| 2013-08-21 18:31:36 | 700 NORTH DIXIE HIGHWAY - FIRE STATION #7 |
| | PERMIT #13080190 |
| | MASTER #11120073 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES FOR |
| | SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN |
| | POSITION. |
| | |
| | PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT |
| | CONNECTION. |
| | |
| | PROVIDE A 1 ZONE SYSTEM (1 FLOW SWITCH) FOR THE |
| | BUILDING. THERE IS NO NEED FOR A SECOND FLOOR SWITCH |
| | AND THIS WILL BE MISLEADING IF THERE IS AN OPERATING |
| | SECOND FLOOR FLOW SWITCH BECAUSE SEVERAL FIRST FLOOR |
| | SPRINKLERS (TRUCK BAYS AND GENERATOR ROOM) ARE BEING |
| | SUPPLIED FROM THE SECOND FLOOR EVEN THOUGH THE |
| | SPRINKLERS ARE PROTECTING THE FIRST FLOOR. |
| | |
| | NO SPRINKLER PROTECTION PROVIDED IN TWO SMALL CLOSESTS |
| | IN GREAT ROOM #111. |
| | |
| | NO SPRINKLER PROTECTION PROVIDED AT THE TOP OF THE |
| | DUMBWAITER SHAFT. |
| | |
| | PLANS DO NOT INDICATE THE METHOD (HEAT DETECTOR/FLOW |
| | SWITCH WITHOUT TIME DELAY) USED TO SHUNT TRIP POWER TO |
| | THE ELEVATOR IN THE EVENT AN AUTOMATIC SPRINKLER |
| | ACTIVATES IN THE ELEVATOR MACHINE ROOM. |
| | |
| | PROVIDE HYDRAULIC CALCULATIONS FOR THE DRY PIPE |
| | PREACTION SYSTEM. |
| | |
| | HYDRAULIC AREA #1 CALCULATES A MAXIMUM OF 3 SPRINKLERS |
| | ON AN 1-1/4" BRANCHLINE; HOWEVER, THERE ARE ADJACENT |
| | BRANCHLINES WITH AS MUCH AS 6 SPRINKLERS ON A 36 FOOT |
| | SECTION OF BRANCHLINE THAT WILL BE MORE HYDRAULICALLY |
| | DEMANDING. PROVIDE AN ADDITIONAL REDUCED AREA (1192 |
| | SQ.FT.) HYDRAULIC CALCULATION FOR THE UTILITIES CALL |
| | TAKER ROOM #3.22 AREA. |
| | |
| | WESLEY JOLIN |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |