Plan Review Details - Permit 13080146
Plan Review Stops For Permit 13080146
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-11-13 Cont ID  
Sent By skennedy Date 2013-11-13 Time 12:37 Rev Time 0.00
Received By skennedy Date 2013-11-13 Time 12:37 Sent To  
Notes
2013-11-13 12:39:26THE OPEN REVIEW OF 11/4/14 BY MA CANNOT BE CLOSED DUE
 TO UNEXPLAINED COMPUTER ISSUE. CUSTOMER IS WAITING,
 THIS IS TO ASSURE REVIEW WAAS PASSED BY MA ON 11/4/13.

Review Stop E ELECTRICAL
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By albarran Date 2013-11-04 Time 11:34 Sent To  
Notes
2013-11-04 11:59:53SENT TO SH DESK
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-08-05 Cont ID  
Sent By dharvey Date 2013-08-05 Time 17:23 Rev Time 0.00
Received By dharvey Date 2013-08-05 Time 17:20 Sent To Z
Notes
2013-08-05 17:23:36WIND LOAD WAS PERFORMED WITHOUT FIXTURES. PROVIDE
 REVISED ENGINEERED WIND LOAD SHOWING THE FIXTURE AND
 ARMS IN PLACE. PLANS AND ENGINEERING DO NOT AGREE FOR
 POLE INSETION DEPTH.
 PROVIDE CLEAR PHOTOMETRICS OF DESIGN TO ENSURE SAFETY
 AND LIGHTING BEYOND THE PROPERTY LINE DOES NOT EXCEED
 .5 FC AND HOW IT WILL BE ACHIEVED IN ACCORDANCE WITH
 THE LISTING OF THE FIXTURE. CLEARLY IDENTIFY POLE
 LOCATIONS AND FIXTURE CONFIGURATION ON PHOTOMETRIC
 PLAN.
 PHOTOMETRICS APPEAR TO DUPLICATE A PREVIOUS REVIEW.
 PLEASE CLARIFY
 PROVIDE LISTING INFORMATION FOR FIXTURES AND ALL
 COMPONENTS
 PROVIDE VOLTAGE DROP CALCS SHOWING COMPLIANCE WITH
 FBC-EC 505.7.3
 PROVIDE EXTERIOR LIGHTING POWER DENSITY INFORMATION PER
 FBC-EC 505.6
 PROVIDE TIME CLOCK WITH PROGRAMING BACKUP FOR MINIMUM
 10 HOURS PER FBC-EC 505.2.4

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-11-13 Cont ID  
Sent By skennedy Date 2013-11-13 Time 12:33 Rev Time 0.00
Received By skennedy Date 2013-10-22 Time 17:47 Sent To  
Notes
2013-11-06 09:35:1211/6 TO ZONING (NEW SHEET)
  
2013-10-22 17:47:54SENT TO ELECTRICAL SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-30 Cont ID  
Sent By dmalone Date 2013-08-19 Time 15:57 Rev Time 0.00
Received By dmalone Date 2013-08-05 Time 13:58 Sent To  
Notes
2013-08-05 13:59:02ROUTED TO ELECTRICAL

Review Stop Z ZONING
Rev No 2 Status N Date 2013-11-06 Cont ID  
Sent By llouie Date 2013-11-06 Time 16:30 Rev Time 0.00
Received By llouie Date 2013-11-06 Time 16:30 Sent To E
Notes
2013-11-06 16:31:3011/6/13 - ZONING REVIEW NOT REQUIRED PER DENISE MALONE.
 LL

Review Stop Z ZONING
Rev No 1 Status P Date 2013-08-30 Cont ID  
Sent By dmalone Date 2013-08-19 Time 15:57 Rev Time 0.00
Received By dmalone Date 2013-08-08 Time 12:07 Sent To B
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved