| Plan Review Stops For Permit 13080209 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2013-08-20 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-08-20 |
Time |
17:27 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-08-06 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2013-08-06 14:19:54 | ADDITIONAL INFORMATION PROVIDED. ALLEQUIPMENT IS TO BE | | | LISTED FOR THE USE AND USED WITHIN THE LISTING. WIRE IN | | | WET LOCATIONS TO BE LISTED FOR THE LOCATION. | | | | | | | | | CALLED CONTRACTOR FOR MORE DETAILS. DID THEY CONSIDER | | | USING PVC FOR CORROSION PROTECTION? ALL EQUIPMENT AND | | | CABLES TO BE LISTD FOR THE USE. CABLES AND CONDUCTORS | | | UNDERGROUND OR IN CONCRETE TO BE WET LOCATION | | | LISTED.PLAN IS NOT CLEAR AS TO HOW POWER AND CONTROL | | | ARE BEING PROVIDED TO GATE ARMS. PROVIDE LISTING | | | INFORMATION AN CUT SHEETS ON EQUIPMENT. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-08-20 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-08-20 |
Time |
17:27 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-08-06 |
Time |
12:57 |
Sent To |
|
|
| Notes |
| 2013-08-20 17:28:17 | TO S HILL | | 2013-08-06 12:57:36 | ROUTED TO ELECTRICAL |
|
|
|