Plan Review Details - Permit 13080164
| Plan Review Stops For Permit 13080164 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2013-10-03 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-10-03 |
Time |
07:07 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-10-02 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2013-10-03 07:07:05 | HEAVILY NOTED PLANS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2013-08-08 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2013-08-08 |
Time |
07:10 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-08-08 |
Time |
06:44 |
Sent To |
|
|
| Notes |
| 2013-08-08 07:09:58 | PLAN SHOWS A 100 SWITCH WITH A 125A PANEL. PAPERWORK | | | STATES A NEMA 1 ENCLOSURE AND LOCATION OF TRANSFER | | | SWITCH IS NOT CLEAR. PROVIDE OVERCURRENT PROTECTION | | | LOCATIONS AND SIZES TO DEFINE THE EDGES OF THE SERVICE. | | | BONDING AND GROUNDING TO COMPLY WITH NEC 250 FOR | | | SERVICE RACEWAYS AND FEEDERS. DOES THE GENERATOR HAVE A | | | MAIN BREAKER? WHAT SIZE? WHAT IS THE AIC AVAIALBLE AND | | | WHAT IS THE RATING OF THE EQUIPMENT TO BE INSTALLED? | | | DOES THE INSTALLATION PROVIDE SUFFICIENT WORKING | | | CLEARANCE PER NEC 110.16? INDICATE WHICH APPLIANCES ARE | | | GAS AND WHICH ARE ELECTRIC. INDICATE WHAT APPLIANCES, | | | IF ANY, ARE CONNECTED TO LOAD SHEDDING AND PROVIDE | | | DETAILED LOAD CALCULATION FOR "NORMAL" AND "EMERGENCY" | | | OPERATION. PAPERWORK INDICATES "SELECTED LIGHTING | | | CIRCUITS" AND A SECOND PANEL IS NOT SHOWN. SHOW TYPE OF | | | FUEL SUPPLY AND LOCATION TO FEED GENERATOR. PERMIT | | | REQUIRED FOR INSTALLATION OF FUEL SUPPLY TO GENERATOR. | | | ADDITIONAL COMMENTS MAY RESULT FROM SUBMISSION OF THE | | | REQUIRED PAPERWORK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-10-03 |
|
|
Cont ID |
|
| Sent By |
dharvey |
Date |
2013-10-03 |
Time |
07:07 |
Rev Time |
0.00 |
| Received By |
dharvey |
Date |
2013-10-02 |
Time |
13:05 |
Sent To |
|
|
| Notes |
| 2013-10-03 07:07:25 | TO S HILL | | 2013-10-02 13:05:22 | SENT TO D HARVEY |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-10-02 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-08-08 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-08-05 |
Time |
15:40 |
Sent To |
|
|
| Notes |
| 2013-08-08 07:11:14 | PLACED IN DENIED UNDER "S" DH | | | EMAIL SENT TO CONTRACTOR WITH NOTES | | 2013-08-05 15:40:39 | ROUTED TO ZONING |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2013-08-07 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2013-08-07 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2013-08-07 |
Time |
14:14 |
Sent To |
E |
|
| Notes |
|
|
|