| 2013-09-19 13:59:49 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: 2010 FBC. |
| | |
| | 1- A) ENGINEER OF RECORD SIGNED AND SEALED PLANS ON THE |
| | WRONG SPACE IN THE TITLE BLOCK, NOT UNDER HIS NAME AND |
| | LICENSE NUMBER SPACE. HE SIGNED THE SPACE FOR "SSC |
| | DESIGN GROUP", WHICH IS AN ARCHITECTURAL FIRM THAT |
| | DOESN'T HAVE A FLORIDA FIRM LICENSE NUMBER. RESUBMIT |
| | DRAWINGS WITH SIGNATURE ON CORRECT SPACE AS REQUIRED BY |
| | CHAPTER 471 FLORIDA STATUTE. |
| | |
| | B) ENGINEER OF RECORD TO SIGN AND SEAL ALL PLANS |
| | SUBMITTED AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE. |
| | SOME DRAWINGS ARE MISSING THE SEAL AND SIGNATURE. |
| | |
| | 2- NEED ARCHITECTURAL FIRM FLORIDA LICENSE NUMBER FOR |
| | "SSC DESIGN GROUP" AS REQUIRED BY CHAPTER 481 FLORIDA |
| | STATUTE. (REPEAT COMMENT). OR REMOVE NAME FROM TITLE |
| | BLOCK. |
| | |
| | 3- REVISE ENERGY CALCULATIONS SUBMITTED. SEC. |
| | 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | A) REVISE THE AREA WEIGHTED AVERAGE OVERHANG DEPTH ON |
| | ITEM #7 TO MATCH PLANS (IT'S NOT 2.000FT). |
| | |
| | B) REVISE ROOF MATERIAL ON PAGE 2 OF 7. THERE ARE NOT |
| | SHINGLES ON THE HOUSE. |
| | |
| | C) REVISE ALL DOORS ON PAGE 4 OF 7 TO MATCH PLANS AND |
| | PRODUCT APPROVALS SUBMITTED. REVISE TYPE, SIZE ETC. TO |
| | MATCH PLANS. |
| | |
| | D) REVISE ALL WINDOWS TO MATCH PLANS AND PRODUCT |
| | APPROVALS. AND REVISE THE OVERHANG DEPTH AND SEPARATION |
| | TO MATCH PLANS. |
| | |
| | E) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING THE CORRECT BUILDER'S NAME. |
| | |
| | 4- PROVIDE DETAILS AND SPECIFICATIONS ON PLANS SHOWING |
| | HOW OBTAINING R-13 ON CONCRETE BLOCK WALLS FOR INTERIOR |
| | AND EXTERIOR WALLS AS SPECIFIED ON THE ENERGY |
| | CALCULATIONS SUBMITTED. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | 5- ENERGY CALCULATIONS SUBMITTED ARE TAKING THE CEILING |
| | FAN CREDIT. SPECIFY ON PLANS CEILING FAN SIZE FOR ALL |
| | ROOMS AS REQUIRED BY SEC. 405.6.6 OF 2010 FBC-ENERGY |
| | CONSERVATION AND TABLE 405.6.6. |
| | |
| | 6- REVISE/COORDINATE ALL WINDOW AND DOOR SCHEDULE |
| | INFORMATION TO MATCH THE ENERGY CALCULATIONS. MATERIAL |
| | TYPE ETC. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) PRECAST LINTELS AS SPECIFIED ON PLANS. NEED 8" |
| | PRECAST LINTEL. NOA 13-0321.07 SUBMITTED IS FOR 4", 6" |
| | & 12" LINTELS. |
| | |
| | B) INSWING WOOD DOOR AS SHOWN ON PLANS FOR NEW CABANA |
| | BATHROOM. (REPEAT COMMENT). |
| | |
| | C) ENTRY DOORS THAT MEET THE CALCULATED DESIGN |
| | PRESSURES. FLORIDA PRODUCT APPROVAL FL9390-R2 SUBMITTED |
| | DOESN'T MEET THE DESIGN PRESSURES. |
| | |
| | D) WINDOW MULLIONS AS SHOWN ON PLANS. AND SPECIFY SIZE |
| | TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES. (REPEAT |
| | COMMENT). |
| | |
| | E)FIXED WINDOWS. NOA 11-1110.15 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA. |
| | ***NOTE: ALSO, NEED PRODUCT APPROVAL FOR ALL WINDOW |
| | SIZES SHOWN ON PLANS. SEE WINDOW SCHEDULE. (REPEAT |
| | COMMENT). |
| | |
| | 8- ABOVE PRODUCT APPROVALS TO BE REVIEWED AND APPROVED |
| | IN WRITING BY THE ENGINEER OF RECORD (NOT SIGNING AND |
| | SEALING). SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. |
| | |
| | 9- SPECIFY CARBON MONOXIDE ALARMS FOR ALL BEDROOM AS |
| | REQUIRED BY SEC. R315. (REPEAT COMMENT). |
| | |
| | 10- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE |
| | INSTALLATION OF SHUTTERS. NEED THIS INSTALLATION |
| | SCHEDULE TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES |
| | OF PRODUCT APPROVAL PROPOSED INSTALLATION AND THE |
| | DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3. (REPEAT |
| | COMMENT) |
| | |
| | |
| | ***NOTE: PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |
| | |
| | ****NOTE: PROVIDE COMPLETE INFORMATION UNDER SEPARATE |
| | PERMITS FOR: POOL WORK, NEW GENERATOR, SCREEN ENCLOSURE |
| | WORK, GAS WORK, ETC. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |