUILDINGS WHEN RETURNS ARE LOCATED IN CENTRAL
 ZONES AND CLOSED INTERIOR DOORS IMPEDE AIR FLOW TO THE
 RETURN GRILL OR WHEN CEILING SPACES ARE USED AS RETURN
 PLENUMS AND FIRE WALLS RESTRICT AIR MOVEMENT FROM ONE
 PORTION OF THE RETURN PLENUM TO ANOTHER. PROVISIONS
 SHALL BE MADE IN BOTH RESIDENTIAL AND COMMERCIAL
 BUILDINGS TO AVOID UNBALANCED AIR FLOWS AND PRESSURE
 DIFFERENTIALS CAUSED BY RESTRICTED RETURN AIR. PRESSURE
 DIFFERENTIALS ACROSS CLOSED DOORS WHERE RETURNS ARE
 CENTRALLY LOCATED SHALL BE LIMITED TO 0.01 INCH WC (2.5
 PASCALS) OR LESS. PRESSURE DIFFERENTIALS ACROSS FIRE
 WALLS IN CEILING SPACE PLENUMS SHALL BE LIMITED TO 0.01
 INCH WC (2.5 PASCALS) BY PROVIDING AIR DUCT PATHWAYS OR
 AIR TRANSFER PATHWAYS FROM THE HIGH PRESSURE ZONE TO
 THE LOW ZONE.
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-08-14 Cont ID  
Sent By lwagner Date 2013-08-14 Time 07:37 Rev Time 0.00
Received By lwagner Date 2013-08-14 Time 07:33 Sent To  
Notes
2013-08-14 07:38:00NO PLUMBING SHOWN AT THIS TIME.