Plan Review Details - Permit 13080083
Plan Review Stops For Permit 13080083
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-08-28 Cont ID  
Sent By jgomez Date 2013-08-28 Time 09:29 Rev Time 0.00
Received By jgomez Date 2013-08-28 Time 09:29 Sent To  
Notes
2013-08-28 09:43:03BUILDING REVIEW APPROVED WITH PROVISO (PROVIDE
 INFORMATION PRIOR TO INSPECTION TO AVOID CONFLICTS OR
 DELAYS):
  
 1- PROVIDE PRODUCT APPROVALS FOR:
 A) SHINGLES. NOA 11-1122.04 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS.
  
 2- ENGINEER OF RECORD TO REVIEW ALL PRODUCT APPROVALS.
  
 3- A) REVISE TENANT SEPARATION WALL SECTION. NEED
 TENANT SEPARATION AT FLOOR CEILING AREA. NEED TO
 SPECIFY ASSEMBLY TESTED PER ASTM E 119 OR UL 263 AS
 REQUIRED BY SEC. R302.3 OF 2010 FBC-RESIDENTIAL. AND,
 COORDINATE THIS INFORMATION WITH THE EXISTING TYPICAL
 WALL SECTION SUBMITTED.
 ***NOTE; ASSEMBLY TO INCLUDE INSULATION AS SHOWN ON
 PLANS..
  
 B) PROVIDE SPECIFICATIONS FOR THE FIRE RATING OF THE
 SUPPORTING CONSTRUCTION AS REQUIRED BY SEC. R302.3.1.
  
 C) PROVIDE SPECIFICATIONS FOR THE RATED PENETRATIONS AS
 REQUIRED BY SEC. R302.4.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-08-07 Cont ID  
Sent By jgomez Date 2013-08-07 Time 17:35 Rev Time 0.00
Received By jgomez Date 2013-08-07 Time 17:34 Sent To  
Notes
2013-08-07 17:41:46RESIDENTIAL (R3) RENOVATION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- CLARIFY SCOPE OF WORK. PLANS SUBMITTED DON'T SPECIFY
 SHINGLES RE-ROOF BUT THERE WERE SHINGLES AND
 UNDERLAYMENT PRODUCT APPROVALS SUBMITTED. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 2- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SHINGLES (IF DOING RE-ROOF. SEE COMMENT #1 ABOVE.).
 NOA 11-1122.04 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE.
 NEED CURRENT NOA.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS.
  
 C) WINDOW MULLIONS AS SHOWN ON PLANS.
  
 3- ENGINEER OF RECORD TO REVIEW PRODUCT APPROVALS. SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 4- A) REVISE TENANT SEPARATION WALL SECTION. NEED
 TENANT SEPARATION AT FLOOR CEILING AREA. NEED TO
 SPECIFY ASSEMBLY TESTED PER ASTM E 119 OR UL 263 AS
 REQUIRED BY SEC. R302.3 OF 2010 FBC-RESIDENTIAL. AND,
 COORDINATE THIS INFORMATION WITH THE EXISTING TYPICAL
 WALL SECTION SUBMITTED.
 ***NOTE: ASSEMBLY TO INCLUDE INSULATION AS SHOWN ON
 PLANS.
  
 B) PROVIDE SPECIFICATIONS FOR THE FIRE RATING OF THE
 SUPPORTING CONSTRUCTION AS REQUIRED BY SEC. R302.3.1.
  
 C) PROVIDE SPECIFICATIONS FOR THE RATED PENETRATIONS AS
 REQUIRED BY SEC. R302.4.
  
 5- BEDROOM WINDOWS: CLEARLY IDENTIFY ON PLANS TYPE AND
 SIZE OF EXISTING WINDOWS TO VERIFY COMPLIANCE WITH THE
 EGRESS REQUIREMENTS OF SEC. 601.2 OF 2010 FBC-EXISTING
 BUILDING.
  
 6- SPECIFY HOW PROVIDING HEAT AS REQUIRED BY SEC.
 R303.8.
  
 7- PROVIDE ENERGY CALCULATIONS. SEC. 103.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-09-10 Cont ID  
Sent By dharvey Date 2013-09-09 Time 06:53 Rev Time 0.00
Received By dharvey Date 2013-09-09 Time 06:24 Sent To  
Notes
2013-09-09 06:53:15MIKE WITH HURRICANE PROVIDED REVISIONS SUITABLE FOR
 ISSUANCE. PLANS RE-REVIEWED AND SIGNED OFF. DH 9/10/13
  
  
  
 LOAD CALULATION AND RISER DO NOT AGREE - ONE SHOWS 400A
 AND ONE SHOWS 200A
 PROVIDE INTERSYSTEM BONDING POINT PER 250.94
 PROVIDE 3 WAY SWITCH AT STEPS
 NO CLOSETS ARE SHOWN IN THE BEDROOMS. PLEASE LOCATE
 SMOKE ALARMS IN ACCORDANCE WITH MANUFACTURERS
 SPECIFICATIONS FOR BEST COVERAGE AND EARLIEST DETECTION
 PROVIDE CALCULATION SHOWING 22K AIC GEAR AND CLARIFY
 RATING OF THE METER CAN. WHAT IS DOWNSTREAM LETTHROUGH?
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-09-03 Cont ID  
Sent By dharvey Date 2013-09-03 Time 16:30 Rev Time 0.00
Received By dharvey Date 2013-09-03 Time 16:17 Sent To  
Notes
2013-09-03 16:30:04SERVICE CALCULATION IS NOT PER NEC 220. UNITS HAVE A
 125A SERVICE AND OVERALL LOAD CALC SHOWS 57.5 A. NO
 HEAT IS PROVIDED.
 PROVIDE DETAILED CUT SHEET ON A/C UNITS SHOWING ACTUAL
 LOAD AND CIRCUIT REQUIRED PER THE LISTING. 110.3, 430,
 440
 WIRE SIZES DO NOT MATCH OVERCURRENT PROTECTION -
 310.15, 310.15, 240.6
 PROVIDE AIC CALCULATIONS AND/OR VALUES FOR METER CENTER
 AND ELECTRIC LOAD CENTERS. 110.
 PROVIDE ARC FLASH WARNINGS PER 110.26
 PLANS NOT COMPLETE, ADDITIONAL ITEMS MAY BE NOTED BASED
 ON RESPONSES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-08-13 Cont ID  
Sent By rmcdouga Date 2013-08-13 Time 08:35 Rev Time 0.00
Received By rmcdouga Date 2013-08-13 Time 07:25 Sent To  
Notes
2013-08-13 08:31:562010 FBC / 2008 NEC
 TWO FAMILY DWELLING
  
 DENIED BY ELECTRICAL
  
 1) NEC 230.2 REQUIRES ONE SERVICE FOR THIS BUILDING AND
 THE PLANS SHOW TWO SEPARATE SERVICES. PLEASE REVISE THE
 RISER DIAGRAM.
  
 2) PROVIDE A HOUSE LOAD CALCULATION IN COMPLIANCE WITH
 NEC 220.84 (B) AND 220.85 TO DETERMINE THE SERVICE
 LOAD. THIS IS IN ADDITION TO THE DWELLING UNIT LOADS
 CALCULATED IN COMPLIANCE WITH NEC 220.40.
  
 3) THE CALCULATIONS THAT WERE SUBMITTED HAVE AN ERROR
 IN THE ADDITION FOR THE TOTAL LOAD. IT SHOULD BE 26,000
 WATTS. THIS IS EQUAL TO 108 AMPS. BASED ON YOUR
 CALCULATIONS THE SPECIFIED PANEL SIZE OF 100 AMPS IS
 TOO SMALL PER NEC 220.40. PLEASE CORRECT.
  
 4) THERE IS NO WATER HEATER INDICATED ON THE PLANS OR
 WATER HEATER CIRCUIT SHOWN IN THE PANEL SCHEDULE FOR
 THE SECOND FLOOR UNIT. IF THE INTENT IS FOR BOTH UNITS
 TO SHARE ONE WATER HEATER IT SHOULD BE LOCATED IN A
 COMMON AREA AND FEED FROM A METER THAT SERVICES THE
 COMMON AREAS. OTHERWISE, THE OCCUPANT IN UNIT ONE IS
 PAYING TO HEAT THE WATER FOR UNIT TWO. THIS APPEARS TO
 BE IN VIOLATION OF FBCR P2801.1 PLEASE CLARIFY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-09-09 Cont ID  
Sent By dharvey Date 2013-09-09 Time 06:54 Rev Time 0.00
Received By dharvey Date 2013-09-05 Time 07:46 Sent To  
Notes
2013-09-09 06:54:07PLACED IN DENIED FILE UNDER "H" DH
2013-09-06 07:47:05SENT TO D HARVEY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-09-04 Cont ID  
Sent By dharvey Date 2013-09-04 Time 07:03 Rev Time 0.00
Received By dharvey Date 2013-08-16 Time 16:50 Sent To  
Notes
2013-09-04 07:04:22PLACED IN DENIED UNDER "H"
2013-08-16 16:50:30INCOMING SENT TO R24 BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-08-13 Cont ID  
Sent By jgomez Date 2013-08-13 Time 15:16 Rev Time 0.00
Received By jgomez Date 2013-08-02 Time 13:45 Sent To  
Notes
2013-08-13 15:16:53ZONING REVIEW DONE ON 8/13/13. JG.
2013-08-05 13:45:39**** E X P E D I T E D ****
  
 R21
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-08-28 Cont ID  
Sent By jgomez Date 2013-08-28 Time 10:04 Rev Time 0.00
Received By jgomez Date 2013-08-28 Time 10:04 Sent To  
Notes
2013-08-28 10:05:28PLUMBING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE CLEAR AND CORRECT PLUMBING RISER DIAGRAM
 THAT MATCHES PLANS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-08-07 Cont ID  
Sent By jgomez Date 2013-08-07 Time 18:09 Rev Time 0.00
Received By jgomez Date 2013-08-07 Time 18:09 Sent To  
Notes
2013-08-07 18:10:03RESIDENTIAL (R3) RENOVATION, PLUMBING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PLUMBING RISER DIAGRAM SUBMITTED DOESN'T MATCH
 FIXTURE LAYOUT SHOWING ON THE FLOOR PLAN. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop Z ZONING
Rev No 2 Status P Date 2013-08-27 Cont ID  
Sent By aaponte Date 2013-08-27 Time 11:46 Rev Time 0.00
Received By aaponte Date 2013-08-27 Time 11:46 Sent To  
Notes
2013-08-27 11:49:05PROVISO: LA DRAWINGS SHALL BE SUBMITTED BEFORE CO.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status F Date 2013-08-13 Cont ID  
Sent By aaponte Date 2013-08-13 Time 11:56 Rev Time 0.00
Received By aaponte Date 2013-08-13 Time 11:56 Sent To  
Notes
2013-08-13 11:59:451. SURVEY INDICATES ONE ADDITIONAL EXTERIOR STAIR.
 DRAWINGS DO NOT SHOW OR INDICATE PROPOSED DEMOLITION.
 2. LANDSCAPE DRAWINGS SHALL BE SUBMITTED.
 3. TWO UNITS ALLOWED ON 422 10 STREET, 1 UNIT ALLOWED
 ON 420 10 STREET, AND 1 UNIT ALLOWED ON 418 10TH
 STREET.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.