Plan Review Details - Permit 13080168
Plan Review Stops For Permit 13080168
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2013-09-06 Cont ID  
Sent By shill Date 2013-09-06 Time 14:47 Rev Time 0.00
Received By shill Date 2013-09-06 Time 14:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2013-09-03 Cont ID  
Sent By shill Date 2013-09-03 Time 16:45 Rev Time 0.00
Received By shill Date 2013-09-03 Time 16:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-08-22 Cont ID  
Sent By shill Date 2013-08-22 Time 21:33 Rev Time 0.00
Received By shill Date 2013-08-22 Time 21:33 Sent To  
Notes
2013-09-03 16:48:18****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. SEE FBC 1603.1.4, WIND DESIGN CRITERIA, WIND SPEED
 IN BOTH VULT AND VASD TO BE PROVIDED. 150MPH WAS NOT
 CLEAR; VULT OR VASD? MINIMUM FOR THIS LOCATION IS
 170MPH VULT / 132 VASD. PLEASE CLARIFY.
  
 ENGINEER MAY SEND A LETTER OF CLARIFICATION VIA EMAIL.
  
 3RD REVIEW, WIND SPEEDCHANGED BUT EXPOSURE WAS CHANGED
 FROM D TO B. PLEASE SEE THIS STRUCTURE ON AN AERIAL. IF
 YOU BELIEVE THIS IS EXPOSURE B RATHER THAN D, PLEASE
 CALL ME TO DISCUSS PRIOR TO RESUBMITTAL. OTHERWISE,
 REVISE BACK TO EXPOSURE B. THIS STRUCTURE IS LOCATED ON
 THE INTRACOASTAL.
  
  
2013-08-22 21:36:16****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. SEE FBC 1603.1.4, WIND DESIGN CRITERIA, WIND SPEED
 IN BOTH VULT AND VASD TO BE PROVIDED. 150MPH WAS NOT
 CLEAR; VULT OR VASD? MINIMUM FOR THIS LOCATION IS
 170MPH VULT / 132 VASD. PLEASE CLARIFY.
  
 ENGINEER MAY SEND A LETTER OF CLARIFICATION VIA EMAIL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-09 Cont ID  
Sent By shill Date 2013-08-09 Time 16:17 Rev Time 0.00
Received By shill Date 2013-08-09 Time 16:17 Sent To  
Notes
2013-08-09 16:20:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DESIGN PRESSURES ARE TO BE DETERMINED BY A DESIGN
 PROFESSIONAL, ASCE 7-10, FBC 1609 (ARCHITECT OR
 ENGINEER)
  
 2. ON THE PRODUCT APPROVAL, INDICATE GLASS OPTION AND
 FASTENING PROPOSED TO COMPLY WITH DESIGN PRESSURES
 SPECIFIED BY ARCHITECT OR ENGINEER.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-09-03 Cont ID  
Sent By shill Date 2013-09-03 Time 16:48 Rev Time 0.00
Received By shill Date 2013-08-28 Time 16:43 Sent To  
Notes
2013-08-28 16:44:11INCOMING SENT TO SAMS DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-08-22 Cont ID  
Sent By shill Date 2013-08-22 Time 21:36 Rev Time 0.00
Received By shill Date 2013-08-16 Time 17:13 Sent To  
Notes
2013-08-16 17:13:29INCOMING SENT TO SAMANTHAS' DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-09 Cont ID  
Sent By shill Date 2013-08-09 Time 16:20 Rev Time 0.00
Received By shill Date 2013-08-05 Time 15:48 Sent To  
Notes
2013-08-05 15:49:00ROUTED TO MISC 1